GE UR Series Manual page 210

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

MEMORY MAP
F400
UR_UINT16: CT/VT BANK SELECTION
Bitmask
Bank selection
0
Card 1 Contact 1 to 4
1
Card 1 Contact 5 to 8
2
Card 2 Contact 1 to 4
2
3
Card 2 Contact 5 to 8
4
Card 3 Contact 1 to 4
5
Card 3 Contact 5 to 8
F450
UR_UINT16: AMBIENT SENSOR TYPES
This is a dynamic format code that is populated at initialization
with transducer types as specified in the order code.
F460
UR_UINT16: TOP-OIL SENSOR TYPES
This is a dynamic format code that is populated at initialization
with transducer types as specified in the order code.
F470
UR_UINT16: TRANSFORMER REFERENCE WINDING SELEC-
TION
F490
UR_UINT16: HI-SPEED CONTACTS
Off, available contact outputs
F491
ENUMERATION: ANALOG INPUT MODE
0 = Default Value, 1 = Last Known
F500
UR_UINT16: PACKED BITFIELD
First register indicates input/output state with bits 0 (MSB) to 15
(LSB) corresponding to input/output state 1 to 16. The second reg-
ister indicates input/output state with bits 0 to 15 corresponding
to input/output state 17 to 32 (if required). The third register indi-
cates input/output state with bits 0 to 15 corresponding to input/
output state 33 to 48 (if required). The fourth register indicates
input/output state with bits 0 to 15 corresponding to input/output
state 49 to 64 (if required).
The number of registers required is determined by the specific
data item. A bit value of 0 = Off and 1 = On.
0 = Off, 1 = On
2-190
CHAPTER 2: MODBUS COMMUNICATION
F501
UR_UINT16: LED STATUS
Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates the
LED is on, 0 indicates the LED is off.
0 = Off, 1 = On
F502
BITFIELD: ELEMENT OPERATE STATES
Each bit contains the operate state for an element. See the F124
format code for a list of element IDs. The operate bit for element
ID X is bit [X mod 16] in register [X/16].
F513
ENUMERATION: POWER SWING MODE
0 = Two Step, 1 = Three Step
F514
ENUMERATION: POWER SWING TRIP MODE
0 = Delayed, 1 = Early
F515
ENUMERATION ELEMENT INPUT MODE
0 = SIGNED, 1 = ABSOLUTE
F516
ENUMERATION ELEMENT COMPARE MODE
0 = LEVEL, 1 = DELTA
F517
ENUMERATION: ELEMENT DIRECTION OPERATION
0 = OVER, 1 = UNDER
F518
ENUMERATION: FLEXELEMENT UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
F519
ENUMERATION: NON-VOLATILE LATCH
0 = Reset-Dominant, 1 = Set-Dominant
F521
ENUMERATION: GROUND DISTANCE POLARIZING CURRENT
0 = Zero-Sequence, 1 = Negative-Sequence
UR SERIES – COMMUNICATIONS GUIDE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents