CHAPTER 3: IEC 61850 COMMUNICATION
SCL LOG MESSAGES
E3-2.0 ERROR: Couldn't add dummy DOType
This message is logged when a data object type cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add dummy DAType
This message is logged when a data attribute cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add ConnectedAP to the dummy ied
This message is logged when a ConnectedAP cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add GSE to the dummy ied
3
This message is logged when GSE section cannot be added to dummy IED. A dummy IED is created for each remote IED.
The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add IED to the dummy ied
This message is logged when an IED section cannot be added to dummy IED. A dummy IED is created for each remote IED.
The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add LD to the dummy ied
This message is logged when a logical device cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add LLN0 to the dummy ied
This message is logged when LLN0 logical node cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add GSEControl=<cbName in LGOS> to the dummy ied
This message is logged when GSEControl section cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: datSet=<dataset name> and datSet=<dataset name> map to same GSEControl=<cbName in
LGOS>
This message is logged when two different dataset mapped to a same GSEControl. The GOOSE subscription parsing is in
progress at this stage.
E3-2.0 ERROR: Couldn't add dataset=<dataset name> to the dummy ied
This message is logged when dataset cannot be added to dummy IED. A dummy IED is created for each remote IED. The
GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add FCDA to the dummy ied
This message is logged when FCDAs cannot be added to dummy IED. A dummy IED is created for each remote IED. The
GOOSE subscription parsing is in progress at this stage.
E3-2.0 ERROR: Couldn't add GGIO1 to the dummy ied
This message is logged when GGIO1 logical node cannot be added to dummy IED. A dummy IED is created for each remote
IED. The GOOSE subscription parsing is in progress at this stage.