B90 End Fault Protection (B_Efp); B90 Instantaneous Overcurrent (B_Ioc); B90 End Fault Protection Data Objects; B90 Instantaneous Overcurrent Data Objects - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
B_DifPDIF#
LNName:
data attribute
data obj.
Type
setSrcRef
ObjectReference
setSrcCB
ObjectReference

3.5.2.6 B90 end fault protection (B_Efp)

This element is instantiated in the following products: B90.
Table 3-24: B90 end fault protection data objects
LNName:
B_EfpPIOC#
data attribute
data obj.
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
InRefγ1
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
InRefγ2
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
BlkRefγ
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference

3.5.2.7 B90 instantaneous overcurrent (B_Ioc)

This element is instantiated in the following products: B90.
Table 3-25: B90 instantaneous overcurrent data objects
B_IocPIOC#
LNName:
data attribute
data obj.
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
3.5.2.8 B90 time overcurrent (B_Toc)
This element is instantiated in the following products: B90.
UR SERIES – COMMUNICATIONS GUIDE
Prot
LDevice inst:
FC UR Name
SP BUS ZONE #τ STATUS setting
SP
LDevice inst:
Prot
FC UR Name
ST EFP # PKP
ST
ST EFP # OP
ST EFP # DPO
SP EFP# BREAKER OPEN for group γ Reference to the data attribute to input
SP
SP EFP# MANUAL CLOSE for group γ Reference to the data attribute to input
SP
SP EFP# BLOCK for group γ
SP
Prot
LDevice inst:
FC UR Name
ST IOC # PKP
ST
ST IOC # OP
ST IOC # DPO
SP IOC# BLOCK
SP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
B90 Bus zone # differential element function
UR element:
Description
Reference to the data attribute to input
Source GoCB of input if via GOOSE
UR element:
B90 End fault protection element # function
Description
EFP # PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
EFP # OP operand
EFP # DPO operand, which is the inverse of
EFP PKP
EFP# BREAKER OPEN setting for setting
group γ
Source GoCB of input if via GOOSE
EFP# MANUAL CLOSE setting for setting
group γ
Source GoCB of input if via GOOSE
EFP# BLOCK setting for setting group γ
Reference to the data attribute to input
Source GoCB of input if via GOOSE
B90 Instantaneous Overcurrent element #
UR element:
Description
IOC # PKP operand, which indicates that Op
operates when delay expires
0, the code for unknown
IOC # OP operand
IOC # DPO operand
IOC# BLOCK setting for setting group γ
Reference to the data attribute to input
Source GoCB of input if via GOOSE
R/W/C
R/C
R/C
R/W/C
R
R
3
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
3-41

Hide quick links:

Advertisement

Table of Contents
loading