GE G30 Instruction Manual

GE G30 Instruction Manual

Generator protection system 7.4x
Hide thumbs Also See for G30:
Table of Contents

Advertisement

GE
Grid Solutions
G30
Generator Protection System
Instruction Manual
Product version: 7.4x
GE publication code: 1601-0166-AE3 (GEK-130981B)
E83849
LISTED
IND.CONT. EQ.
52TL
1601-0166-AE3

Advertisement

Table of Contents
loading

Summary of Contents for GE G30

  • Page 1 Grid Solutions Generator Protection System Instruction Manual Product version: 7.4x GE publication code: 1601-0166-AE3 (GEK-130981B) E83849 LISTED IND.CONT. EQ. 52TL 1601-0166-AE3...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3: Table Of Contents

    Environmental........................2-36 2.5.12 Type tests ..........................2-37 2.5.13 Production tests ........................2-37 2.5.14 Approvals ..........................2-38 2.5.15 Maintenance.........................2-38 3 INSTALLATION Unpack and inspect..................3-1 Panel cutouts....................3-2 3.2.1 Horizontal units ........................3-2 3.2.2 Vertical units ........................... 3-3 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 4 3.7.5 Automatic discovery of UR devices................3-61 Connect to the G30..................3-62 3.8.1 Connect to the G30 in EnerVista................. 3-62 3.8.2 Use Quick Connect via the front panel RS232 port..........3-63 3.8.3 Use Quick Connect via a rear Ethernet port............3-64 Set up CyberSentry and change default password .........3-64...
  • Page 5 System setup ....................5-125 5.5.1 AC inputs ..........................5-125 5.5.2 Power system........................5-126 5.5.3 Signal sources........................5-127 5.5.4 Transformer ........................5-130 5.5.5 Breakers..........................5-141 5.5.6 Disconnect switches ......................5-145 5.5.7 FlexCurves...........................5-148 FlexLogic......................5-155 5.6.1 FlexLogic operands ......................5-155 5.6.2 FlexLogic rules ........................5-166 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 6 5.11.1 Test mode function ......................5-299 5.11.2 Test mode forcing......................5-299 5.11.3 Force contact inputs ..................... 5-300 5.11.4 Force contact outputs ....................5-300 6 ACTUAL VALUES Actual Values menu..................6-1 Front panel......................6-3 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 7 TARGETS 7.1.1 Virtual inputs........................... 7-2 7.1.2 Clear records .......................... 7-2 7.1.3 Set date and time......................... 7-3 7.1.4 Relay maintenance......................7-3 7.1.5 Security ............................. 7-4 Targets menu ....................7-4 7.2.1 Target messages ........................7-5 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 8 11.8 Upgrade firmware ..................11-12 11.9 Replace module....................11-13 11.10 Battery ......................11-14 11.10.1 Replace battery for SH/SL power supply ............. 11-14 11.10.2 Dispose of battery ......................11-15 11.11 Clear files and data after uninstall............11-19 11.12 Repairs......................11-19 viii G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 9 A.1 FlexAnalog items .....................A-1 OPERANDS B RADIUS SERVER B.1 RADIUS server configuration ................. B-1 CONFIGURATION C COMMAND LINE C.1 Command line interface .................C-1 INTERFACE D MISCELLANEOUS D.1 Warranty ......................D-1 D.2 Revision history ....................D-1 ABBREVIATIONS INDEX G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 10 TABLE OF CONTENTS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 11: Introduction

    Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on the relay nameplate. Do not apply current or voltage in excess of the specified limits. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 12: For Further Assistance

    Fax: +1 905 927 5098 Worldwide e-mail: multilin.tech@ge.com Europe e-mail: multilin.tech.euro@ge.com Website: http://www.gegridsolutions.com/multilin When contacting GE by e-mail, optionally include a device information file, which is generated in the EnerVista software by clicking the Service Report button. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 13 CHAPTER 1: INTRODUCTION FOR FURTHER ASSISTANCE Figure 1-1: Generate service report G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 14 FOR FURTHER ASSISTANCE CHAPTER 1: INTRODUCTION G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 15: Product Description

    The Ethernet port supports IEC 61850, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any standard web browser (G30 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
  • Page 16 PRODUCT DESCRIPTION CHAPTER 2: PRODUCT DESCRIPTION The G30 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are upgradable. The following single-line diagrams illustrate the relay functionality using American National Standards Institute (ANSI) device numbers.
  • Page 17 CHAPTER 2: PRODUCT DESCRIPTION PRODUCT DESCRIPTION Figure 2-2: Single-line diagram PTS on transformer LV side (protection assigned to generator neutral CTS) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 18 Percent differential Virtual outputs (96) DNP 3.0 or IEC 60870-5-104 protocol Setting groups (6) VT fuse failure Ethernet Global Data Protocol Time synchronization over IRIG-B or IEEE 1588 Event recorder Time synchronization over SNTP G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 19: Security

    The G30 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear communications port.
  • Page 20 |--------------- Clear Relay Records (settings) |--------------- Communications |--------------- Modbus User Map |--------------- Real Time Clock |--------------- Oscillography |--------------- Data Logger |--------------- Demand |--------------- User-Programmable LEDs |--------------- User-Programmable Self Tests |--------------- Control Pushbuttons RW |--------------- User-Programmable Pushbuttons G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 21 |---------- Front panel labels designer |---------- Status |---------- Metering |---------- Transducer I/O |---------- Records |---------- Product Info Maintenance |---------- Modbus Analyzer |---------- Change front panel |---------- Update firmware |---------- Retrieve file Table Notes: G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 22: Order Codes

    The order code is on the product label and indicates the product options applicable. The G30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit. It consists of the following modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay communications.
  • Page 23: Order Codes With Enhanced Ct/Vt Modules

    CHAPTER 2: PRODUCT DESCRIPTION ORDER CODES 2.3.1 Order codes with enhanced CT/VT modules Table 2-4: G30 order codes for horizontal units - * ** - * * * - F ** - H ** - M ** - P **...
  • Page 24 Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels Table 2-5: G30 order codes for reduced-size vertical units - * ** - * * * - F ** - H **...
  • Page 25 820 nm, multimode, LED, 1 Channel 1300 nm, multimode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 1300 nm, single-mode, LASER, 1 Channel Channel 1 - G.703; Channel 2 - 820 nm, multimode G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-11...
  • Page 26: Order Codes With Process Bus Modules

    G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels 2.3.2 Order codes with process bus modules Table 2-6: G30 order codes for horizontal units with process bus - * ** - * * * - F ** - H **...
  • Page 27 Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels Table 2-7: G30 order codes for reduced-size vertical units with process bus - * ** - * * * - F ** - H **...
  • Page 28 Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, Laser 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode Laser G.703, 1 Channel G.703, 2 Channels RS422, 1 Channel 7W RS422, 2 Channels 2-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 29: Replacement Modules

    Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the serial number of your existing unit. Not all replacement modules apply to the G30 relay. The modules specified in the order codes for the G30 are available as replacement modules for the G30.
  • Page 30 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels 820 nm, multimode, LED, 1 Channel 1300 nm, multimode, LED, 1 Channel 1300 nm, single-mode, ELED, 1 Channel 2-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 31: Signal Processing

    (when applicable), and auxiliary voltages. The 2.4 kHz cut-off frequency applies to both 50 Hz and 60 Hz applications and fixed in the hardware, and thus is not dependent on the system nominal frequency setting. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-17...
  • Page 32 The A/D converter has the following ranges of AC signals: Voltages: Eq. 2-1 Currents: Eq. 2-2 Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through 25th are estimated. 2-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 33: Specifications

    ICD/CID/IID files, and so on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, CyberSentry (advanced cyber security), the Parallel Redundancy Protocol (PRP), IEC 60870-5-103, and so on. 2.5 Specifications Specifications are subject to change without notice. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-19...
  • Page 34: Protection Elements

    > 2.0 × CT: ±1.5% of reading > 2.0 × CT rating Curve shapes: IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse, Short/Very/ Extremely Inverse; I t; FlexCurves™ (programmable); Definite Time (0.01 s base curve) Curve multiplier: Time Dial = 0.00 to 600.00 in steps of 0.01...
  • Page 35 0.00 to 250.00 Ω in steps of 0.01 Pickup level: 0.015 to 30.000 pu in steps of 0.01 Dropout level: 97 to 98% <16 ms at 3 × pickup at 60 Hz Operation time: G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-21...
  • Page 36 ±3.5% of operate time or ±1/2 cycle (whichever is greater) from pickup to operate Operate time: <30 ms at 0.9 pickup at 60 Hz for Definite Time mode THIRD HARMONIC NEUTRAL UNDERVOLTAGE Operating quantity: 3rd harmonic of auxiliary undervoltage 2-22 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 37 <30 ms at 1.10 × pickup at 60 Hz VOLTS PER HERTZ Voltage: Phasor only Pickup level: 0.80 to 4.00 in steps of 0.01 pu V/Hz Dropout level: 97 to 98% of pickup Level accuracy: ±0.02 pu G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-23...
  • Page 38 0 to 65.535 s in steps of 0.001 Reset delay: 0 to 65.535 s in steps of 0.001 Timer accuracy: ±3% of operate time or ±1/4 cycle (whichever is greater) 95% settling time for df/dt: <24 cycles 2-24 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 39 0.000 to 1.250 pu in steps of 0.001 Accuracy: ±0.5% of reading from 10 to 208 V Pickup delay: 0 to 65.535 s in steps of 0.001 Timer accuracy: ±3% of operate time or ±20 ms, whichever is greater G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-25...
  • Page 40: User-Programmable Elements

    20 ms to 60 days Pickup and dropout delay: 0.000 to 65.535 s in steps of 0.001 NON-VOLATILE LATCHES Type: set-dominant or reset-dominant Number: 16 (individually programmed) Output: stored in non-volatile memory 2-26 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 41: Monitoring

    64 samples per power cycle Triggers: any element pickup, dropout, or operate; contact input change of state; contact output change of state; FlexLogic equation Data: AC input channels; element state; contact input state; contact output state G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-27...
  • Page 42: Metering

    Accuracy at 0.1 to 1.5 x CT rating and 0.8 to 1.2 x VT rating: ±1.0% of reading WATT-HOURS (POSITIVE AND NEGATIVE) Accuracy: ±2.0% of reading Range: ±0 to 1 × 10 Parameters: three-phase only Update rate: 50 ms 2-28 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 43: Inputs

    260 V to neutral 1 min/hr at 420 V to neutral FREQUENCY Nominal frequency setting: 25 to 60 Hz Sampling frequency: 64 samples per power cycle Tracking frequency range: 3 to 70 Hz G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-29...
  • Page 44 Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1 Unreturned message alarm: Responding to: Rate of unreturned messages in the ring configuration 2-30 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 45: Power Supply

    Make and carry for 0.2 s: 30 A as per ANSI C37.90 Carry continuous: Break (DC inductive, L/R = 40 ms): Voltage Current 24 V 48 V 0.5 A 125 V 0.3 A 250 V 0.2 A G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-31...
  • Page 46 Note: values for 24 V and 48 V are the same due to a required 95% voltage drop across the load impedance. Operate time: < 0.6 ms Internal Limiting Resistor: 100 Ω, 2 W 2-32 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 47: Communication Protocols

    19.2 or 115.2 kbps, Modbus RTU RS485 1 rear port: up to 115 kbps, Modbus RTU, DNP 3, IEC 60870-5-103 Typical distance: 1200 m Isolation: 2 kV, isolated together at 36 Vpk G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-33...
  • Page 48: Inter-Relay Communications

    Emitter, fiber type Cable type Transmit power Received Power budget Maximum sensitivity optical input power 820 nm, Multimode 62.5/125 μm -16 dBm -32 dBm 16 dBm -8 dBm 50/125 μm -20 dBm 12 dBm 2-34 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 49 Typical distances listed are based on the following assumptions for system loss. As actual losses vary from one installation to another, the distance covered by your system can vary. CONNECTOR LOSSES (TOTAL OF BOTH ENDS) ST connector: 0.7 dB (each) FIBER LOSSES 820 nm multimode: 3 dB/km G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-35...
  • Page 50: Cybersentry Security

    95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6 days) OTHER Altitude: 2000 m (maximum) Pollution degree: Overvoltage category: Ingress protection: IP20 front, IP10 back Noise: 0 dB 2-36 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 51: Type Tests

    Insulation: class 1, Pollution degree: 2, Over voltage cat II 1 Not tested by third party. 2.5.13 Production tests THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-37...
  • Page 52: Approvals

    Normally, cleaning is not required. When dust has accumulated on the faceplate display, wipe with a dry cloth. To avoid deterioration of electrolytic capacitors, power up units that are stored in a de-energized state once per year, for one hour continuously. 2-38 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 53: Installation

    For any issues, contact GE Grid Solutions as outlined in the For Further Assistance section in chapter 1. Check that you have the latest copy of the G30 Instruction Manual and the UR Family Communications Guide, for the applicable firmware version, at http://www.gegridsolutions.com/multilin/manuals/index.htm...
  • Page 54: Panel Cutouts

    Maintenance > Change Front Panel. 3.2.1 Horizontal units The G30 is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 55: Vertical Units

    3.2.2 Vertical units The G30 is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 56 PANEL CUTOUTS CHAPTER 3: INSTALLATION Figure 3-4: Vertical dimensions (enhanced panel) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 57 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-5: Vertical and mounting dimensions (standard panel) For side-mounting G30 devices with the enhanced front panel, see the following documents available on the UR DVD and the GE Grid Solutions website: • GEK-113180 — UR-Series UR-V Side-Mounting Front Panel Assembly Instructions •...
  • Page 58 PANEL CUTOUTS CHAPTER 3: INSTALLATION For side-mounting G30 devices with the standard front panel, use the following figures. Figure 3-6: Vertical side-mounting installation (standard panel) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 59 CHAPTER 3: INSTALLATION PANEL CUTOUTS Figure 3-7: Vertical side-mounting rear dimensions (standard panel) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 60: Rear Terminal Layout

    (nearest to CPU module), indicated by an arrow marker on the terminal block. The figure shows an example of rear terminal assignments. Figure 3-8: Example of modules in F and H slots G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 61: Wiring

    CPU modules are installed in slots B and D of the chassis with 13 inch-pounds of torque on the screws at the top and bottom of the modules. 3.3 Wiring 3.3.1 Typical wiring Figure 3-9: Typical wiring diagram (T module shown for CPU) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 62 WIRING CHAPTER 3: INSTALLATION Figure 3-10: Typical wiring diagram, PTS on the transformer LV-side (T module shown for CPU) 3-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 63: Dielectric Strength

    3.3.2 Dielectric strength Dielectric strength is the maximum electric strength that can be sustained without breakdown. It is measured in volts. The table shows the dielectric strength of the UR-series module hardware. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-11...
  • Page 64: Control Power

    The power supply module can be ordered for two possible voltage ranges, and the G30 can be ordered with or without a redundant power supply module option. Each range has a dedicated input connection for proper operation. The ranges are as follows (see the Specifications section of chapter 2 for details): •...
  • Page 65: Ct/Vt Modules

    These modules have enhanced diagnostics that can automatically detect CT/VT hardware failure and take the relay out of service. CT connections for both ABC and ACB phase rotations are identical, as shown in the Typical Wiring Diagram. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-13...
  • Page 66 UR models. Substitute the tilde “~” symbol with the slot position of the module in the following figure. Figure 3-14: CT/VT module wiring 3-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 67: Process Bus Modules

    3.3.5 Process bus modules The G30 can be ordered with a process bus interface module. The module interfaces with the HardFiber Process Bus System, or HardFiber Brick, allowing bidirectional IEC 61850 fiber optic communications with up to eight HardFiber Bricks.
  • Page 68 Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears, substitute the contact number. 3-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 69 ~6a, ~6c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-17...
  • Page 70 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used 3-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 71 CHAPTER 3: INSTALLATION WIRING Figure 3-16: Contact input and output module wiring (Sheet 1 of 2) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-19...
  • Page 72 CHAPTER 3: INSTALLATION Figure 3-17: Contact input and output module wiring (Sheet 2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output connections. 3-20 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 73 G30 input even when the output is open, if there is a substantial distributed capacitance (represented by C1) present in the wiring between the output and the G30 input and the debounce time setting in the G30 relay is low enough.
  • Page 74 This example is for illustrative purposes only and the calculations present the worst-case scenario. In practice, the value of debounce time can be lower. Contact input ON state impedance used in the calculation of the discharge period is based on the following table. 3-22 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 75 Eq. 3-2 The 2 mA current is used in case the contact input is connected across the GE Form A contact output with voltage monitoring. Otherwise use the amperage of the active circuit connected to the contact input when its contact output is open and the voltage across the contact input is third trigger threshold to calculate the resistor value.
  • Page 76 The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP switch for each contact, for a total of 16 inputs. Figure 3-22: Auto-burnish DIP switches 3-24 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 77 In case of external devices that are susceptible to parasitic capacitance of long cable runs affected by switching surges from external circuits, that can cause inadvertent activation of contact inputs with the external contact open, GE recommends using the Digital I/O module with active impedance circuit.
  • Page 78: Transducer Inputs And Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay. Where a tilde “~” symbol appears, substitute the slot position of the module. Figure 3-24: Transducer input/output module wiring The following figure show how to connect RTDs. 3-26 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 79: Rs232 Faceplate Port

    EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors. The baud rate for this port can be set, with a default of 115200 bps. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-27...
  • Page 80: Cpu Communication Ports

    Figure 3-26: RS232 faceplate port connection 3.3.9 CPU communication ports 3.3.9.1 Overview In addition to the faceplate RS232 port, there is a rear RS485 communication port. The CPU modules do not require a surge ground connection. 3-28 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 81 This common voltage is implied to be a power supply common. Some systems allow the shield (drain wire) to be used as common wire and to connect directly to the G30 COM terminal (#3); others function correctly only if the common wire is connected to the G30 COM terminal, but insulated from the shield.
  • Page 82: Irig-B

    IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices. The IRIG-B code allows time accuracies of up to 100 ns. Using the IRIG-B input, the G30 operates an internal oscillator with 1 µs resolution and accuracy.
  • Page 83: Direct Input And Output Communications

    UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx to UR1-Rx. A maximum of 16 URs can be connected in a single ring. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-31...
  • Page 84 UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the first ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second ring. 3-32 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 85 Those that apply depend on options purchased. The options are outlined in the Inter-Relay Communications section of the Order Code tables in Chapter 2. All of the fiber modules use ST type connectors. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-33...
  • Page 86: Fiber: Led And Eled Transmitters

    The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser modules. Figure 3-35: 7x Laser fiber modules The following figure shows configuration for the 2I and 2J fiber-laser modules. 3-34 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 87: Interface

    The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrangement of these pins, see the Rear Terminal Layout section earlier in this chapter. All pin interconnections are to be maintained for a connection to a multiplexer. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-35...
  • Page 88 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module is inserted fully. 3-36 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 89 (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). The switch settings for the internal and loop timing modes are shown. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-37...
  • Page 90 One source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface. Figure 3-42: G.703 dual loopback mode 3-38 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 91: Rs422 Interface

    (data module 1) connects to the clock inputs of the UR RS422 interface in the usual way. In G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-39...
  • Page 92 Figure 3-45: Timing configuration for RS422 two-channel, three-terminal application Data module 1 provides timing to the G30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure because they vary by manufacturer.
  • Page 93: Rs422 And Fiber Interface

    For the direct fiber channel, address power budget issues properly. When using a laser interface, attenuators can be necessary to ensure that you do not exceed maximum optical input power to the receiver. Figure 3-47: RS422 and fiber interface connection G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-41...
  • Page 94: And Fiber Interface

    Connection — as per all fiber optic connections, a Tx to Rx connection is required The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports the IEEE C37.94 standard. The figure shows the concept. 3-42 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 95 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of G30 communication for two and three terminal applications.
  • Page 96 When the clips have locked into position, the module is inserted fully. Figure 3-52: IEEE C37.94 timing selection switch setting Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. 3-44 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 97: C37.94Sm Interface

    Fiber optic cable length — Up to 11.4 km • Fiber optic connector — Type ST • Wavelength — 1300 ±40 nm • Connection — As per all fiber optic connections, a Tx to Rx connection is required G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-45...
  • Page 98 5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of G30 communication for two and three terminal applications.
  • Page 99 When the clips have locked into position, the module is inserted fully. Figure 3-55: C37.94SM timing selection switch setting Modules shipped since January 2012 have status LEDs that indicate the status of the DIP switches, as shown in the following figure. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-47...
  • Page 100: Activate Relay

    Press the right arrow until the message displays. MESSAGE SECURITY Press the down arrow until the message displays. MESSAGE INSTALLATION Press the right arrow until the Not Programmed message displays. MESSAGE RELAY SETTINGS: 3-48 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 101: Install Software

    To communicate via the faceplate RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to the relay and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports section earlier in this chapter. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-49...
  • Page 102: System Requirements

    This device (catalog number F485) connects to the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the G30 rear communications port. The converter terminals (+, –, GND) are connected to the G30 communication module (+, –, COM) terminals. See the CPU Communication Ports section in chapter 3 for details.
  • Page 103: Install Software

    Click the Next button to begin the installation. The files are installed in the directory indicated, and the installation program automatically creates icons and adds an entry to the Windows start menu. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-51...
  • Page 104: Add Device To Software

    3.7 Add device to software You connect remotely to the G30 through the rear RS485 or Ethernet port with a computer running the EnerVista UR Setup software. The G30 also can be accessed locally with a computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 105 From the Windows desktop, right-click the My Network Places icon and select Properties to open the network connections window. Or in Windows 7, access the Network and Sharing Center in the Control Panel. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-53...
  • Page 106 Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button. Click the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the G30 relay and the last number different (in this example, 1.1.1.2).
  • Page 107 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: verify the physical connection between the G30 and the computer, and double-check the programmed IP address in setting, then repeat step 2. Product Setup  Communications  Network  IP Address...
  • Page 108 If this computer is used to connect to the Internet, re-enable any proxy server settings after the computer has been disconnected from the G30 relay. Start the Internet Explorer software. Select the UR device from the EnerVista Launchpad to start EnerVista UR Setup. 3-56 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 109 Click the Quick Connect button to open the window. Select the Ethernet interface and enter the IP address assigned to the G30, then click the Connect button. The EnerVista UR Setup software creates a site named “Quick Connect” with a corresponding device also named “Quick Connect”...
  • Page 110: Configure Serial Connection

    For the RS232 connection, a computer with an RS232 port and a serial cable are required. To use the RS485 port at the back of the relay, a GE Grid Solutions F485 converter (or compatible RS232-to-RS485 converter) is required. See the F485 instruction manual for details.
  • Page 111: Configure Ethernet Connection

    SEL-2032. This option enables display of a terminal window to allow interaction with the other device. 11. Click the Read Order Code button to connect to the G30 and upload the order code to the software. If a communications error occurs, ensure that the EnerVista software serial communications values entered in the previous step correspond to the relay setting values, and also ensure that the same IP address is not assigned to multiple G30 ports.
  • Page 112 12. If using a gateway to connect to the device, select Yes from the drop-down list. 13. Click the Read Order Code button to connect to the G30 device and upload the order code. If the device was entered already, a message displays "Device ’x’ is also using IP address.." If a communications error occurs, ensure that the values entered in the previous steps correspond to the relay setting values, and also ensure that the same IP address is not assigned to multiple G30 ports.
  • Page 113: Configure Modem Connection

    CHAPTER 3: INSTALLATION ADD DEVICE TO SOFTWARE The device has been configured for Ethernet communications. Proceed to the Connect to the G30 section to begin communications. 3.7.4 Configure modem connection A modem connection allows a computer to communicate with a UR device over phone lines.
  • Page 114: Connect To The G30

    When unable to connect because of an "ACCESS VIOLATION," access Device Setup and refresh the order code for the device. When unable to connect, ensure that the same IP address is not assigned to multiple G30 ports, for example under Settings > Product Setup > Communications > Network.
  • Page 115: Use Quick Connect Via The Front Panel Rs232 Port

    Connect a nine-pin to nine-pin RS232 serial cable to the computer and the front panel RS232 port. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista DVD or online from http://www.gegridsolutions.com/multilin). See the software installation section if not already installed.
  • Page 116: Use Quick Connect Via A Rear Ethernet Port

    Connect" and displays them in the Online Window. Expand the sections to view data directly from the G30 device. Use the Device Setup button to change the site name. Each time that the EnerVista software is initialized, click the Quick Connect button to establish direct communications to the G30.
  • Page 117: Import Settings

    If required, change the Files of type drop-down list. Select the file to import. To apply the settings to a live device, drag-and-drop the device entry from the Offline Window area to its entry in the Online Window area. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 3-65...
  • Page 118 IMPORT SETTINGS CHAPTER 3: INSTALLATION Individual settings also can be dragged and dropped between Online and Offline Window areas. The order codes much match. 3-66 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 119: Interfaces

    The EnerVista UR Setup software is provided with every G30. This chapter outlines the EnerVista software interface features. The EnerVista UR Setup Help File also provides details for getting started and using the software interface.
  • Page 120: Event Viewing

    IP Address IP Subnet Mask IP Routing When a settings file is loaded to a G30 that is in-service, the following sequence occurs: The G30 takes itself out of service. The G30 issues a UNIT NOT PROGRAMMED major self-test error.
  • Page 121: File Support

    Settings list / offline window area Software windows, with common tool bar Settings file data view windows, with common tool bar Workspace area with data view tabs Status bar 10. Quick action hot links G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 122: Protection Summary Window

    4.1.6 Protection summary window The Protection Summary is a graphical user interface to manage elements, such as enabling and disabling them. Access it under Settings > Protection Summary. See the Settings chapter for information on use. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 123: Settings Templates

    Right-click the selected device or settings file and select the Template Mode > Create Template option. The settings file template is now enabled and the file menus displayed in light blue. A message displays. The settings file is now in template editing mode. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 124 Figure 4-4: Settings template with all settings specified as locked Specify the settings to make viewable by clicking them. A setting available to view is displayed against a yellow background. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 125 To display only the settings available for editing: Select an installed device or a settings file from the left menu of the EnerVista UR Setup window. Apply the template by selecting the Template Mode > View In Template Mode option. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 126 Once the template has been applied, users are limited to edit the settings specified by the template, but all settings are shown. The effect of applying the template to the phase time overcurrent settings is shown as follows. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 127: Secure And Lock Flexlogic Equations

    4.1.8.1 Lock FlexLogic equations To lock individual entries of a FlexLogic equation: Right-click the settings file or online device and select the Template Mode > Create Template item to enable the settings template feature. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 128 The effect of applying the template to the FlexLogic entries is shown here. Figure 4-10: Locking FlexLogic entries through settings templates The FlexLogic entries are also shown as locked in the graphical view and on the front panel display. 4-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 129 Right-click the setting file in the offline window area and select the Edit Device Properties item. The window opens. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-11...
  • Page 130: Settings File Traceability

    When a settings file is transferred to a G30 device, the date, time, and serial number of the G30 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This information can be compared with the G30 actual values at any later date to determine if security has been compromised.
  • Page 131 With respect to the figure, the traceability feature is used as follows. The transfer date of a settings file written to a G30 is logged in the relay and can be viewed in the EnerVista software or the front panel display. Likewise, the transfer date of a settings file saved to a local computer is logged in the EnerVista software.
  • Page 132 4.1.9.2 Online device traceability information The G30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista online window as shown in the example.
  • Page 133: Front Panel Interface

    The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the front panel. To view the front panel in EnerVista software: Click Actual Values > Front Panel. Figure 4-18: Front panel use in the software (C60 shown) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-15...
  • Page 134: Front Panel Keypad

    MESSAGE arrow from a header display displays specific information for the category. Conversely, continually pressing the MESSAGE left arrow from a setting value or actual value display returns to the header display. 4-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 135: Changing Settings

    TIME: 10.0 s MESSAGE TIME setting.  MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the key again to view the MAXIMUM: 10.0 next context sensitive help message. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-17...
  • Page 136 Flash messages appear sequentially for several HELP seconds each. For the case of a text setting message, pressing displays how to edit and store new values. HELP 4-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 137: Faceplate

    The following figure shows the horizontal arrangement of the faceplate panel. Figure 4-21: Standard horizontal faceplate The following figure shows the vertical arrangement of the faceplate panel for relays ordered with the vertical option. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-19...
  • Page 138: Led Indicators

    RESET latched conditions can also be reset via the menu). SETTINGS  INPUT/OUTPUTS  RESETTING keys are used by the breaker control feature. USER Figure 4-23: Typical LED panel for enhanced faceplate 4-20 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 139 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label package of every G30, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 140 NEUTRAL/GROUND — Indicates that neutral or ground was involved User-programmable indicators The second and third panels provide 48 amber LED indicators whose operation is controlled by the user. Support for applying a customized label beside every LED is provided. 4-22 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 141: Custom Led Labeling

    EnerVista UR Setup software is installed and operational • The G30 settings have been saved to a settings file • The UR front panel label cutout sheet (GE part number 1006-0047) has been downloaded from http://www.gegridsolutions.com/products/support/ur/URLEDenhanced.doc and printed • Small-bladed knife To create custom LED labels for the enhanced front panel display: Start the EnerVista UR Setup software.
  • Page 142 Select the Front Panel Label Designer item from the Online Window or Offline Window area, for example under Settings > Front Panel Label Designer. If the option does not display, it means that the G30 does not have an enhanced front panel or that no customization is possible. The Online Window has the advantage of displaying the live fields as opposed to blank fields.
  • Page 143 Bend the tab at the center of the tool tail as shown. To remove the LED labels from the G30 enhanced front panel and insert the custom labels: Use the knife to lift the LED label and slide the label tool underneath. Ensure that the bent tabs are pointing away from the relay.
  • Page 144 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown. To remove the user-programmable pushbutton labels from the G30 enhanced front panel and insert the custom labels: Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown. Ensure that the bent 4-26 G30 GENERATOR PROTECTION SYSTEM –...
  • Page 145 Remove the tool and attached user-programmable pushbutton label. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-27...
  • Page 146: Breaker Control

    4.2.9 Breaker control The G30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, that can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from the faceplate keypad or automatically initiated from a FlexLogic operand.
  • Page 147: Change Passwords

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the G30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 148: Invalid Password Entry

    By default, when an incorrect Command or Setting password has been entered via the faceplate interface three times within five minutes, the FlexLogic operand is set to “On” and the G30 does not allow settings or LOCAL ACCESS DENIED command level access via the faceplate interface for five minutes.
  • Page 149: Logic Diagrams

    Not. Negates/reverses the output, for example 0 becomes 1.  Connection  S, R Set, Reset Timer pickup. Triggered by the settings latch in the diagram. Timer reset. Triggered by the reset latch in the diagram. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-31...
  • Page 150: Flexlogic Design And Monitoring Using Engineer

    Works with all UR firmware versions The figure shows an example where several inputs are used to trigger an output. With the OR function, any one of the inputs can trigger the output. 4-32 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 151 This section explains how to use Engineer. It outlines the following topics: • Design logic • Send file to and from device • Monitor logic • View front panel • Generate connectivity report • Preferences G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-33...
  • Page 152: Design Logic

    Preparation — Under Settings > Inputs/Outputs > Virtual Outputs, virtual outputs 3 and 4 are named DLTrigger Top logic — Seven-minute timer trigger Bottom logic — Turn on LED 9 for 10 seconds when the trigger starts 4-34 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 153 This procedure uses input / output logic as an example. To create a logic diagram: In the Offline Window area, access Engineer for the device, then Logic Designer. If the device is not listed, right-click G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-35...
  • Page 154 Add the input blocks to the logic diagram. For example, click the I/O Tokens tab on the right, click the Input element, then click in the logic sheet to add it. Or drag-and-drop it. 4-36 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 155 Line option. The cursor needs to be at the connection point to end the line, not elsewhere on the block. Note that the outline color is no longer red on the blocks. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-37...
  • Page 156 The warning "input using disabled feature" means that input needs to be enabled. Double-click the block, click the View Associated Screen button, enable the setting, save, and recompile. The output and messages are explained in the next section. 4-38 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 157 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated. The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders.
  • Page 158 The same timer is used in more than one place in the editor. This means (TIMER_ID, SheetReference) either the circuit that the Timer belongs to has been branched, or the Timer has been duplicated. 4-40 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 159 Click the Ok button to save and exit from the window. In the logic diagram, select an element, then click in the drawing area to add it, click again to add a second box, and so on. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-41...
  • Page 160 Optimization Summary. Changes also display when the FlexLogic Equation Editor is accessed. The logic diagram does not change. In the example shown, no lines were saved to free up space. Figure 4-45: Code optimization results 4-42 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 161 Type in the second text string box, or select any of the 32 previous searches from the drop-down list. Click the Search button. Any results display. The search applies to all tabs, not just the active tab. Double-click a search result to view the item. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-43...
  • Page 162: Send File To And From Device

    When a window opens, select the device to which you want to send the file, then click the Send button and confirm. The order codes must match. The file is sent to the live device. Any errors can be viewed in the log file at the prompt. 4-44 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 163: Monitor Logic

    (green box outline). In this case, the battery is weak and needs to be replaced. This can be viewed as the Replace Battery message on the front panel of the device and in the EnerVista software under Actual Values > Front Panel > Front Panel or Display/Keypad. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-45...
  • Page 164: View Front Panel And Print Labels

    To save the report and labels, click File > Save As, enter a file name, and select the FPR, JPG, or PDF format. Use the instructions in the second tab of the window to add the labels to the physical device. 4-46 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 165: Generate Connectivity Report

    View > Toolbar > Advanced Actions — Active when in Logic Designer. Toggles a toolbar to nudge, rotate, flip, or change the order of an element. View > Show Unused Pins — Enable to display unconnected pins. Disable to eliminate unconnected pins from the view, for example when printing. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-47...
  • Page 166 File Information The text entered here displays at the bottom right of a diagram when printing, provided that the Show Title Block option is enabled. Note the option to change the logo from the GE logo to your company logo. Display The panel sets how the element boxes display.
  • Page 167 The software displays the color specified when an element is on. There is no color when the element is off. The software displays another color when the status cannot be determined and is unknown. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-49...
  • Page 168 Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status. 4.4.6.4 COMTRADE waveforms Waveform files are viewable in the EnerVista software. The preferences are unrelated to Engineer and are outlined in the UR Family Communications Guide. 4-50 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 169: Toolbars

    When you re-launch the EnerVista software, communication is on by default. 4.4.7.2 Token Toolbox Drawing Tools Draw a line. Click and drag to draw. Draw multiple joined lines. Click and drag for each line. Double-click to finish. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-51...
  • Page 170 Remote inputs from other devices Input from another UR device. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously. Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive and cannot be used simultaneously. 4-52 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 171 Tag-In can is used to reference an existing Tag-Out. It joins another diagram to a previous diagram. Boolean Tokens These symbols are used to create FlexLogic Equations. Use them as intermediate logic for the Virtual Output equations. The display can vary from that shown here. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-53...
  • Page 172 Place a positive one shot and a negative one shot symbol in the Logic Designer diagram Place a timer in the Logic Designer diagram Elements These blocks configure properties of the element or use element operands as input to FlexLogic equations. 4-54 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 173 Set the width of the selected components to the same width as the reference component Same Height Set the height of the selected components to the same height as the reference component G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4-55...
  • Page 174 Front, Back Moves current components to the absolute front or back of all viewable layers Forward, Backward Moves current components on layer higher or lower than its original layer hierarchy 4-56 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 175: Settings

     FAULT REPORT  OSCILLOGRAPHY See page 5-99    DATA LOGGER See page 5-102    USER-PROGRAMMABLE See page 5-103   LEDS  USER-PROGRAMMABLE See page 5-106   SELF TESTS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 176 See page 5-178   GROUPED ELEMENTS   SETTING GROUP 2     SETTING GROUP 3    SETTING GROUP 4    SETTING GROUP 5   G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 177  RTD INPUTS See page 5-294     DCMA OUTPUTS See page 5-295     SETTINGS TEST MODE Range: Disabled, Isolated, Forcible   TESTING FUNCTION: Disabled See page 5-299 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 178: Overview

    For example, on a system with a 13.8 kV nominal primary voltage, the base quantity is 13800 V. With 14400:120 V delta- connected VTs, the secondary base quantity and secondary voltage setting is: Eq. 5-1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 179: Introduction To Ac Sources

    A given source can contain all or some of the following signals: three-phase currents, single-phase ground current, three-phase voltages, and an auxiliary voltage from a single VT for checking for synchronism. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 180 RMS levels, fundamental frequency phasors, symmetrical components, and harmonics for voltage or current, as allowed by the hardware in each channel. These modules can calculate other parameters as directed by the CPU module. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 181: Product Setup

    Password security and EnerVista security are disabled. Lost password If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default values, not just the passwords. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 182 CHAPTER 5: SETTINGS To reset the unit after a lost password: Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email account. Customer service provides a code to reset the relay to the factory defaults.
  • Page 183 When entering a settings or command password via EnerVista or any serial interface, the user must enter the corresponding connection password. If the connection is to the back of the G30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 184 SETTINGS  PRODUCT SETUP  SECURITY  ACCESS SUPERVISION  ACCESS  ACCESS LEVEL See below   SUPERVISION  TIMEOUTS INVALID ATTEMPTS Range: 2 to 5 in steps of 1  BEFORE LOCKOUT: 3 5-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 185 INVALID ATTEMPTS BEFORE LOCKOUT The G30 provides a means to raise an alarm upon failed password entry. If password verification fails while accessing a password-protected level of the relay (either settings or commands), the FlexLogic operand is UNAUTHORIZED ACCESS asserted.
  • Page 186 The status of this timer updates every five seconds. 5.3.1.3 EnerVista security Enable the security management system The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista. 5-12 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 187 If you force password entry by using this feature, ensure that you know the Administrator password. If you do not know the password and are locked out of the software, contact GE Grid Solutions for the default password of a UR device.
  • Page 188 The EnerVista security management system must be enabled (the Enable Security check box enabled) To modify user privileges: Select the Security > User Management item from the top menu to open the user management window. Locate the username in the User field. 5-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 189 This feature requires a CyberSentry software option. See the Order Codes section in chapter 2 for details. The EnerVista software provides the means to configure and authenticate the G30 access using either a server or the device. Access to functions depends on user role.
  • Page 190 When the "Device" button is selected, the G30 uses its local authentication database and not the RADIUS server to authenticate the user. In this case, it uses built-in roles (Administrator, Engineer, Supervisor, Operator, Observer, or Administrator and Supervisor when Device Authentication is disabled), as login accounts and the associated passwords are stored on the G30 device.
  • Page 191 Figure 5-3: Security panel when CyberSentry installed For the Device > Settings > Product Setup > Supervisory option, the panel looks like the following. Figure 5-4: Supervisory panel For the Security panel, the following settings are available. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-17...
  • Page 192 Administrator is to re-enable Device authentication when Device authentication is disabled. To re-enable Device authentication, the Supervisor unlocks the device for setting changes, and then the Administrator can re- enable Device authentication. 5-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 193 LOGIN: Range: Administrator, Engineer, Supervisor,   None Operator, Factory (for factory use only), None  CHANGE LOCAL See page 5-20   PASSWORDS  SESSION See page 5-21   SETTINGS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-19...
  • Page 194 • Observer — This role has read-only access to all G30 settings. This role allows unlimited concurrent access but it has no download access to any files on the device. Observer is the default role if no authentication has been done to the device.
  • Page 195 In Device authentication mode, the Observer role does not have a password associated with it. In Server authentication mode the Observer role requires a password. If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry, the default password is "ChangeMe1#".
  • Page 196 SETTINGS  PRODUCT SETUP  SECURITY  SUPERVISORY  SELF TESTS  SELF TESTS  FAILED See below    AUTHENTICATE FIRMWARE LOCK: Range: Enabled, Disabled  Enabled SETTINGS LOCK: Range: Enabled, Disabled  Enabled 5-22 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 197 After making any required changes, log out. When changing settings offline, ensure that only settings permitted by the role that performs the settings download are changed because only those changes are applied. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-23...
  • Page 198 Clear Energy command (not applicable to all UR products) Clear Unauthorized Access command Clear Teleprotection Counters command (not applicable to all UR products) Clear All Relay Records command Role Log in Role Log off 5-24 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 199: Display Properties

    CHAPTER 5: SETTINGS PRODUCT SETUP In addition to supporting syslog, a G30 with CyberSentry also saves the security events in two local security files, these being SECURITY_EVENTS.CSV and SETTING_CHANGES.LOG. Details on these files and how to retrieve them are available in the EnerVista software under Maintenance >...
  • Page 200 Some customers prefer very low currents to display as zero, while others prefer the current to display even when the value reflects noise rather than the actual signal. The G30 applies a cut-off value to the magnitudes and angles of the measured currents.
  • Page 201: Clear Relay Records

    Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user- programmable pushbuttons to clear specific records is a typical application for these commands. Since the G30 responds to rising edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
  • Page 202: Communications

    Range: 0 to 1000 ms in steps of 10  MIN TIME: 0 ms , and — The G30 is equipped with two independent serial communication RS232 BAUD RATE RS485 COM2 BAUD RATE PARITY ports. The faceplate RS232 port is intended for local use and has two options for baud rate. The rear COM2 port is RS485 and has settings for baud rate and parity.
  • Page 203 5.3.4.3 Ethernet network topology The G30 has three Ethernet ports. Each Ethernet port must belong to a different network or subnetwork. Configure the IP address and subnet to ensure that each port meets this requirement. Two subnets are different when the bitwise AND operation performed between their respective IP address and mask produces a different result.
  • Page 204 SCADA is provided through LAN2. P2 and P3 are connected to LAN2, where P2 is the primary channel and P3 is the redundant channel. In this configuration, P3 uses the IP and MAC addresses of P2. Figure 5-6: Multiple LANs, with redundancy 5-30 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 205 IP addresses and mask. Configure the network IP and subnet settings before configuring the routing settings. To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiating information, such as the serial number and order code of your device.
  • Page 206 2 is performed. The delay in switching back ensures that rebooted switching devices connected to the G30, which signal their ports as active prior to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active again, port 3 returns to standby mode.
  • Page 207 UR 7 redundancy Failover is selected for redundancy. 5.3.4.6 Parallel Redundancy Protocol (PRP) The G30 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 208 The default route is used as the last choice when no other route towards a given destination is found.  DEFAULT IPv4 ROUTE GATEWAY ADDRESS: Range: standard IPV4 unicast address format   127.0.0.1  IPv4 NETWORK RT1 DESTINATION: Range: standard IPV4 address format   ROUTE 1 127.0.0.1 5-34 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 209 (RtGwy & Prt1Mask) == (Prt1IP & Prt1Mask) || (RtGwy & Prt2Mask) == (Prt2IP & Prt2Mask) || (RtGwy & Prt3Mask) == (Prt3IP & Prt3Mask) where & is the bitwise-AND operator == is the equality operator || is the logical OR operator G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-35...
  • Page 210 PRT2 IP ADDRESS = 10.1.2.2 PRT2 SUBNET IP MASK = 255.255.255.0 IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1 STATIC NETWORK ROUTE 1: RT1 DESTINATION = 10.1.3.0/24; RT1 NET MASK = 255.255.255.0; and RT1 GATEWAY = 10.1.2.1 5-36 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 211 0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change takes effect when the G30 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
  • Page 212 Modbus, IEC 61850 Channel 2: RS485 Channel 1: RS485 Modbus Modbus, IEC 61850 Channel 2: none IEC 104 Modbus Modbus IEC 104, Modbus, IEC 61850 IEC 103 Modbus IEC 103 Modbus, IEC 61850 5-38 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 213 Range: 1 to 10080 min. in steps of 1  PERIOD: 1440 min DNP MESSAGE FRAGMENT Range: 30 to 2048 in steps of 1  SIZE: 240 DNP OBJECT 1 Range: 1, 2  DEFAULT VARIATION: 2 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-39...
  • Page 214  COMMUNICATIONS  PROTOCOL multiple DNP masters (usually an RTU or a SCADA master station). Since the G30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the G30 at one time.
  • Page 215 DNP ADDRESS unique address to each DNP slave. The G30 can specify a maximum of five clients for its DNP connections. These are IP addresses for the controllers to which the G30 can connect. The settings follow. SETTINGS  PRODUCT SETUP  COMMUNICATIONS  DNP PROTOCOL  DNP NETWORK CLIENT ADDRESSES ...
  • Page 216 DNP TCP connection for greater than the time specified by this setting, the connection is aborted by the G30. This frees up the connection to be re-used by a client. Any change takes effect after cycling power to the relay.
  • Page 217 The maximum number of simultaneous clients supported by the UR family is five. EnerVista setup for IEC 61850 The EnerVista UR Setup software provides the interface to configure G30 settings for the IEC 61850 protocol. This section describes this interface. The software also supports import/export and merging of IEC 61850 Substation Configuration Language (SCL) files as documented in the UR Family Communications Guide.
  • Page 218 Figure 5-11: IEC 61850 panel Opening the IEC 61850 window while online causes the UR Setup software to retrieve and import an SCL file from the G30. This System Configuration Description (SCD) file contains all the settings in the UR at the time of the file request, both those that are mapped into the IEC 61850 information model (that is, the "public"...
  • Page 219 When the Save button is clicked in the online IEC 61850 window, UR Setup software prepares a configured IED description (CID) file containing all the settings of the UR and sends the CID file to the G30. Upon receipt, the G30 checks the CID file for correctness, going out of service, then back into service when the CID file is accepted.
  • Page 220 Default: TEMPLATE The value entered sets the IED name used by IEC 61850 for the G30. An IED name unique within the network must be entered for proper operation. Valid characters are upper and lowercase letters, digits, and the underscore (_) character.
  • Page 221 Range: status-only, direct-with-normal-security, sbo-with-normal-security Default: sbo-with-normal-security This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the G30. An "on" control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to Forcible, and a "test/blocked"...
  • Page 222 Protection logical device has been set to instance name "Prot", the function-related name "Feeder1Prot" and the configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The next paragraphs explain how to do this setup. 5-48 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 223 Figure 5-15: Menu for logical node If the insert option is selected, or the edit option is selected for other than the Master logical device, a logical device parameters edit dialog opens. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-49...
  • Page 224 Each logical device inst name is required to be unique within the device, and it cannot be blank. Also, if the corresponding functional ldName setting is blank, the concatenation of the IED name and the logical device 5-50 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 225 The UR increments the value of paramRev by one whenever one or multiple setting changes occurs in one Modbus write request by any means (front panel, Modbus, or MMS) other than by SCL file G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-51...
  • Page 226 Routable GOOSE (R-GOOSE) is supported in firmware release 7.4 and later. Routable GOOSE allows UR and other devices to be located in separate networks. Encryption/decryption of messages is performed by a separate gateway device. Messages are routed using a separate router, using IP addresses. Note the following behavior: 5-52 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 227 The UR does not implement the Fixed-Length encoded GOOSE messages option specified in IEC 61850-8-1:2011 clause A.3; the UR always uses the ASN.1 Basic encoding rules (as specified in ISO/IEC 8825-1) as specified in IEC 61850 edition 1.0 and as optional in IEC 61850 edition 2.0. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-53...
  • Page 228 TxGOOSE1 messages from other GOOSE messages. <LDName> is a syntactic variable that is set to the value of setting Master functional ldName if one or more characters have been entered to that setting, otherwise the value of setting IED NAME suffixed with "Master". 5-54 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 229 Network devices can forward a message with a higher priority value before a message with a lower priority value, which speeds delivery of high-priority messages in heavily loaded networks. The standard recommends that higher-priority messages, such as GOOSE, have priority values in the range of 4 to 7. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-55...
  • Page 230 Range: 1 to 60 s in steps of 1 s Default: 60 s This setting specifies the time interval between heartbeat messages, meaning messages that are sent periodically while no events are detected. 5-56 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 231 61850-90-5 R GOOSE service can be subscribed to. The UR accepts both the variable length encoded GOOSE messages specified IEC 61850 8 1:2004 and the Fixed-Length encoded GOOSE messages as specified in IEC 61850 8 1:2011 clause A.3. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-57...
  • Page 232 RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 does not check the value received in the goID field. If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's TxGOOSE GoID setting. 5-58 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 233 <GoCBName> is the name of the publishing control block. The G30 translates the ACSI format required for this setting to the MMS format used in GOOSE messages: <LDName>/LLN0$GO$<GoCBName> If the publisher is a UR 7.3x or 7.40 series device, <LDName> is the value of the publisher's Master functional ldName setting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master".
  • Page 234 If the publisher is a UR 7.3x or 7.40 series device, set these settings to match the basic type of the members of the publisher's data set selected by the publisher's TxGOOSE datSet setting. 5-60 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 235 SCD (supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. The figure shows a selection being made by importing a CID file using the Add IED function. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-61...
  • Page 236 This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the publisher. The following choices are available: 5-62 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 237 Range: None, RxGOOSE1, RxGOOSE2, and so on Default: None This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to None, the RxGOOSE DPS1 FlexLogic operand assumes its default state. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-63...
  • Page 238 (supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the user select the ones to add. Figure 5-23: RxGOOSE Analog Inputs panel There are 32 RxGOOSE analog inputs. 5-64 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 239 Range: 0.000 to 1000000000.000 in steps of 0.001 Default: 1.000 This setting specifies the per-unit base value for other G30 features to use with the RxGOOSE Analog1 operand. A FlexElement for instance subtracts two quantities after converting their values to integers rescaled to a common base, the common base being the largest of the base values of the two quantities.
  • Page 240 RptEna attribute is false. Buffered and unbuffered reports Navigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports or Unbuffered Reports. 5-66 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 241 Also, the control block can be configured to send integrity reports containing the present value of all members either on demand from the client or periodically. A TCP handshaking mechanism causes messages that are not read and acknowledged by the client to be retransmitted. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-67...
  • Page 242 Control blocks and data sets can be pre-configured by sending the G30 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to select the data set members and to pre-configure the control blocks.
  • Page 243 This setting selects the data set whose members' status is reported in Unbuffered Report1 messages using the UR Setup software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as described later. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-69...
  • Page 244 DataSets Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets. 5-70 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 245 The DataSet name is not copied or pasted. In short, use this feature to copy a DataSet Member setting and paste it into another Member setting, a text file, or Word, as examples. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-71...
  • Page 246 Select the member from the drop-down list. Or right-click an entry to copy, paste, delete, or insert. Product setup Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup. 5-72 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 247 Deadband parameters of measured values related to the Energy metering are configured here. Real Time Clock Navigate to Settings > Product Setup > Communications > IEC 61850 > Product Setup > Real Time Clock. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-73...
  • Page 248 However, a tabulation of the analog values and their associated deadband setting can be found in the UR Family Communications Guide. Figure 5-30: Deadband settings with .db suffix 5-74 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 249 Navigate to Settings > Communications > IEC 61850 > System Setup > Breakers > Breaker 1 to access the settings that configure the IEC 61850 protocol interface with the first breaker control and status monitoring element. The settings and functionality for the others are similar. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-75...
  • Page 250 SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of either BkrCSWI1.Pos or Bkr0XCBR1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-interlocking. 5-76 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 251 This setting specifies the maximum time between an operate command to breaker 1 via BkrCSWI1.Pos until BkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached in the set time. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-77...
  • Page 252 If a SelectWithValue or Operate service with ctlVal true and with Check.Interlock-check true is requested of DiscCSWI1.Pos or Disc0XSWI1.Pos and the selected operand is not activated, a Negative Response (-Rsp) is issued with the REASON CODE of Blocked-by-interlocking. 5-78 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 253 > System Setup section later. These signals force a disconnect switch trip or close control while the operand selected by setting XSWI1 ST.LOC OPERAND is not active. "sbo" here is select-before-operate. Enhanced security means that the G30 reports to the client the disconnect switch 1 position the end of the command sequence.
  • Page 254 Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings that configure the IEC 61850 protocol interface for record clear commands. 5-80 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 255 This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo" here is select-before-operate. Enhanced security means that the G30 reports to the client the breaker 1 position at the end of the command sequence.
  • Page 256 Virtual Inputs are controllable FlexLogic operands that can be controlled via IEC 61850 commands to GGIO2, by DNP, by Modbus, and by the UR front panel. The settings related to these IEC 61850 commands are described here. 5-82 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 257 Navigate to Settings > Product Setup > Communications > IEC 61850 > GGIO > GGIO4 > GGIO4.AnIn1 to access the settings for the first GGIO4 value. The settings and functionality for the others are similar. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-83...
  • Page 258 <LDName>/GGIO4.AnIn01.instMag.f. This setting is stored as an IEEE 754 / IEC 60559 floating point number. Because of the large range of this setting, not all possible values can be stored. Some values are rounded to the closest possible floating point number. 5-84 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 259 PRODUCT SETUP File transfer by IEC 61850 The G30 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as an example. In the AX-S4 61850 Explorer window, click the Tools menu and access the SISCO File Transfer Utility.
  • Page 260 NUMBER: 0 The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the G30 over a network. The G30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the G30 contains a list and description of all available files, for example event records and oscillography.
  • Page 261 0.0.0.0 The G30 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to which the G30 can connect. A maximum of two simultaneous connections are supported at any given time.
  • Page 262 Modbus register address. The default setting value of “0” is considered invalid. Fast exchanges (50 to 1000 ms) are generally used in control schemes. The G30 has one fast exchange (exchange 1) and two slow exchanges (exchange 2 and 3).
  • Page 263 EXCH 1 DATA ITEM 1 to 20/50 from the G30 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format. See the Modbus memory map in the UR Series Communications Guide for details.
  • Page 264 PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs and none of IRIG-B, PTP, or SNTP is active, the G30 sets the invalid bit in the time stamp of a time-tagged message.
  • Page 265 Range: -32768 to 32767 in steps of 1  OFFSET: 0  ASDU 4 ANALOG 9 Range: FlexAnalog parameter  ASDU 4 ANALOG 9 Range: 0.000 to 65.535 in steps of 0.001  FACTOR: 1.000 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-91...
  • Page 266 FlexAnalog operands. The measurands sent are voltage, current, power, power factor, and frequency. If any other FlexAnalog is chosen, the G30 sends 0 instead of its value. Note that the power is transmitted in KW, not W. Measurands are transmitted as ASDU 3 or ASDU 9 (type identification value set to measurands I, respectively measurands II).
  • Page 267 Commands are received as General Command (Type Identification 20). The user can configure the action to perform when an ASDU command comes. A list of available mappings is provided on the G30. This includes 64 virtual inputs (see the following table). The ON and OFF for the same ASDU command can be mapped to different virtual inputs.
  • Page 268: Modbus User Map

    ADDRESS The UR Family Communications Guide outlines the Modbus memory map. The map is also viewable in a web browser; enter the IP address of the G30 in a web browser and click the option. 5.3.6 Real time clock 5.3.6.1 Menu SETTINGS ...
  • Page 269 Setup for IRIG-B is illustrated in the Installation chapter. For the Other protocols, whenever a time synchronization message is received through any of the active protocols, the G30 clock updates. However, given that IEC 60870-5-103, IEC 60870-5-104, Modbus, and DNP are low-accuracy time synchronization methods, avoid their use for synchronization when better accuracy time protocols, such as IRIG-B and PTP, are active in the system.
  • Page 270 PRODUCT SETUP CHAPTER 5: SETTINGS The G30 supports the Precision Time Protocol (PTP) specified in IEEE Std 1588 2008 using the Power Profile (PP) specified in IEEE Std C37.238 2011. This enables the relay to synchronize to the international time standard over an Ethernet network that implements PP.
  • Page 271 G30 clock is closely synchronized with the SNTP/ NTP server. It takes up to two minutes for the G30 to signal an SNTP self-test error if the server is offline.
  • Page 272: User-Programmable Fault Report

     2:00 The G30 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B signals. UTC time is provided by SNTP servers. The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if the Local Time settings are not configured properly.
  • Page 273: Oscillography

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (x.xx, for example) and relay model (G30), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 274 When changes are made to the oscillography settings, all existing oscillography records are cleared. 5.3.8.2 Digital channels SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  DIGITAL CHANNELS  DIGITAL CHANNELS DIGITAL CHANNEL 1: Range: FlexLogic operand    5-100 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 275 The source harmonic indices appear as oscillography analog channels numbered from 0 to 23. These correspond directly to the to the 2nd to 25th harmonics in the relay as follows: Analog channel 0 ↔ 2nd harmonic Analog channel 1 ↔ 3rd harmonic Analog channel 23 ↔ 25th harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-101...
  • Page 276: Data Logger

    When set to “Trigger,” the data logger records any configured channels at the instance of the rising edge of the source FlexLogic operand. The data logger ignores all DATA LOGGER TRIGGER 5-102 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 277: User-Programmable Leds

    LED column. This test checks for hardware failures that lead to more than one LED being turned on from a single logic point. This stage can be interrupted at any time. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-103...
  • Page 278 : “0.10 s” PUSHBTN 1 DROP-OUT TIME Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS  menu: PRODUCT SETUP  USER-PROGRAMMABLE LEDS  LED TEST 5-104 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 279 “Latched,” the LED, once lit, remains so until reset by the faceplate button, from a remote device via a RESET communications channel, or from any programmed operand, even if the LED operand state de-asserts. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-105...
  • Page 280: User-Programmable Self-Tests

    Moreover, they do not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in Enabled mode, minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7 for information on major and minor self-test alarms. 5-106 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 281: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Figure 5-43: Control pushbuttons (enhanced faceplate) An additional four control pushbuttons are included on the standard faceplate when the G30 is ordered with the 12 user- programmable pushbutton option.
  • Page 282: User-Programmable Pushbuttons

    PUSHBTN 1 DROP-OUT Range: 0 to 60.00 s in steps of 0.05  TIME: 0.00 s PUSHBTN 1 LED CTL: Range: FlexLogic operand  PUSHBTN 1 MESSAGE: Range: Disabled, Normal, High Priority  Disabled 5-108 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 283  EVENTS: Disabled The G30 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details. User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The number depends on the front panel ordered.
  • Page 284 The duration of the incoming set signal must be at least 50 ms. — This setting assigns the FlexLogic operand serving to deactivate the user-programmable pushbutton PUSHBTN 1 RESET element. This setting is applicable only if the user-programmable pushbutton is in "Latched" mode. 5-110 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 285 10 seconds. — If this setting is enabled, each user-programmable pushbutton state change is logged as an PUSHBUTTON 1 EVENTS event into the event recorder. The figures show the user-programmable pushbutton logic. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-111...
  • Page 286 PRODUCT SETUP CHAPTER 5: SETTINGS Figure 5-48: User-programmable pushbutton logic (Sheet 1 of 2) 5-112 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 287: Flex State Parameters

    The state bits can be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are packed into each register, with the lowest-numbered state in the lowest-order bit. Sixteen registers accommodate the 256 state bits. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-113...
  • Page 288: User-Definable Displays

    When this type of entry occurs, the sub-menus are automatically configured with the proper content—this content can be edited subsequently. 5-114 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 289 If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items are different. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-115...
  • Page 290: Direct Inputs And Outputs

    DIRECT OUTPUT DEVICE ID messages. All UR-series IEDs in a ring need to have unique numbers assigned. The IED ID is used to identify the sender of the direct input and output message. 5-116 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 291 DIRECT I/O DATA RATE setting applies to a G30 with dual-channel communication cards and allows crossing DIRECT I/O CHANNEL CROSSOVER over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network regardless of the physical media of the two communication channels.
  • Page 292 DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 2: DIRECT OUTPUT DEVICE ID: “2” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 3: 5-118 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 293 Figure 5-53: Three-terminal line application A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2 constitute a first ring, while IEDs 2 and 3 constitute a second ring). G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-119...
  • Page 294 In this application, apply the following settings. For UR-series IED 1: DIRECT OUTPUT DEVICE ID: “1” DIRECT I/O CH1 RING CONFIGURATION: “Yes” DIRECT I/O CH2 RING CONFIGURATION: “Yes” For UR-series IED 2: 5-120 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 295 EVENTS: Disabled The G30 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 296: Teleprotection

     EVENTS: Disabled The G30 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unreturned messages.
  • Page 297: Installation

    5.4 Remote resources 5.4.1 Remote resources configuration When the G30 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
  • Page 298 Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the G30 process card and specific Brick. The relay is then configured to measure specific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 299: System Setup

    The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A). 5.5.1.2 Voltage banks SETTINGS  SYSTEM SETUP  AC INPUTS  VOLTAGE BANK F5(M5)  VOLTAGE BANK F5 PHASE VT F5 Range: Wye, Delta   CONNECTION: Wye G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-125...
  • Page 300: Power System

    PHASE ROTATION sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be connected to system phases A, B, and C for correct operation. 5-126 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 301: Signal Sources

    FREQUENCY TRACKING frequency applications. The frequency tracking feature functions only when the G30 is in the “Programmed” mode. If the G30 is “Not Programmed,” then metering values are available but can exhibit significant errors. Systems with an ACB phase sequence require special consideration. See the Phase Relationships of Three-phase Transformers section of chapter 5.
  • Page 302 CT wiring problem. A disturbance detector is provided for each source. The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector logic is as follows. 5-128 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 303 8 CTs 4 CTs, 4 VTs 4 CTs, 4 VTs C60, D60, G30, G60, L30, L90, M60, T60 not applicable This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half system. The following figure shows the arrangement of sources used to provide the functions required in this application, and the CT/VT inputs that are used to provide the data.
  • Page 304: Transformer

    SETTINGS  SYSTEM SETUP  TRANSFORMER  TRANSFORMER  GENERAL See below     WINDING 1 See page 5-132    WINDING 2    THERMAL INPUTS See page 5-140   5-130 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 305 CT primary by SQRT 3. This compensates for the increase of SQRT 3 caused by the Delta CT connection. Therefore, the Actual Value of current and power cannot be used for measurements in this case. Figure 5-59: Wye winding and Delta CT connection G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-131...
  • Page 306 (shown when viewed Winding is not Winding 1) The G30 is provided with this optional feature, specified as an option at the time of ordering. Using the order code for your device, see the order codes in chapter 2 for details.
  • Page 307 In this standard, the arbitrary labeling of the windings is shown as I, II, and III. This standard states that the phase relationships are established for a condition where a source phase sequence of I-II-III is connected to transformer windings labeled I, II, and III respectively. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-133...
  • Page 308 The following example shows why this happens, using a transformer described in IEC nomenclature as a type “Yd1” or in GE Multilin nomenclature as a “Y/d30.” The example shows the physical connections within the transformer that produce a phase angle in the delta winding that lag the respective wye winding by 30°.
  • Page 309 Interposing CTs or tapped relay windings were used to minimize this error. The G30 automatically corrects for CT mismatch errors. All currents are magnitude compensated to be in units of the CTs of one winding before the calculation of differential and restraint quantities.
  • Page 310 In this example, the unit CT is 1500:5 on winding 2. Magnitude compensation factors (M) are the scaling values by which each winding current is multiplied to refer it to the reference winding. The G30 calculates magnitude compensation factors for each winding as follows: Eq. 5-11 In our example, the magnitude compensation factors are calculated as follows: Eq.
  • Page 311 The G30 performs this phase angle compensation and zero sequence removal automatically, based on the settings entered for the transformer. All CTs are connected Wye (polarity markings pointing away from the transformer). All currents are phase and zero sequence compensated internally before the calculation of differential and restraint quantities.
  • Page 312 SYSTEM SETUP CHAPTER 5: SETTINGS Table 5-18: Phase and zero sequence compensation for typical values of Φ comp 5-138 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 313 [w] = magnitude, phase, and zero-sequence compensated winding w phase currents M [w] = magnitude compensation factor for winding w (see previous sections) [w], I [w], and I [w] = phase and zero sequence compensated winding w phase currents (see earlier) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-139...
  • Page 314 Range: –60 to 60°C in steps of 1  –30°C MARCH AVERAGE: Range: –60 to 60°C in steps of 1  –10°C  DECEMBER AVERAGE: Range: –60 to 60°C in steps of 1  –10°C 5-140 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 315: Breakers

    1. The number of breaker control elements depends on the number of CT/VT modules specified with the G30. The following settings are available for each breaker control element.
  • Page 316 — This setting specifies the interval required to maintain setting changes in effect after an MANUAL CLOSE RECAL1 TIME operator has initiated a manual close command to operate a circuit breaker. — Selects an operand indicating that breaker 1 is out-of-service. BREAKER 1 OUT OF SV 5-142 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 317 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-63: Dual breaker control logic (Sheet 1 of 2) IEC 61850 functionality is permitted when the G30 is in “Programmed” mode and not in local control mode. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-143...
  • Page 318 IEC 61850 trip and close commands shown is one protection pass only. To maintain the close/ open command for a certain time, do so on the contact outputs using the "Seal-in" setting, in the Trip Output element, or in FlexLogic. 5-144 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 319: Disconnect Switches

    “1-Pole” mode where each disconnect switch pole has its own auxiliary switch. — This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch 1 SWITCH 1 OPEN open command. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-145...
  • Page 320 SWITCH 1 ALARM DELAY position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the G30 is in “Programmed” mode and not in local control mode. 5-146...
  • Page 321 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-65: Disconnect switch logic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-147...
  • Page 322: Flexcurves

    15.0 0.48 0.88 15.5 0.50 0.90 16.0 0.52 0.91 16.5 0.54 0.92 17.0 0.56 0.93 17.5 0.58 0.94 18.0 0.60 0.95 18.5 0.62 0.96 19.0 0.64 0.97 19.5 0.66 0.98 10.0 20.0 5-148 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 323 30 ms. At approximately four times pickup, the curve operating time is equal to the MRT and from then onwards the operating time remains at 200 ms. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-149...
  • Page 324 Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If this is attempted, the EnerVista software generates an error message and discards the proposed changes. 5.5.7.5 Standard recloser curves The following graphs display standard recloser curves available for the G30. 5-150 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 325 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-69: Recloser curves GE101 to GE106 Figure 5-70: Recloser curves GE113, GE120, GE138, and GE142 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-151...
  • Page 326 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-71: Recloser curves GE134, GE137, GE140, GE151, and GE201 Figure 5-72: Recloser curves GE131, GE141, GE152, and GE200 5-152 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 327 CHAPTER 5: SETTINGS SYSTEM SETUP Figure 5-73: Recloser curves GE133, GE161, GE162, GE163, GE164, and GE165 Figure 5-74: Recloser curves GE116, GE117, GE118, GE132, GE136, and GE139 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-153...
  • Page 328 SYSTEM SETUP CHAPTER 5: SETTINGS Figure 5-75: Recloser curves GE107, GE111, GE112, GE114, GE115, GE121, and GE122 Figure 5-76: Recloser curves GE119, GE135, and GE202 5-154 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 329: Flexlogic

    Figure 5-77: UR architecture overview The states of all digital signals used in the G30 are represented by flags (or FlexLogic operands, which are described later in this section). A digital “1” is represented by a set flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic equation, or to operate a contact output.
  • Page 330 Counter 1 EQL The number of pulses counted is equal to the set number Lower than Counter 1 LO The number of pulses counted is below the set number Fixed Logic 1 Logic 0 5-156 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 331 Auxiliary AUX UV1 DPO Auxiliary undervoltage element has dropped out undervoltage AUX UV1 OP Auxiliary undervoltage element has operated AUX UV2 to 3 Same set of operands as shown for AUX UV1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-157...
  • Page 332 DIR POWER 1 DPO The directional power element has dropped out DIR POWER 1 OP The directional power element has operated DIR POWER 2 Same set of operands as DIR POWER 1 5-158 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 333 NEUTRAL TOC1 PKP Neutral time overcurrent 1 has picked up Neutral time NEUTRAL TOC1 OP Neutral time overcurrent 1 has operated overcurrent NEUTRAL TOC1 DPO Neutral time overcurrent 1 has dropped out G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-159...
  • Page 334 Phase A of phase undervoltage 1 has dropped out PHASE UV1 DPO B Phase B of phase undervoltage 1 has dropped out PHASE UV1 DPO C Phase C of phase undervoltage 1 has dropped out 5-160 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 335 Source 1 VT neutral wire open detected. When the VT is connected in Delta, do not enable this function because there is no neutral wire for Delta connected VT. SRC2 VT FUSE FAIL to SRC4 Same set of operands as shown for SRC1 VT FF G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-161...
  • Page 336 Same set of operands as shown for TRIP BUS 1 ELEMENT: UNDERFREQ 1 PKP Underfrequency 1 has picked up Underfrequency UNDERFREQ 1 OP Underfrequency 1 has operated UNDERFREQ 1 DPO Underfrequency 1 has dropped out 5-162 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 337 ↓ ↓ Cont Op 64 VOff (does not appear unless ordered) INPUTS/OUTPUTS: DIRECT INPUT 1 On Flag is set, logic=1 Direct inputs ↓ ↓ DIRECT INPUT 32 On Flag is set, logic=1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-163...
  • Page 338 Replace bracketed text with RxGOOSE DPS1 status is "intermediate-state" <RxGOOSE DPS1 ID> Off Replace bracketed text with RxGOOSE DPS1 status is "off" <RxGOOSE DPS1 ID> On Replace bracketed text with RxGOOSE DPS1 status is "on" 5-164 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 339 2 to 16 any input is ‘1’ 2 to 16 all inputs are ‘1’ 2 to 16 all inputs are ‘0’ NAND 2 to 16 any input is ‘0’ only one input is ‘1’ G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-165...
  • Page 340: Flexlogic Rules

    A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") can be used once only. If this rule is broken, a syntax error is declared. 5.6.3 FlexLogic evaluation Each equation is evaluated in the ascending order in which the parameters have been entered. 5-166 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 341: Flexlogic Example

    4, which is programmed in the contact output section to operate relay H1 (that is, contact output H1). Therefore, the required logic can be implemented with two FlexLogic equations with outputs of virtual output 3 and virtual output 4, shown as follows. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-167...
  • Page 342 It is generally easier to start at the output end of the equation and work back towards the input, as shown in the following steps. It is also recommended 5-168 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 343 It is now possible to check that this selection of parameters produces the required logic by converting the set of parameters into a logic diagram. The result of this process is shown in the figure, which is compared to the logic for virtual output 3 diagram as a check. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-169...
  • Page 344 Now check that the selection of parameters produce the required logic by converting the set of parameters into a logic diagram. The result is shown in the figure, which is compared to the logic for virtual output 4 diagram as a check. 5-170 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 345 Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-171...
  • Page 346: Flexlogic Equation Editor

    Range: Off, any analog actual value parameter  FLEXELEMENT 1 INPUT Range: SIGNED, ABSOLUTE  MODE: SIGNED FLEXELEMENT 1 COMP Range: LEVEL, DELTA  MODE: LEVEL FLEXELEMENT 1 Range: OVER, UNDER  DIRECTION: OVER 5-172 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 347 — This setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if FLEXELEMENT 1 +IN this setting is set to “Off.” For proper operation of the element, at least one input must be selected. Otherwise, the element does not assert its output operands. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-173...
  • Page 348 Figure 5-86: FlexElement direction, pickup, and hysteresis In conjunction with the setting, the element can be programmed to provide two extra FLEXELEMENT 1 INPUT MODE characteristics, as shown in the following figure. 5-174 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 349 (Brk X Arc Amp A, B, and C) DCmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured under the +IN and –IN inputs DELTA TIME BASE = 1 µs G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-175...
  • Page 350: Non-Volatile Latches

    FUNCTION: Disabled LATCH 1 ID: Range: up to 20 alphanumeric characters  NV Latch 1 LATCH 1 TYPE: Range: Reset Dominant, Set Dominant  Reset Dominant LATCH 1 SET: Range: FlexLogic operand  5-176 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 351: Grouped Elements

    The active setting group can be preset or selected in the menu (see the Control Elements section SETTING GROUPS later in this chapter). See also the Introduction to Elements section at the beginning of this chapter. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-177...
  • Page 352: Setting Group 1

     AGING FACTOR See page 5-184    LOSS OF LIFE See page 5-185   This menu contains the settings for the transformer differential elements and the transformer thermal elements. 5-178 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 353 > K, where PKP represents a percent differential pickup setting and K is a restraint factor defined by the relays settings Slope 1, Slope 2, and a transition area between breakpoint 1 and breakpoint 2 settings. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-179...
  • Page 354 CHAPTER 5: SETTINGS Figure 5-89: Percent differential calculations The G30 percent differential element is based on a configurable dual-breakpoint / dual-slope differential restraint characteristic. The purpose of the preset characteristic is to define the differential restraint ratio for the transformer winding currents at different loading conditions and distinguish between external and internal faults.
  • Page 355 2nd harmonic and the fundamental frequency component. The traditional 2nd harmonic restraint responds to the ratio of magnitudes of the 2nd harmonic and fundamental frequency components. If low second harmonic ratios during magnetizing inrush conditions are not expected, set the relay to a traditional way of restraining. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-181...
  • Page 356 The relay produces three FlexLogic operands that can be used for testing or for special applications, such as building custom logic (1-out-of-3) or supervising some protection functions (ground time overcurrent, for example) from the 2nd harmonic inhibit. 5-182 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 357 CHAPTER 5: SETTINGS GROUPED ELEMENTS Figure 5-91: Percent differential logic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-183...
  • Page 358 2.0 pu AGING FACTOR Range: 0 to 30000 min. in steps of 1  DELAY: 10 min. AGING FACTOR BLOCK: Range: FlexLogic operand  AGING FACTOR TARGET: Range: Self-reset, Latched, Disabled  Self-Reset 5-184 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 359 — Enter the expended life, in hours, required for operation of the element. Set this setting above the LOSS OF LIFE PICKUP total transformer life set as a reference based on nominal loading conditions and a 30°C ambient temperature, as outlined in the IEEE standards. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-185...
  • Page 360: Phase Current

     DIRECTIONAL 1 5.7.4.2 Inverse TOC curve characteristics The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t standard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 361 2.756 97.074 42.166 17.654 10.790 7.849 6.308 5.397 4.814 4.417 4.134 129.432 56.221 23.538 14.387 10.465 8.410 7.196 6.418 5.889 5.513 10.0 161.790 70.277 29.423 17.983 13.081 10.513 8.995 8.023 7.361 6.891 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-187...
  • Page 362 4.980 4.280 3.837 3.528 3.297 3.116 2.971 IEC Curve B 0.05 1.350 0.675 0.338 0.225 0.169 0.135 0.113 0.096 0.084 0.075 0.10 2.700 1.350 0.675 0.450 0.338 0.270 0.225 0.193 0.169 0.150 5-188 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 363 A to E = constants defined in the table = characteristic constant defined in the table = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”) RESET Table 5-30: GE type IAC inverse time curve constants IAC curve shape IAC Extreme Inverse 0.0040 0.6379...
  • Page 364 GROUPED ELEMENTS CHAPTER 5: SETTINGS Table 5-31: GE type IAC curve trip times Multiplier Current ( I / I pickup (TDM) 10.0 IAC Extremely Inverse 1.699 0.749 0.303 0.178 0.123 0.093 0.074 0.062 0.053 0.046 3.398 1.498 0.606 0.356 0.246 0.186...
  • Page 365 T = Operate Time (in seconds) TDM = Multiplier setting I = Input Current = Pickup Current setting pickup = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed) RESET G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-191...
  • Page 366 GROUPED ELEMENTS CHAPTER 5: SETTINGS Recloser curves The G30 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section earlier in this chapter for details. 5.7.4.3 Phase time overcurrent (ANSI 51PV, IEC PTOC) SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE TOC1(2) ...
  • Page 367 — Selects the signal source for the phase time overcurrent protection element. SIGNAL SOURCE — Selects how phase current input quantities are interpreted by the G30. Inputs can be selected as fundamental INPUT phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 368 PHASE IOC1 BLOCK A: Range: FlexLogic operand   PHASE IOC1 BLOCK C: Range: FlexLogic operand  PHASE IOC1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset PHASE IOC1 Range: Disabled, Enabled  EVENTS: Disabled 5-194 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 369 Range: 0.004 to 3.000 pu in steps of 0.001  THRESHOLD: 0.700 pu PHASE DIR 1 BLOCK Range: No, Yes  WHEN V MEM EXP: No PHASE DIR 1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-195...
  • Page 370 (phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA). The table shows the operating and polarizing signals used for phase directional control. 5-196 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 371 When set to "No," the directional element allows tripping of phase overcurrent elements under directional control. — This setting enables and disables the logging of phase directional overcurrent events in the PHASE DIR 1 EVENTS sequence of events recorder. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-197...
  • Page 372: Neutral Current

       NEUTRAL TOC 2    NEUTRAL IOC 1 See page 5-200    NEUTRAL See page 5-201   DIRECTIONAL OC1  NEUTRAL   DIRECTIONAL OC2 5-198 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 373 — This setting selects the signal source for the neutral time overcurrent protection element. NEUTRAL TOC1 SIGNAL SOURCE — This setting selects how neutral current input quantities are interpreted by the G30. Inputs can be NEUTRAL TOC1 INPUT selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 374 The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents resulting from: • System unbalances under heavy load conditions • Transformation errors of current transformers (CTs) during double-line and three-phase faults • Switch-off transients during double-line and three-phase faults 5-200 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 375 VOLT: Calculated V0 NEUTRAL DIR OC1 OP Range: Calculated 3I0, Measured IG  CURR: Calculated 3I0 NEUTRAL DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001  SEQ RESTRAINT: 0.063 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-201...
  • Page 376 The following tables define the neutral directional overcurrent element. V_0 is the zero-sequence voltage, I_0 is the zero-sequence current, ECA is the element characteristic angle, and IG is the ground current. 5-202 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 377 REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation) Take the bias into account when using the neutral directional overcurrent element to directionalize other protection elements. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-203...
  • Page 378 A similar situation arises for a wye/delta/wye transformer, where current in one transformer winding neutral can reverse when faults on both sides of the transformer are considered. 5-204 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 379 When selecting this setting, keep in mind that the design uses a positive-sequence restraint technique for the “Calculated 3I0” mode of operation. Proper application of this element requires that the operating current and the polarizing voltage (or current) be measured from the same side of the transformer. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-205...
  • Page 380: Ground Current

     RESTRICTED GROUND   FAULT 4 The G30 relay contains one Ground Time Overcurrent, one Ground Instantaneous Overcurrent, and four Restricted Ground Fault elements. See the Inverse TOC Curve Characteristics section earlier for information. 5-206 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 381 — This setting selects the signal source for the ground time overcurrent protection element. GROUND TOC1 SIGNAL SOURCE — This setting selects how ground current input quantities are interpreted by the G30. Inputs can be GROUND TOC1 INPUT selected as fundamental phasor magnitudes or total waveform RMS magnitudes as required by the application.
  • Page 382 0.02 to 46 times the CT rating. This channel can be equipped with a standard or sensitive input. The conversion range of a sensitive channel is from 0.002 to 4.6 times the CT rating. 5-208 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 383 Application of the restricted ground fault protection extends the coverage towards the neutral point (see the following figure). G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-209...
  • Page 384 Even with the improved definition of the restraining signal, the breaker-and-a-half application of the restricted ground fault must be approached with care, and is not recommended unless the settings are carefully selected to avoid maloperation due to CT saturation. 5-210 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 385 (Igr(k)) does not reduce instantly but keeps decaying decreasing its value by 50% each 15.5 power system cycles. Having the differential and restraining signals developed, the element applies a single slope differential characteristic with a minimum pickup as shown in the following logic diagram. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-211...
  • Page 386 Given the following inputs: IA = 1.10 pu ∠0°, IB = 1.0 pu ∠–120°, IC = 1.0 pu ∠120°, and IG = 0.05 pu ∠0° The relay calculates the following values: I_0 = 0.033 pu ∠0°, I_2 = 0.033 pu ∠0°, and I_1 = 1.033 pu ∠0° 5-212 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 387: Negative Sequence Current

    NEG SEQ DIR OC1 FWD Range: 0 to 90° Lag in steps of 1  ECA: 75° Lag NEG SEQ DIR OC1 FWD Range: 40 to 90° in steps of 1  LIMIT ANGLE: 90° G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-213...
  • Page 388 CT errors, since the current is low. The operating quantity depends on the way the test currents are injected into the G30. For single phase injection •...
  • Page 389 The negative-sequence directional pickup must be greater than the PRODUCT SETUP  DISPLAY PROPERTIES setting value.  CURRENT CUT-OFF LEVEL G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-215...
  • Page 390 When NEG SEQ DIR OC1 TYPE selecting this setting, keep in mind that the design uses a positive-sequence restraint technique. Figure 5-110: Negative-sequence directional OC1 logic 5-216 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 391: Generator Unbalance (Ansi 46)

    This is set to prevent false trips for faults that would be cleared normally by system protections. — The maximum operate time of the stage 1 element. This setting can be applied to limit the GEN UNBAL STG1 TMAX maximum tripping time for low level unbalances. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-217...
  • Page 392 — The minimum operate time of the stage 2 element. This is set to prevent nuisance alarms GEN UNBAL STG2 PKP DELAY during system faults. Figure 5-111: Generator unbalance inverse time curves Figure 5-112: Generator unbalance logic 5-218 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 393: Split Phase Protection (Ansi 50Sp)

    The split phase element allows a separate pickup setting to be applied for each phase. Additionally, the pickup can be biased by the load current (slope characteristic). Two modes of operation are supported (over and over-under). G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-219...
  • Page 394 Eq. 5-50 and offset is the split phase current at no-load. In “Over” mode, the element picks up if > pickup) and (I ≥ min_load) Eq. 5-51 split bias load 5-220 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 395 | > pickup) and (I ≥ min_load) Eq. 5-52 split bias load Figure 5-115: Split phase protection operating characteristics Settings are described as follows. — This setting enables and disables the function. SPLIT PHASE FUNCTION G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-221...
  • Page 396 CTs (first figure presented). In this instance, a time delay can be used to ride through the saturation event. Alternately, the CT saturation flag also can be used to supervise the function. 5-222 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 397: Voltage Elements

    Figure 5-116: Split phase protection logic 5.7.10 Voltage elements 5.7.10.1 Menu SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  VOLTAGE ELEMENTS  VOLTAGE ELEMENTS  PHASE See below   UNDERVOLTAGE1   G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-223...
  • Page 398 600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay characteristic. The undervoltage delay setting defines the family of curves shown as follows. Eq. 5-53 5-224 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 399 Range: 0.000 to 3.000 pu in steps of 0.001  VOLTAGE: 0.100 pu PHASE UV1 BLOCK: Range: FlexLogic operand  PHASE UV1 Range: Self-reset, Latched, Disabled  TARGET: Self-reset PHASE UV1 Range: Disabled, Enabled  EVENTS: Disabled G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-225...
  • Page 400 The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as calculated from phase-to-ground (wye) connected VTs. The figure shows specific voltages to be used for each phase. 5-226 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 401 FlexCurves A, B, or C) or be used as a definite time element. The setting applies only if the NEUTRAL OV1 PICKUP DELAY setting is “Definite Time.” The source assigned to this element must be configured for a phase VT. NEUTRAL OV1 CURVE G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-227...
  • Page 402 There are three negative-sequence overvoltage elements available. Use the negative-sequence overvoltage element to detect loss of one or two phases of the source, a reversed phase sequence of voltage, or a non-symmetrical system voltage condition. 5-228 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 403 Range: Disabled, Enabled  Disabled The G30 contains one auxiliary undervoltage element for each VT bank. This element monitors undervoltage conditions of the auxiliary voltage. selects the voltage level at which the time undervoltage element starts timing. The nominal secondary...
  • Page 404 Range: Disabled, Enabled  Disabled The G30 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM is the per-unit (pu) base used when setting the SETUP ...
  • Page 405 If the voltage mode is set as “Phase- phase”, then the operating quantity for this element is the phase-to-phase nominal voltage. Likewise, if the voltage G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-231...
  • Page 406 “Phase-ground”, then the operating quantity for this element is the phase-to-ground nominal voltage. It is beneficial to use the phase-to-phase voltage mode for this element when the G30 device is applied on an isolated or resistance-grounded system.
  • Page 407 TDM = Time Delay Multiplier (delay in sec.) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The figure shows the volts/hertz inverse B curves. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-233...
  • Page 408 TDM = Time Delay Multiplier (delay in sec.) V = fundamental RMS value of voltage (pu) F = frequency of voltage signal (pu) Pickup = volts-per-hertz pickup setpoint (pu) The figure shows the volts/hertz inverse C curves. 5-234 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 409: Loss Of Excitation (Ansi 40)

    LOSS OF EXCITATION Range: 0.000 to 65.535 s in steps of 0.01  PKP DELAY2: 0.500 s LOSS OF EXCITATION Range: 0.000 to 1.250 pu in steps of 0.001  UV SUPV: 0.700 pu G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-235...
  • Page 410 ‘blocked’ event if events are enabled, and becomes inactive. When unblocked, the element starts functioning instantly. If exposed to pickup conditions for an extended period of time and unblocked, the element picks up and starts timing out at the moment of unblocking. 5-236 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 411: Accidental Energization (Ansi 50/27)

    PICKUP: 0.500 pu ACCDNT ENRG OFFLINE: Range: FlexLogic operand  ACCDNT ENRG BLOCK: Range: FlexLogic operand  ACCDNT ENRG TARGET: Range: Self-reset, Latched, Disabled  Self-reset ACCDNT ENRG EVENTS: Range: Disabled, Enabled  Disabled G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-237...
  • Page 412 VT connection. — This setting specifies the FlexLogic operand indicating that the protected generator is offline. ACCDNT ENRG OFFLINE Figure 5-130: Accidental energization logic 5-238 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 413: Sensitive Directional Power (Ansi 32)

    The operating quantity is displayed in the actual value. ACTUAL VALUES  METERING  SENSITIVE DIRECTIONAL POWER 1(2) The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-239...
  • Page 414 For example, section (a) in the figure shows settings for reverse power, while section (b) shows settings for low forward power applications. 5-240 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 415 DIR POWER 1 RCA setting to “90°,” active underpower by setting to “180°,” and reactive underpower by DIR POWER 1 RCA DIR POWER 1 RCA setting to “270°.” DIR POWER 1 RCA G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-241...
  • Page 416: Stator Ground

    5.7.14 Stator ground 5.7.14.1 Menu SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  STATOR GROUND  STATOR STATOR GROUND Range: SRC 1, SRC 2, SRC 3, SRC 4   GROUND SOURCE: SRC1 5-242 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 417 Measuring the actual value of GROUND the operating quantity for a specific machine under variety of load conditions can be helpful when selecting the pickup threshold for this feature. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-243...
  • Page 418: Control Elements

    Figure 5-134: Third harmonic neutral undervoltage logic 5.8 Control elements 5.8.1 Overview Control elements are used for control rather than protection. See the Introduction to Elements section at the beginning of this chapter for information. 5-244 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 419: Trip Bus

    Once the required element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned to a trip bus. If more than one operate-type operand is required, it can be assigned directly from the trip bus menu. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-245...
  • Page 420 TRIP BUS 1 RESET RESET OP operand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or via communications resets the trip bus output. 5-246 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 421: Setting Groups

    Prevents the active setting group from changing when the selected FlexLogic operand is "On." This SETTING GROUPS BLK — can be useful in applications where it is undesirable to change the settings under certain conditions, such as during a control sequence. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-247...
  • Page 422: Selector Switch

    RANGE: 7 SELECTOR 1 TIME-OUT: Range: 3.0 to 60.0 s in steps of 0.1  5.0 s SELECTOR 1 STEP-UP: Range: FlexLogic operand  SELECTOR 1 STEP-UP Range: Time-out, Acknowledge  MODE: Time-out 5-248 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 423 (“Acknowledge” mode). When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically, a user-programmable pushbutton is configured as the stepping up control input. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-249...
  • Page 424 (that is, the three-bit input is not available (0,0,0) or out of range), then the selector switch output is set to position 0 (no output operand selected) and an alarm is established ( SELECTOR 1 PWR ALARM 5-250 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 425 The selector position pre-selected via the three-bit control input has not been confirmed before the time The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-251...
  • Page 426 CONTROL ELEMENTS CHAPTER 5: SETTINGS Figure 5-138: Time-out mode 5-252 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 427 1 through 3. The pre-selected setting group is to be applied automatically after five seconds of inactivity of the control inputs. When the relay powers up, it is to synchronize the setting group to the three-bit control input. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-253...
  • Page 428 SETTINGS  PRODUCT menu: SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1 : “Self-reset” PUSHBUTTON 1 FUNCTION : “0.10 s” PUSHBUTTON 1 DROP-OUT TIME The figure shows the logic for the selector switch. 5-254 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 429: Underfrequency (Ansi 81U)

     DELAY : 2.000 s UNDERFREQ 1 TARGET: Range: Self-reset, Latched, Disabled  Self-reset UNDERFREQ 1 EVENTS: Range: Disabled, Enabled  Disabled There are six identical underfrequency elements, numbered 1 through 6. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-255...
  • Page 430: Overfrequency (Ansi 81O)

    The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage channel, current channel A, and ground current channel. The first available signal is used for frequency calculation. 5-256 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 431: Frequency Rate Of Change (Ansi 81R)

    Range: 0 to 65.535 s in steps of 0.001  DELAY: 0.000 s FREQ RATE 1 RESET Range: 0 to 65.535 s in steps of 0.001  DELAY: 0.000 s FREQ RATE 1 BLOCK: Range: FlexLogic operand  G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-257...
  • Page 432 If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum voltage supervision is 3 V. Figure 5-143: Frequency rate of change logic 5-258 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 433: Frequency Out-Of-Band Accumulation

     FREQUENCY OOB FREQ ACCUM 1 Range: Enabled, Disabled   ACCUMULATOR 1 FUNCTION: Disabled FREQ ACCUM 1 UPPER Range: 20.00 to 70.00 Hz in steps of 0.01  FREQ 60.00 Hz G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-259...
  • Page 434: Synchrocheck (Ansi 25)

    Range: FlexLogic operand  SYNCHK1 V1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4  SRC 1 SYNCHK1 V2 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4  SRC 2 5-260 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 435 V1 or V2 to traverse an angle equal to 2 × ΔΦ at a frequency equal to the frequency difference ΔF. This time is calculated by: Eq. 5-60 where ΔΦ is phase angle difference in degrees ΔF is frequency difference in Hz G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-261...
  • Page 436 — Specifies the minimum slip frequency allowed in Hz in the dynamic mode. The dynamic mode is SYNCHK1 S-CLS MIN dF disarmed when the slip frequency drops below this setting. — Specifies the breaker closing time in seconds. SYNCHK1 S-CLS BRK TIME 5-262 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 437 VAG from the other source. If the comparison is required on a specific voltage, the user can externally connect that specific voltage to auxiliary voltage terminals and then use this "Auxiliary Voltage" to check the synchronism conditions. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-263...
  • Page 438 The relay uses the phase channel of a three-phase set of voltages if programmed as part of that source. The relay uses the auxiliary voltage channel only if that channel is programmed as part of the Source and a three-phase set is not. 5-264 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 439 CHAPTER 5: SETTINGS CONTROL ELEMENTS Figure 5-147: Synchrocheck logic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-265...
  • Page 440: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY — This setting enables or disabled the digital element pickup LED. When set to “Disabled,” the DIGITAL ELEMENT 1 PICKUP LED operation of the pickup LED is blocked. 5-266 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 441 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact that is open when the breaker is open (see figure). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5-149: Trip circuit example 1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-267...
  • Page 442 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off.” In this case, the settings are as follows (EnerVista example shown). 5-268 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 443: Digital Counters

    COUNTER 1 BLOCK: Range: FlexLogic operand  CNT1 SET TO PRESET: Range: FlexLogic operand  COUNTER 1 RESET: Range: FlexLogic operand  COUNT1 FREEZE/RESET: Range: FlexLogic operand  COUNT1 FREEZE/COUNT: Range: FlexLogic operand  G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-269...
  • Page 444 If control power is interrupted, the accumulated and frozen values are saved into non-volatile memory during the power-down operation. 5-270 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 445: Monitoring Elements

     CT FAILURE   DETECTOR 4  VT FUSE FAILURE 1 See page 5-276     VT FUSE FAILURE 4    THERMAL OVERLOAD See page 5-277   PROTECTION G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-271...
  • Page 446 — Selects the threshold value above which the output operand is set. BKR 1 ARC AMP LIMIT 5-272 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 447 -cycle) and AMP MAX (kA) values of the last event. — This setting specifies the maximum symmetrical interruption rating of the circuit breaker. BKR 1 INTERUPTION RATING Figure 5-152: Arcing current measurement G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-273...
  • Page 448 CONTROL ELEMENTS CHAPTER 5: SETTINGS Figure 5-153: Breaker arcing current logic 5-274 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 449 CT FAIL 1 3V0 INPUT — Specifies the pickup value for the 3V_0 source. CT FAIL 1 3V0 INPUT PICKUP — Specifies the pickup delay of the CT failure element. CT FAIL 1 PICKUP DELAY G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-275...
  • Page 450 Once the fuse failure condition is declared, it is sealed-in until the cause that generated it disappears. 5-276 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 451 THERMAL PROTECTION 1(2)  THERMAL THERMAL PROTECTION 1 Range: Disabled, Enabled   PROTECTION 1 FUNCTION: Disabled THERMAL PROTECTION 1 Range: SRC 1, SRC 2, SRC 3, SRC 4  SOURCE: SRC1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-277...
  • Page 452 The reset time of the thermal overload protection element is also time delayed using following formula: Eq. 5-63 where τ = thermal protection trip time constant = a minimum reset time setting 5-278 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 453 IEC255-8 cold curve or hot curve equations op(In) is the reset time calculated at index n as per the reset time equation rst(In) G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-279...
  • Page 454: Inputs/Outputs

    The figure shows the logic for the thermal overload protection element. Figure 5-157: Thermal overload protection logic 5.9 Inputs/outputs 5.9.1 Contact inputs SETTINGS  INPUTS/OUTPUTS  CONTACT INPUTS  CONTACT INPUTS   CONTACT INPUT H5a   5-280 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 455 The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-settable debounce time in order for the G30 to validate the new contact state. In the following figure, the debounce time is set at 2.5 ms;...
  • Page 456: Virtual Inputs

    VIRTUAL INPUT 1 Range: Disabled, Enabled  FUNCTION: Disabled  VIRTUAL INPUT 1 ID: Range: up to 20 alphanumeric characters  Virt Ip 1 VIRTUAL INPUT 1 Range: Self-Reset, Latched  TYPE: Latched 5-282 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 457: Contact Outputs

    Range: FlexLogic operand  CONTACT OUTPUT H1 Range: Disabled, Enabled  EVENTS: Enabled A contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Wet and dry contacts are supported. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-283...
  • Page 458 On power up, the relay reads positions of the latching contacts from the hardware before executing any other functions of the relay (such as protection and control features or FlexLogic). 5-284 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 459 The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset. Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT menus (assuming an H4L module): OUTPUTS  CONTACT OUTPUT H1a CONTACT OUTPUT H1c G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-285...
  • Page 460 Write the following FlexLogic equation (EnerVista example shown). Program the Latching Outputs by making the following changes in the SETTINGS  INPUTS/OUTPUTS  CONTACT menu (assuming an H4L module): OUTPUTS  CONTACT OUTPUT H1a 5-286 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 461: Virtual Outputs

    DIRECT INPUT 1 Range: 0 to 16  DEVICE ID: 0 DIRECT INPUT 1 Range: 0 to 32  BIT NUMBER: DIRECT INPUT 1 Range: On, Off, Latest/On, Latest/Off  DEFAULT: Off G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-287...
  • Page 462 UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The figure shows that two IEDs are connected via single-channel digital communication cards. 5-288 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 463 OP" UR IED 1: : "2" DIRECT INPUT 7 DEVICE ID : "3" DIRECT INPUT 7 BIT NUMBER : select "On" for security, select "Off" for dependability DIRECT INPUT 7 DEFAULT STATE G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-289...
  • Page 464 : "2" (this is a message from IED 2) DIRECT INPUT 5 BIT NUMBER : "2" DIRECT INPUT 6 DEVICE ID : "4" (effectively, this is a message from IED 3) DIRECT INPUT 6 BIT NUMBER UR IED 3: 5-290 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 465: Teleprotection

    The teleprotection function must be enabled to utilize the inputs. 5.9.7.2 Teleprotection inputs SETTINGS  INPUTS/OUTPUTS  TELEPROTECTION  TELEPROT INPUTS  TELEPROT INPUTS TELEPROT INPUT 1-1 Range: Off, On, Latest/Off, Latest/On  DEFAULT: Off   G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-291...
  • Page 466 (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel failure between any pair of relays. 5-292 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 467: Transducer Inputs/Outputs

    VALUE: 0.000 The G30 is provided with optional DCmA capability. This feature is specified as an option at the time of ordering. See the Order Codes section in chapter 2 for details. Hardware and software are provided to receive signals from external transducers and to convert these signals into a digital format for use as required.
  • Page 468: Rtd Inputs

    FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output contact directly. 5-294 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 469: Dcma Outputs

    DCMA OUTPUT F1 Range: –90.000 to 90.000 pu in steps of 0.001  MIN VAL: 0.000 pu DCMA OUTPUT F1 Range: –90.000 to 90.000 pu in steps of 0.001  MAX VAL: 1.000 pu G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-295...
  • Page 470 — This setting allows selection of the output range. Each DCmA channel can be set independently DCMA OUTPUT F1 RANGE to work with different ranges. The three most commonly used output ranges are available. 5-296 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 471 The CT ratio is 5000:5 and the maximum load current is 4200 A. The current is to be monitored from 0 A upwards, allowing for 50% overload. The phase current with the 50% overload margin is: Eq. 5-72 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-297...
  • Page 472 ±0.5% of the full scale for the analog output module, or ± 0.005 x (1-0) x 254.03 kV = ±1.27 kV • ±0.5% of reading For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is 0.005 × 230.94 kV + 1.27 kV = 2.42 kV. 5-298 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 473: Testing

     FUNCTION: Disabled The G30 provides a test facility to verify the functionality of contact inputs and outputs, some communication functions and the phasor measurement unit (where applicable), using simulated conditions. The test mode can be in any of three states: Disabled, Isolated, or Forcible.
  • Page 474: Force Contact Inputs

    : Normal  FORCE Cont Op xx Range: Normal, Energized, De-energized, Freeze  : Normal The force contact outputs feature provides a method of performing checks on the function of all contact outputs. 5-300 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 475 While the selected operand is Off, the output behaves as it does when in service. On restart, the setting and the force contact input and force contact output settings revert to TEST MODE FORCING their default states. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 5-301...
  • Page 476 TESTING CHAPTER 5: SETTINGS 5-302 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 477: Actual Values

      RxGOOSE STATUS See page 6-6    RxGOOSE See page 6-6   STATISTICS  DIGITAL COUNTERS See page 6-7    SELECTOR SWITCHES See page 6-7   G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 478  RxGOOSE Analogs See page 6-24    SENSITIVE See page 6-24   DIRECTIONAL POWER  STATOR See page 6-24   GROUND  VOLTS PER HERTZ 1 See page 6-25   G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 479: Front Panel

    The front panel can be viewed and used in the EnerVista software, for example to view an error message displayed on the front panel. To view the front panel in EnerVista software: Click Actual Values > Front Panel. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 480: Status

    The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates the logic state of the virtual input. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 481: Rxgoose Boolean Inputs

    Range: On, Off  STATUS: Off The G30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. 6.3.4 RxGOOSE DPS inputs ACTUAL VALUES ...
  • Page 482: Virtual Outputs

     Offline The G30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE All RxGOOSE Online Input.
  • Page 483: Digital Counters

    The second line value indicates the state of the given FlexState bit. 6.3.13 Ethernet ACTUAL VALUES  STATUS  ETHERNET  ETHERNET ETHERNET PRI LINK Range: Fail, OK  STATUS: Fail  ETHERNET SEC LINK Range: Fail, OK  STATUS: Fail G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 484: Real Time Clock Synchronizing

    PTP and that being received via IRIG-B. A positive value indicates that PTP time is fast compared to IRIG- B time. 6.3.15 Direct inputs ACTUAL VALUES  STATUS  DIRECT INPUTS  DIRECT INPUTS AVERATE MSG RETURN  TIME CH1: 0 ms  UNRETURNED MSG  COUNT CH1: 0 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 485: Direct Devices Status

    SIGNATURE: 0 FAST EXCHANGE 1  DATA LENGTH: 0 These values provide information for debugging an Ethernet Global Data (EGD) network. The EGD signature and packet size for the fast EGD exchange display. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 486: Teleprotection Channel Tests

    MODBUS TCP (max 4) Range: 0 to 4  DNP TCP(max 2) Range: 0 to 2  IEC-104 TCP(max 2) Range: 0 to 2  SFTP (max 4) Range: 0 to 4  6-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 487: Parallel Redundancy Protocol (Prp)

    Range: 0 to 4G, blank if PRP disabled  The G30 is provided with optional PRP capability. This feature is specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
  • Page 488: Metering

    GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast. 6.4 Metering 6.4.1 Metering conventions 6.4.1.1 UR convention for measuring power and energy The figure illustrates the conventions established for use in UR devices. 6-12 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 489 6.4.1.2 UR convention for measuring phase angles All phasors calculated by URs and used for protection, control and metering functions are rotating phasors that maintain the correct phase angle relationships with each other at all times. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-13...
  • Page 490 For display and oscillography purposes the phase angles of symmetrical components are referenced to a common reference as described in the previous sub-section. WYE-connected instrument transformers • ABC phase rotation: • ACB phase rotation: The above equations apply to currents as well. 6-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 491 * The power system voltages are phase-referenced – for simplicity – to V and V , respectively. This, however, is a relative matter. It is important to remember that the G30 displays are always referenced as specified under SETTINGS  SYSTEM SETUP  POWER SYSTEM  FREQUENCY AND PHASE REFERENCE The example above is illustrated in the following figure.
  • Page 492: Transformer

    ACTUAL VALUES  METERING  TRANSFORMER  THERMAL ELEMENTS  THERMAL TOP OIL °C:   ELEMENTS 70°C HOTTEST-SPOT °C:  130° AGING FACTOR:  DAILY RATE LOL:  15 hrs XFMR LIFE LOST:  100000 hrs 6-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 493: Sources

    0.000 A SRC 1 RMS Ic:  0.000 A SRC 1 RMS In:  0.000 A SRC 1 PHASOR Ia:  0.000 A 0.0° SRC 1 PHASOR Ib:  0.000 A 0.0° G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-17...
  • Page 494 0.000 V 0.0° SRC 1 RMS Vab:  0.00 V SRC 1 RMS Vbc:  0.00 V SRC 1 RMS Vca:  0.00 V SRC 1 PHASOR Vab:  0.000 V 0.0° 6-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 495 SRC 1 REACTIVE PWR  φc: 0.000 var SRC 1 APPARENT PWR  3φ: 0.000 VA SRC 1 APPARENT PWR  φa: 0.000 VA SRC 1 APPARENT PWR  φb: 0.000 VA G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-19...
  • Page 496 S = V x Î x Î x Î Eq. 6-1 When VTs are configured in delta, the G30 does not calculate power in each phase and three-phase power is measured as S = V x Î x Î Eq. 6-2...
  • Page 497 = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT) m is the last sample number for the sliding window h = 1, 2,..., 25 is the harmonic number The short-time Fourier transform is applied to the unfiltered signal: Eq. 6-3 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-21...
  • Page 498: Synchrocheck

    The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the setting in the menu. See the Power FREQUENCY AND PHASE REFERENCE SETTINGS  SYSTEM SETUP  POWER SYSTEM System section of chapter 5 for details. 6-22 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 499: Frequency Rate Of Change

    × I for the +IN and –IN inputs BASE BASE BASE SOURCE THD & HARMONICS BASE = 1% SOURCE VOLTAGE = maximum nominal primary RMS value of the +IN and –IN inputs BASE G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-23...
  • Page 500: Rxgoose Analogs

     0.000 The G30 is provided with optional GOOSE communications capability. This feature is specified as a software option at the time of ordering. See the Order Codes section of chapter 2 for details. The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE messages sent from other devices.
  • Page 501: Volts Per Hertz

    6.5 Records 6.5.1 User-programmable fault reports ACTUAL VALUES  RECORDS  USER-PROGRAMMABLE FAULT REPORTS  USER-PROGRAMMABLE NEWEST RECORD   FAULT REPORTS NUMBER: 0 LAST CLEARED DATE:  2002/8/11 14:23:57 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-25...
  • Page 502: Event Records

    The event records are also viewable in the software and in a web browser. The figure shows the event records in the software. To view them in a web browser, enter the IP address of the device. Figure 6-5: Event records viewed in EnerVista software 6-26 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 503: Oscillography

    BKR 1 ACC ARCING AMP  φC: 0.00 kA2-cyc BKR 1 OPERATING TIME  φA: 0 ms BKR 1 OPERATING TIME  φB: 0 ms BKR 1 OPERATING TIME  φC: 0 ms G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-27...
  • Page 504: Product Information

    Range: YYYY/MM/DD HH:MM:SS  OPERATING TIME: Range: operating time in HH:MM:SS  0:00:00 CT/ VT ADVANCED DIAG Range: Yes, No  ACTIVE: No LAST SETTING CHANGE: Range: YYYY/MM/DD HH:MM:SS  1970/01/01 23:11:19 6-28 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 505: Firmware Revisions

    Range: YYYY/MM/DD HH:MM:SS  2016/09/15 16:41:32 Date and time when the FPGA was built. The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been installed. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 6-29...
  • Page 506 PRODUCT INFORMATION CHAPTER 6: ACTUAL VALUES 6-30 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 507: Commands And Targets

    The commands menu contains relay directives intended for operations personnel. All commands can be protected from unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash message appears after successfully command entry. COMMAND EXECUTED G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 508: Virtual Inputs

    This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a command setting to “Yes” and pressing the key. After clearing data, the command setting automatically reverts to ENTER “No.” G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 509: Set Date And Time

    PERFORM LAMP TEST — This command causes the relay to scan the backplane for the hardware modules and update the UPDATE ORDER CODE order code to match. If an update occurs, the following message displays. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 510: Targets Menu

    Although the diagnostic information is cleared before the G30 is shipped from the factory, the user can want to clear the diagnostic information for themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
  • Page 511: Target Messages

    A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target messages of all the devices inserted into that site. Each G30 element with a TARGET setting has a target message that when activated by its element is displayed in sequence with any other currently active target messages in the menu.
  • Page 512 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the G30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed module (for example, F8L).
  • Page 513 Description of problem: A bad IRIG-B input signal has been detected. • How often the test is performed: Monitored whenever an IRIG-B signal is received. • What to do: Ensure the following: – The IRIG-B cable is properly connected. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 514 How often the test is performed: On any setting changes, when new settings were written to device. • What to do: Verify that the setting change was legitimate and essential for proper functioning of the protection and control system. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 515 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the G30 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 516 Description of problem: There is a problem with the Compact Flash memory in the CPU module. • How often the test is performed: On relay power-up and afterwards once every 24 hours. 7-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 517 AC bank crosschecking setting to none, until the Process Bus Failure clears. Once the problem AC bank has been identified, the values from each of the two Bricks can be examined individually by temporarily mapping each to an AC bank with a single origin. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 7-11...
  • Page 518 Brick output failing to respond to an output command can only be detected while the command is active, and so in this case the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended, however the output can still be non-functional. 7-12 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 519: Application Of Settings

    In-zone transformer with VT on the low-voltage (LV) side • With no in-zone transformer 8.1.2 In-zone transformer with VT on the high-voltage side Consider the generator protection system show, with an in-zone transformer with VT on the high-voltage (HV) side. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 520 The difference seen by the differential is the transformer phase shift plus the CT phase shift, or –30° + (–180°) = –210°. The transformer configuration is therefore as shown in the following figure. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 521: In-Zone Transformer With Vt On The Low-Voltage Side

    Consider the generator protection system shown, with an in-zone transformer with VT on the low-voltage (LV) side. Figure 8-2: Typical wiring, VT on the low-voltage side of the transformer The two sources are configured as follows. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 522: No In-Zone Transformer

    1. In this case, the only phase shift that must be accounted for is the phase shift of the transformer. Winding 2 is therefore shifted by –30°. 8.1.4 No in-zone transformer Consider the generator protection system shown, with no in-zone transformer. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 523 The two sources are configured as follows. The G30 requires the use of the transformer windings settings for the differential element, even if the differential is applied only as a stator differential for the generator. These settings ensure that the differential element operates with the correct phase shifts, and applies the correct magnitude compensation.
  • Page 524: Settings

    PHASE VT RATIO = Eq. 8-3 NEUTRAL VT RATIO = Eq. 8-4 Enter the following values through the EnerVista software or the front panel SETTINGS  SYSTEM SETUP  AC INPUTS  menu. VOLTAGE BANK F5 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 525: Power System

    Elements using the auxiliary VT input are assigned to the “GEN” source. Make the following changes through the EnerVista software or the front panel SETTINGS  SYSTEM SETUP  SOURCE 1 menus. SETTINGS  SYSTEM SETUP  SOURCE 2 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 526: Generator Unbalance

    Stage 2 is typically set lower than stage 1 with a time delay to prevent nuisance alarms for external faults that are normally cleared by system protection. For the application example, the pickup setting is: Eq. 8-6 Source 2 is to be chosen for this element. The settings are as follows. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 527: Loss Of Excitation

    The source used for loss of excitation produces positive power when the machine is generating. Make the following changes in the EnerVista software or the front panel SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1  LOSS OF menu. EXCITATION G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 528: Reverse Power

    System backup protection is implemented using a phase time overcurrent element with voltage restraint enabled. The NEUTRL source is to be chosen for this element. Set the pickup of this element at a safe margin above the maximum load expected on the machine. Eq. 8-17 8-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 529 The neutral source is chosen. Make the following changes in the EnerVista software or the front panel SETTINGS  menu. GROUPED ELEMENTS  SETTING GROUP 1  PHASE CURRENT  PHASE TOC1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 8-11...
  • Page 530: Overexcitation

    The following inputs and outputs are used in this example. Make the following changes in the EnerVista software or the front panel menus. SETTINGS  INPUTS/OUTPUTS  CONTACT INPUTS  CONTACT INPUT H7a(H7c) 8-12 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 531: Frequency

    The elements are to be blocked when offline. Underfrequency is to initiate a trip. Overfrequency is to alarm only. Either source can be assigned. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 8-13...
  • Page 532: Accidental Energization

    SETTING S  GROUPED ELEMENTS  SETTING menu. GROUP 1  ACCIDENTAL ENERGIZATION 8.2.12 FlexLogic The following logic as given as an example. The logic for each specific application depends on system design, protection philosophies, and operating practices. 8-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 533 CHAPTER 8: APPLICATION OF SETTINGS SETTINGS Figure 8-6: Application example FlexLogic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 8-15...
  • Page 534 SETTINGS CHAPTER 8: APPLICATION OF SETTINGS 8-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 535: Commissioning

    Injection to a particular G30 frequency element must be to its configured source and to the channels that the source uses for frequency measurement. For frequency measurement, a source uses the first quantity configured in the following...
  • Page 536 0.20 Hz before the threshold and subtract 1 second from the test set time reading of ramp start to relay operation. Note that the G30 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time taken by the frequency responding component to pickup.
  • Page 537: Theory Of Operation

    10.1.1 CT saturation detection The saturation detector of the G30 takes advantage of the fact that any CT operates correctly for a short period of time, even under very large primary currents that would subsequently cause a very deep saturation. As a result, in the case of an external fault, the differential current stays very low during the initial period of linear operation of the CTs while the restraining signal develops rapidly.
  • Page 538 The operation of the saturation detector is available as the FlexLogic operand BUS 1() SAT. Figure 10-2: Saturation detector state machine 10-2 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 539: Maintenance

    UR Family Communications Guide for the entries. The upper part of the window displays values. The lower part of the window is for factory service use. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 11-1...
  • Page 540 Float — A numbering system with no fixed number of digits before or after the decimal point. An example is 0.000000. Binary — A numbering system using 0 and 1. An example is 0000-0000-0000-0000. Entries are not saved when closing the window. 11-2 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 541: General Maintenance

    GENERAL MAINTENANCE 11.2 General maintenance The G30 requires minimal maintenance. As a microprocessor-based relay, its characteristics do not change over time. Expected service life is 20 years for UR devices manufactured June 2014 or later when applied in a controlled indoors environment and electrical conditions within specification.
  • Page 542 15 = Role Log in 11.3.1.2 Setting changes file The SETTING_CHANGES.LOG file stores all the setting changes. A total of 1024 events are stored in a circular buffer in non- volatile memory. 11-4 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 543: Copy Settings To Other Device

    11.4 Copy settings to other device Settings from one G30 device can be copied to another G30 device for rapid deployment. The order codes must match. See the Settings File section at the beginning of the Interfaces chapter for a list of settings not deployed, such as IP address.
  • Page 544: Back Up And Restore Settings

    This section describes how to backup settings to a file and how to use that file to restore the settings to the original relay or to a replacement relay. 11-6 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 545: Back Up Settings

    Have this option enabled when you want to keep the IID file from the UR device instead of from another tool. The location of the file is C:\ProgramData\GE Power Management\urpc\Offline, for example.
  • Page 546 Select the Save As option, which displays for firmware 7.3 and later, and select the CID option from the drop-down list. The file is copied from the computer to the location specified. 11-8 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 547: Restore Settings

    This means that the URS file is from UR version 7.30 or higher, has the IEC 61850 software option in the order code, but any IEC 61850 content will be compromised and will need to be configured. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 11-9...
  • Page 548 EnerVista UR Setup software. The values that these settings had at the time the backup was created are contained within the backup file, accessed through EnerVista UR Setup software. 11-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 549: Upgrade Software

    Expand the entry for the UR device. Click the Read Order Code button. The order code and version of the device are populated to the software. Click the OK button to save the change. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 11-11...
  • Page 550: Upgrade Firmware

    You access the Convert Device Settings option by right-clicking the file in the Offline Window area at the lower left. GE recommends converting settings in firmware steps, for example when converting from 6.0 to 7.4x, convert first to 7.0 then 7.4 in order to follow embedded conversion rules and keep settings. Note that the values of all settings that have been defaulted during conversion are not listed in the conversion report;...
  • Page 551: Replace Module

    Open the enhanced faceplate to the left once the thumb screw has been removed. This allows for easy access of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the G30. Figure 11-10: Modules inside relay with front cover open (enhanced faceplate) The standard faceplate can be opened to the left once the black plastic sliding latch on the right side has been pushed up, as shown below.
  • Page 552: Battery

    Risk of fire if battery is replaced with incorrect type or polarity. To replace the battery: Turn off the power to the unit. Wait a minimum of three minutes to ensure that there is no power to the battery. 11-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 553: Dispose Of Battery

    The battery is marked with this symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling return the battery to your supplier or to a designated collection point. For more information see: www.recyclethis.info. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 11-15...
  • Page 554 (Cd), plomb (Pb), ou mercure (Hg). Pour le recyclage, retourner la batterie à votre fournisseur ou à un point de collecte. Pour plus d'informations, voir: www.recyclethis.info. 11-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 555 (Cd), ołowiu (Pb) lub rtęci (Hg). Dla zapewnienia właściwej utylizacji, należy zwrócić baterie do dostawcy albo do wyznaczonego punktu zbiórki. Więcej informacji można znaleźć na stronie internetowej www.recyclethis.info. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 11-17...
  • Page 556 North America 905-294-6222 Latin America +55 11 3614 1700 Europe, Middle East, Africa +(34) 94 485 88 00 Asia +86-21-2401-3208 India +91 80 41314617 From GE Part Number 1604-0021-A1, GE Publication Number GEK-113574. 11-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 557: Clear Files And Data After Uninstall

    Customers are responsible for shipping costs to the factory, regardless of whether the unit is under warranty. • Fax a copy of the shipping information to the GE Grid Solutions service department in Canada at +1 905 927 5098. Use the detailed return procedure outlined at https://www.gegridsolutions.com/multilin/support/ret_proc.htm...
  • Page 558: Storage

    Other than the battery, there are no special requirements for disposal of the unit at the end its service life. For customers located in the European Union, dispose of the battery as outlined earlier. To prevent non-intended use of the unit, remove the modules, dismantle the unit, and recycle the metal when possible. 11-20 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 559: A.1 Flexanalog Items

    Field RTD 5 Value Field RTD 5 value 5829 Field RTD 6 Value Field RTD 6 value 5830 Field RTD 7 Value Field RTD 7 value 5831 Field RTD 8 Value Field RTD 8 value G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 560 SRC 2 Ic Angle Degrees Source 2 phase C current angle 6225 SRC 2 In Mag Amps Source 2 neutral current magnitude 6227 SRC 2 In Angle Degrees Source 2 neutral current angle G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 561 6353 SRC 4 In Mag Amps Source 4 neutral current magnitude 6355 SRC 4 In Angle Degrees Source 4 neutral current angle 6356 SRC 4 Ig RMS Amps Source 4 ground current RMS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 562 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude 6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle 6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 563 SRC 4 Vag RMS Volts Source 4 phase AG voltage RMS 6850 SRC 4 Vbg RMS Volts Source 4 phase BG voltage RMS 6852 SRC 4 Vcg RMS Volts Source 4 phase CG voltage RMS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 564 Source 2 phase C real power 7208 SRC 2 Q Vars Source 2 three-phase reactive power 7210 SRC 2 Qa Vars Source 2 phase A reactive power 7212 SRC 2 Qb Vars Source 2 phase B reactive power G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 565 Source 1 positive varhour 7430 SRC 1 Neg varh varh Source 1 negative varhour 7440 SRC 2 Pos Watthour Source 2 positive Watthour 7442 SRC 2 Neg Watthour Source 2 negative Watthour G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 566 SRC 1 Vb Harm[6] Source 1 phase B voltage sixth harmonic 8095 SRC 1 Vb Harm[7] Source 1 phase B voltage seventh harmonic 8096 SRC 1 Vb Harm[8] Source 1 phase B voltage eighth harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 567 SRC 2 Va Harm[3] Source 2 phase A voltage third harmonic 8142 SRC 2 Va Harm[4] Source 2 phase A voltage fourth harmonic 8143 SRC 2 Va Harm[5] Source 2 phase A voltage fifth harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 568 Source 2 phase B voltage twenty-fifth harmonic 8189 SRC 2 Vc THD Source 2 phase C voltage total harmonic distortion (THD) 8190 SRC 2 Vc Harm[2] Source 2 phase C voltage second harmonic A-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 569 SRC 3 Va Harm[22] Source 3 phase A voltage twenty-second harmonic 8236 SRC 3 Va Harm[23] Source 3 phase A voltage twenty-third harmonic 8237 SRC 3 Va Harm[24] Source 3 phase A voltage twenty-fourth harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-11...
  • Page 570 SRC 3 Vc Harm[19] Source 3 phase C voltage nineteenth harmonic 8283 SRC 3 Vc Harm[20] Source 3 phase C voltage twentieth harmonic 8284 SRC 3 Vc Harm[21] Source 3 phase C voltage twenty-first harmonic A-12 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 571 SRC 4 Vb Harm[16] Source 4 phase B voltage sixteenth harmonic 8330 SRC 4 Vb Harm[17] Source 4 phase B voltage seventeenth harmonic 8331 SRC 4 Vb Harm[18] Source 4 phase B voltage eighteenth harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-13...
  • Page 572 Transformer restraint phase B current angle 8973 Xfmr Harm2 Ibd Mag % fo Transformer differential phase B second harmonic current magnitude 8974 Xfmr Harm2 Ibd Angle Degrees Transformer differential phase B second harmonic current angle A-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 573 SRC 1 Ib Harm[6] Source 1 phase B current sixth harmonic 10279 SRC 1 Ib Harm[7] Source 1 phase B current seventh harmonic 10280 SRC 1 Ib Harm[8] Source 1 phase B current eighth harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-15...
  • Page 574 SRC 2 Ia Harm[3] Source 2 phase A current third harmonic 10342 SRC 2 Ia Harm[4] Source 2 phase A current fourth harmonic 10343 SRC 2 Ia Harm[5] Source 2 phase A current fifth harmonic A-16 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 575 Source 2 phase B current twenty-fifth harmonic 10405 SRC 2 Ic THD Source 2 phase C current total harmonic distortion 10406 SRC 2 Ic Harm[2] Source 2 phase C current second harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-17...
  • Page 576 SRC 3 Ia Harm[22] Source 3 phase A current twenty-second harmonic 10460 SRC 3 Ia Harm[23] Source 3 phase A current twenty-third harmonic 10461 SRC 3 Ia Harm[24] Source 3 phase A current twenty-fourth harmonic A-18 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 577 SRC 3 Ic Harm[19] Source 3 phase C current nineteenth harmonic 10523 SRC 3 Ic Harm[20] Source 3 phase C current twentieth harmonic 10524 SRC 3 Ic Harm[21] Source 3 phase C current twenty-first harmonic G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-19...
  • Page 578 SRC 4 Ib Harm[16] Source 4 phase B current sixteenth harmonic 10586 SRC 4 Ib Harm[17] Source 4 phase B current seventeenth harmonic 10587 SRC 4 Ib Harm[18] Source 4 phase B current eighteenth harmonic A-20 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 579 Degrees Synchrocheck 1 _synchscope 10864 Synchchk 2 Delta V Volts Synchrocheck 2 delta voltage 10866 Synchchk 2 Delta Phs Degrees Synchrocheck 2 delta phase 10867 Synchchk 2 Synchscp Degrees Synchrocheck 2 synchscope G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-21...
  • Page 580 Breaker 1 amp max phase B 12052 Brk 1 Amp Max C kA2-cyc Breaker 1 amp max phase C 12054 Brk 2 Acc Arc Amp A kA2-cyc Breaker 2 Acc arcing amp phase A A-22 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 581 RTD input 7 actual value 13559 RTD Ip 8 RTD input 8 actual value 13560 RTD Ip 9 RTD input 9 actual value 13561 RTD Ip 10 RTD input 10 actual value G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-23...
  • Page 582 Current setting group 32768 Tracking Frequency Terminal tracking frequency 39168 FlexElement 1 Value FlexElement 1 actual value 39170 FlexElement 2 Value FlexElement 2 actual value 39172 FlexElement 3 Value FlexElement 3 actual value A-24 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 583 45632 RxGOOSE Analog 25 RxGOOSE analog input 25 45634 RxGOOSE Analog 26 RxGOOSE analog input 26 45636 RxGOOSE Analog 27 RxGOOSE analog input 27 45638 RxGOOSE Analog 28 RxGOOSE analog input 28 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL A-25...
  • Page 584 45640 RxGOOSE Analog 29 RxGOOSE analog input 29 45642 RxGOOSE Analog 30 RxGOOSE analog input 30 45644 RxGOOSE Analog 31 RxGOOSE analog input 31 45646 RxGOOSE Analog 32 RxGOOSE analog input 32 A-26 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 585: B Radius Server Configuration

    UR device for successful authentication, and the shortname is a short, optional alias that can be used in place of the IP address. client 10.0.0.2/24 { secret = testing123 shortname = private-network-1 In the <Path_to_Radius>\etc\raddb folder, create a file called dictionary.ge and add the following content. # ########################################################## GE VSAs ############################################################ VENDOR...
  • Page 586 8.2. Access Settings > Product Setup > Security. Configure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the RADIUS shared secret as specified in the clients.conf file.
  • Page 587: C Command Line Interface

    This setting cannot be changed using the command line interface. • Use quotes ("") to enclose any parameter containing a space • Commands, options, and parameters are case sensitive G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 588 For non-CyberSentry devices — Set <authentication type> to "traditional". Note that <authentication type> defaults to "traditional" if not specified. Set <account> to "COMMANDS" or "SETTINGS". If not specified, the SETTINGS account is used. Example: SetupCLI URPC login -d "C30 Melbourne" -A traditional -a SETTINGS -w 1password1 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 589 Read settings from device <device> and save them to the .urs file <File>. The <File> must not already exist. The default path to the output file is C:\Users\Public\Public Documents\GE Power Management\URPC\Data Example: SetupCLI URPC getsettings -d C30 -f "C30 Markham.urs"...
  • Page 590 SetupCLI URPC getsettings -d demoDevice -f devicefile.urs SetupCLI URPC compare -f existingfile.urs -r devicefile.urs -o output.txt The output is similar to the following: Comparing settings file aaa.urs : C:\Users\Public\Public Documents\GE Power Management\URPC\Data\ with bbb.urs : C:\Users\Public\Public Documents\GE Power Management\URPC\Data\ Setting Name...
  • Page 591 SetupCLI URPC getsettings -d DEV@SETUP_CLI -f "example file.urs" SetupCLI URPC logout -d DEV@SETUP_CLI SetupCLI URPC exit DEV@SETUP_CLI has to be used as the device name in the commands followed by the 'adddevice' command. G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 592 COMMAND LINE INTERFACE APPENDIX C: COMMAND LINE INTERFACE G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 593: Revision History

    This chapter provides the warranty and revision history. D.1 Warranty For products shipped as of 1 October 2013, GE Grid Solutions warrants most of its GE manufactured products for 10 years. For warranty details including any limitations and disclaimers, see the Terms and Conditions at https://www.gegridsolutions.com/multilin/warranty.htm...
  • Page 594 31 January 2017 17-3427 1601-0166-AE3 7.4x 28 April 2017 17-3561 Table D-2: Major changes for G30 manual version AE3 (English) Page Description General revision Updated order codes Added Theory of Operation chapter in order to add Saturation Detector section 11-5...
  • Page 595 Added Monitoring section 10-2 Added Retrieve Files section Added Command Line Interface appendix Table D-5: Major changes for G30 manual version AB2 (English) Page Description Updated document throughout, including numbers of elements and FlexLogic operands table Added EAC compliance information throughout, including logo on title page, rear panel, added specifications, added life...
  • Page 596 REVISION HISTORY APPENDIX D: MISCELLANEOUS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 597 Fiber Optic Contact Output FPGA Field-programmable Gate Array Communication FREQ Frequency COMM Communications Frequency-Shift Keying COMP Compensated, Comparison File Transfer Protocol CONN Connection FlexElement™ CONT Continuous, Contact Forward CO-ORD Coordination Central Processing Unit Generator G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 598 PUTT Permissive Under-reaching Transfer Trip Manual / Manually Pulse Width Modulated Maximum Power Model Implementation Conformance Minimum, Minutes QUAD Quadrilateral Man Machine Interface Manufacturing Message Specification Rate, Reverse Minimum Response Time Registration Authority G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 599 Transport Selector Time Undercurrent Time Undervoltage TX (Tx) Transmit, Transmitter Under Undercurrent Utility Communications Architecture User Datagram Protocol Underwriters Laboratories UNBAL Unbalance Universal Relay Universal Recloser Control .URS Filename extension for settings files G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 600 ABBREVIATIONS G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 601 ........3-13, 3-35, 3-39, 3-41, 3-42 FlexLogic operands ...............5-163 logic diagram ...................5-185 settings ....................5-184 specifications ..................2-24 Back up settings ..............5-45, 11-6 Alarm LEDs ...................5-105 Banks ....................5-7, 5-125 AND gate explained ................4-53 ANSI device numbers ................2-2 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 602 PTP ......................5-95 explained ................... 5-283 set on front panel ................7-3 FlexLogic operands ..............5-163 settings ....................5-94 settings ....................5-283 Control elements ................5-244 Control power description ................... 3-12 specifications ..................2-33 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 603 ................6-1 FlexLogic operands ...............5-163 Dataset member is empty message ........5-54 settings ....................5-287 Date, set ...................... 7-3 specifications ..................2-30 DCmA inputs ...................6-25 actual values ..................6-25 FlexAnalogs ..................A-23 settings ....................5-293 specifications ..................2-30 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 604 ..................4-2 File transfer by IEC 61850 .............. 5-85 firmware upgrade or downgrade ..........11-12 File transfer by TFTP installation ................... 3-51 ................5-86 oscillography ..................4-2 requirements ..................3-50 restart relay ..................5-45 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 605 ..................... 4-19 security ....................4-9 FUNCTION setting ..................5-5 specifications ..................2-26 Fuse failure timer settings ...................5-172 ...................5-276 worksheet ..................5-169 Fuse specifications ................2-31 Force contact inputs ...............5-300 Fuses not field-replaceable ............11-19 Force contact outputs ..............5-300 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 606 RTD inputs .................... 3-26 Hottest-spot temperature virtual ....................5-282 actual values ..................6-16 FlexLogic operands ...............5-163 logic diagram ...................5-184 settings ....................5-184 specifications ..................2-24 HTTP ......................5-85 port, close .................... 5-85 Humidity specifications ..............2-36 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 607 .............. 2-29 explained ....................4-20 power specifications ..............2-28 In Service ....................3-48 THD specifications ................2-29 settings ....................5-105 voltage specifications ..............2-28 Trouble ....................3-48 Microsoft Windows requirement ..........3-50 Link power budget ................2-34 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 608 ................5-287 Overcurrent curve types Neutral IOC .............. 5-186 Overcurrent curves FlexLogic operands ...............5-159 logic diagram ...................5-201 FlexCurves ..................5-191 settings ....................5-200 IAC ......................5-189 specifications ..................2-21 IEC ......................5-188 viii G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 609 ....................6-19 Per-unit quantity ..................5-4 Power supply Phase angle metering ...............6-13 description ................... 3-12 Phase compensation ..............5-136 removal to replace battery ............11-14 Phase current metering ..............6-17 specifications ..................2-31 Power system settings ..............5-126 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 610 ..................2-20 Revision history ..................D-1 RF immunity specifications ............2-37 Quick Connect ................3-63, 3-64 RFI, conducted specifications ............2-37 R-GOOSE description ................ 5-52 RMS voltage specifications ............2-28 Routable GOOSE .................. 5-52 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 611 ..................2-36 import ....................3-65 system and event logs ..............5-24 takes relay out of service when loaded ........4-2 Security audit list of port numbers ..........5-31 traceability ..................4-12 Settings password ............4-29, 5-9, 5-10 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 612 ..................6-7 settings ....................5-86 control with IEC 61850 ..............5-78 ......................A-15 settings ................5-145, 5-248 THD metering ..................6-21 analog channel correspondence .......... 5-101 specifications ..................2-29 THD metering specifications ............2-29 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...
  • Page 613 Updates settings ....................5-130 device not recognized ..............11-11 thermal inputs .................5-140 firmware .....................11-12 Transformer differential ..........5-132, 5-140 FPGA .....................11-13 Triangle in Offline Window .............4-39 instruction manual ................3-1 order code ....................7-3 software .....................11-11 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL xiii...
  • Page 614 Yellow caution icon in Offline Window ........4-39 Voltage elements ................5-224 Voltage metering actual values ..................6-18 specifications ..................2-28 Zero-sequence compensation ..........5-136 Voltage restraint characteristic ..........5-192 Zero-sequence core balance ............3-14 G30 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL...

Table of Contents