Source Voltage Thd And Harmonics (Read Only) (4 Or 6 Modules); Breaker Flashover (Read/Write Setting) (1 Or 2 Modules); Bus Actuals (Read Only) (6 Modules) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
Source Voltage THD and Harmonics (Read Only) (4 or 6 Modules) (For F60, if order code has HIZ DSP, then 0
modules)
C70, F35, F60,
1F80
Source 1 Va THD
G30, G60
"
1F81
Source 1 Va Harmonics - 2nd to 25th (24
items)
"
1F99
Source 1 Vb THD
"
1F9A
Source 1 Vb Harmonics - 2nd to 25th (24
items)
"
1FB2
Source 1 Vc THD
"
1FB3
Source 1 Vc Harmonics - 2nd to 25th (24
items)
"
1FCB
...Repeated for Source 2
"
2016
...Repeated for Source 3
"
2061
...Repeated for Source 4
C70, F35
20AC
...Repeated for Source 5
"
20F7
...Repeated for Source 6

Breaker Flashover (Read/Write Setting) (1 or 2 Modules)

B30, C60, C70,
2196
Breaker Flashover 1 Function
D60, F60, G60,
L60, L90, M60,
T60
"
2197
Breaker Flashover 1 Side 1 Source
"
2198
Breaker Flashover 1 Side 2 Source
"
2199
Breaker Flashover 1 Status Closed A
"
219B
Breaker Flashover 1 Status Closed B
"
219D
Breaker Flashover 1 Status Closed C
"
219F
Breaker Flashover 1 Voltage Pickup Level
"
21A0
Breaker Flashover 1 Voltage Difference
Pickup Level
"
21A2
Breaker Flashover 1 Current Pickup Level
"
21A3
Breaker Flashover 1 Pickup Delay
"
21A4
Breaker Flashover 1 Supervision Phase A
"
21A6
Breaker Flashover 1 Supervision Phase B
"
21A8
Breaker Flashover 1 Supervision Phase C
"
21AA
Breaker Flashover 1 Block
"
21AC
Breaker Flashover 1 Events
"
21AD
Breaker Flashover 1 Target
"
21AE
Reserved (4 items)
B30, C60, D60,
21B2
...Repeated for Breaker Flashover 2
F60, G60, L60,
L90, M60, T60

Bus Actuals (Read Only) (6 Modules)

B90
21D0
Bus Zone 1 Differential Magnitude
"
21D4
Bus Zone 1 Differential Angle
"
21D5
Bus Zone 1 Restraint Magnitude
"
21D7
Bus Zone 1 Restraint Angle
"
21D8
Bus Zone 1 Maximum CT
"
21DA
Reserved (4 items)
"
21DE
...Repeated for Bus Zone 2
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 99.9
---
0.1
0 to 99.9
---
0.1
0 to 99.9
---
0.1
0 to 99.9
---
0.1
0 to 99.9
---
0.1
0 to 99.9
---
0.1
0 to 1
---
1
0 to 5
---
1
0 to 6
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 1.5
pu
0.001 F001
0 to 100000
V
1
0 to 1.5
pu
0.001 F001
0 to 65.535
s
0.001 F001
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 1
---
1
0 to 2
---
1
---
---
---
0 to 999999.999
A
0.001 F060
-359.9 to 0
degrees 0.1
0 to 999999.999
A
0.001 F060
-359.9 to 0
degrees 0.1
0 to 50000
---
1
---
---
---
MEMORY MAP
Format
Default
F001
0
F001
0
F001
0
F001
0
F001
0
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F211
0 (None)
F300
0
F300
0
F300
0
850
F060
1000
600
100
F300
0
F300
0
F300
0
F300
0
F102
0 (Disabled)
F109
0 (Self-Reset)
F001
0
0
F002
0
0
F002
0
F060
1
F001
0
2-27
2

Hide quick links: