Pixit Conformance Statement; Pixit For Association Model - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

PIXIT CONFORMANCE STATEMENT

I29
Interpret client references in the control blocks of other
IEDs to find the control block instances allocated to this
IED, and data sent to this IED.
I210
Set IED configuration values and parameter values as
defined in SCD file
I211
Support changed (reduced capability) valKind (e.g. from
Set to RO or to Conf) (able 46)
I212
Support ldName on other IEDs (9.3.4)
I213
Interpret input signal references to source control
blocks (9.3.13)
I214
Imports UTF-8 coding of XML
IID export after IED engineering
3
I31
IED version and instance information: LPHD.PhyNam:
hwRev, swRev, serNum, LLN0.NamPlt.configRev
I32
Configuration values (fc=CF)
I33
Setting Parameter values (fc=SP, SG)
I34
SCL Header management (9.1)
I35
Modify IED data model (add LN/Data object/LD, or
remove unused LD/LN/Data object)
Tool functionality
I41
Support MustUnderstand concept (8.2)
I42
Bind incoming 61850 signals to IED internal (input)
signals
I43
Use or create IED Input section for binding incoming
(external) signals to internal signals, to document this
binding
I44
Create CID file for IED
I45
Support ldName for LD name specification
I46
Modify LN prefixes or ldInst
3.7 PIXIT conformance statement
This section outlines protocol implementation extra information for testing (PIXIT), which relates to restrictions and
limitations of a device. This section specifies the PIXIT of the IEC 61850 interface in UR devices with firmware version 7.3
and later.
Together with PICS and the MICS, the PIXIT forms the basis for a conformance test according to IEC 61850-10. The PIXIT
entries contain information that is not available in the PICS, MICS, TICS documents or SCL file.
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-10. The "Ed" column indicates if
the entry is applicable for IEC 61850 Edition 1 and/or Edition 2.
Table 3-120: PIXIT for Association model
ID
Ed
As2
1,2
As3
1,2
As5
1,2
3-136
Description
TCP_KEEPALIVE value. The recommended
range is 1..20s.
Lost connection detection time
What association parameters are
necessary for successful association?
CHAPTER 3: IEC 61850 COMMUNICATION
UR
UR Setup
Value/comments
Yes
Yes
Yes
Yes
Where configurable
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Value / Clarification
7200 seconds
120 seconds (if there is no MMS traffic for this time,
the connection is dropped)
Transport selector Y
Session selector Y
Presentation selector Y
AP Title N
AE Qualifier N
UR SERIES – COMMUNICATIONS GUIDE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents