CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
48F3
Compensated OV Zc Ang
"
48F4
Compensated OV I_1max
"
48F5
Compensated OV STG1 PKP
"
48F6
Compensated OV STG1 Delay
"
48F7
Compensated OV STG2 PKP
"
48F8
Compensated OV STG2 Delay
"
48F9
Compensated OV SGT3 PKP
"
48FA
Compensated OV STG3 Delay
"
48FB
Compensated OV Block
"
48FD
Compensated OV Target
"
48FE
Compensated OV Events

Demand (Read/Write Setting)

C60, F35, F60,
490A
Demand Current Method
L90, N60, T60
"
490B
Demand Power Method
"
490C
Demand Interval
"
490D
Demand Input

Demand (Read/Write Command)

C60, F35, F60,
490F
Demand Clear Record
L90, N60, T60

FlexCurves A and B (Read/Write Settings)

All except C30,
4910
FlexCurve A (120 items)
N60
"
4988
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
All
4A00
Modbus Address Settings for User Map (256
items)

User Displays Settings (Read/Write Setting) (16 Modules)

All
4C00
User-Definable Display 1 Top Line Text
"
4C0A
User-Definable Display 1 Bottom Line Text ---
"
4C14
Modbus Addresses of Display 1 Items (5
items)
"
4C19
Reserved (7 items)
"
4C20
...Repeated for User-Definable Display 2
"
4C40
...Repeated for User-Definable Display 3
"
4C60
...Repeated for User-Definable Display 4
"
4C80
...Repeated for User-Definable Display 5
"
4CA0
...Repeated for User-Definable Display 6
"
4CC0
...Repeated for User-Definable Display 7
"
4CE0
...Repeated for User-Definable Display 8
"
4D00
...Repeated for User-Definable Display 9
"
4D20
...Repeated for User-Definable Display 10
"
4D40
...Repeated for User-Definable Display 11
"
4D60
...Repeated for User-Definable Display 12
"
4D80
...Repeated for User-Definable Display 13
"
4DA0
...Repeated for User-Definable Display 14
"
4DC0
...Repeated for User-Definable Display 15
"
4DE0
...Repeated for User-Definable Display 16
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
30 to 90
degrees 1
0.01 to 1
pu
0.01
0.25 to 3
pu
0.001 F001
0 to 600
sec
0.01
0.25 to 3
pu
0.001 F001
0 to 600
sec
0.01
0.25 to 3
pu
0.001 F001
0 to 600
sec
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 2
---
1
0 to 2
---
1
0 to 5
---
1
0 to 4294967295
---
1
0 to 1
---
1
0 to 655535
ms
1
0 to 655535
ms
1
0 to 65535
---
1
---
---
---
---
---
0 to 65535
---
1
---
---
---
MEMORY MAP
Format
Default
F001
90
F001
20
1300
F001
100
1300
F001
100
1300
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F139
0 (Thermal
Exponential)
F139
0 (Thermal
Exponential)
F132
2 (15 MIN)
F300
0
F126
0 (No)
F011
0
F011
0
F001
0
F202
" "
F202
" "
F001
0
F001
0
2-59
2