MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Bkr0XCBR#
LNName:
data attribute
data obj.
InRef4
setSrcRef
setSrcCB
InRef8
setSrcRef
setSrcCB
InRef5
setSrcRef
setSrcCB
InRef6
3
setSrcRef
setSrcCB
InRef7
setSrcRef
setSrcCB
Table 3-93: Breaker control data objects
LNName:
BkrΘXCBR#
data attribute
data obj.
Loc
stVal
OpCnt
stVal
units
units.SIUnit
units.multiplier
BadSt1
stVal
ClsSt1
stVal
OpnSt1
stVal
IntermSt1
stVal
Pos
stVal
ctlModel
BlkOpn
stVal
ctlModel
BlkCls
stVal
ctlModel
InRef1
3-92
System
LDevice inst:
Type
FC UR Name
ORG
SP BREAKER # BLK CLOSE
ObjectReference
SP
ObjectReference
ORG
SP XCBR# SYNCCHECK CLS
ObjectReference
SP
ObjectReference
ORG
SP BREAKER # EXT ALARM
ObjectReference
SP
ObjectReference
ORG
SP BREAKER # OUT OF SV
ObjectReference
SP
ObjectReference
ORG
SP XCBR# ST.LOC OPERAND
ObjectReference
SP
ObjectReference
LDevice inst:
System
Type
FC UR Name
SPS
ST Bkr0XCBR#.Loc.stVal
BOOLEAN
INS
ST
INT32
CF
Unit
ENUMERATED
ENUMERATED
SPS
ST BREAKER # ψ BAD ST
BOOLEAN
SPS
ST BREAKER # ψ CLSD
BOOLEAN
SPS
ST BREAKER # ψ OPEN
BOOLEAN
SPS
ST BREAKER # ψ INTERM
BOOLEAN
DPC
ST
CODED ENUM
CF
CtlModels
SPC
ST Bkr0XCBR#.BlkOpn.stVal
BOOLEAN
CF
CtlModels
SPC
ST Bkr0XCBR#.BlkCls.stVal
BOOLEAN
CF
CtlModels
ORG
CHAPTER 3: IEC 61850 COMMUNICATION
Breaker Control element #
UR element:
Description
BREAKER # BLK CLOSE setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
XCBR# SYNCCHECK CLS setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
BREAKER # EXT ALARM setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
BREAKER # OUT OF SV (out-of-service)
setting.
Reference to the data attribute to input
Source GoCB of input if via GOOSE
XCBR# ST.LOC OPERAND (local control)
setting.
Reference to the data attribute to input
Source GoCB of input if via GOOSE
UR element:
Breaker Control element #
Description
Value of operand selected by setting XCBR#
ST.LOC OPERAND
Phase ψ breaker operations counter
1, the code for dimensionless
0, the code for a multiplier of 1
BREAKER # ψ BAD ST operand
BREAKER # ψ CLSD operand
BREAKER # ψ OPEN operand
BREAKER # ψ INTERM operand
Breaker φψ position status
0, the code for status-only
Breaker open commands blocked from all
sources including protection
0, the code for status-only
Breaker close commands blocked from all
sources including protection
0, the code for status-only
BREAKER # φA/3P CLSD setting" if Θ="1",
"BREAKER # φB CLSD setting" if Θ="2", or
"BREAKER # φC CLSD setting" if Θ="3
UR SERIES – COMMUNICATIONS GUIDE
R/W/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents