CHAPTER 3: IEC 61850 COMMUNICATION
LNName: Disc0XSWI#
data obj. data attribute
Type
InRef4
ORG
setSrcRef
ObjectReferenc
e
setSrcCB
ObjectReferenc
e
InRef5
ORG
setSrcRef
ObjectReferenc
e
setSrcCB
ObjectReferenc
e
Table 3-99: Disconnect switch data objects
LNName: DiscΘXSWI#
data obj. data attribute
Type
Loc
SPS
stVal
BOOLEAN
OpCnt
INS
stVal
INT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
SwTyp
ENS
stVal
BOOLEAN
BadSt1
SPS
stVal
BOOLEAN
ClsSt1
SPS
stVal
BOOLEAN
OpnSt1
SPS
stVal
BOOLEAN
IntermSt1
SPS
stVal
BOOLEAN
Pos
DPC
stVal
CODED ENUM
ctlModel
CtlModels
BlkOpn
SPC
stVal
BOOLEAN
ctlModel
CtlModels
BlkCls
SPC
stVal
BOOLEAN
ctlModel
CtlModels
UR SERIES – COMMUNICATIONS GUIDE
LDevice inst: System
UR element: Disconnect Control element #
FC UR Name
SP
SWITCH # BLK CLOSE
SP
SP
XSWI# ST.LOC OPERAND
SP
LDevice inst: System
UR element: Disconnect Control element #
FC UR Name
ST
Disc0XSWI#.Loc.stVal
ST
CF
ST
ST
SWITCH # φψ BAD STATUS
ST
SWITCH # φψ CLOSED
ST
SWITCH # φψ OPEN
ST
SWITCH # φψ INTERM
ST
CF
ST
Disc0XSWI#.BlkOpn.stVal
CF
ST
Disc0XSWI#.BlkCls.stVal
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
SWITCH # BLK CLOSE setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
XSWI# ST.LOC OPERAND (local control)
setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
Description
Value of operand selected by XSWI#
ST.LOC OPERAND
Phase ψ disconnect switch operation
counter
1, the code for dimensionless
0, the code for a multiplier of 1
Disconnect switch type, fixed at 2
(Disconnector)
2
SWITCH # φψ BAD STATUS operand
SWITCH # φψ CLOSED operand
SWITCH # φψ OPEN operand
SWITCH # φψ INTERM operand, which is
disconnect pole discrepancy status
Disconnect switch φψ position control
0, the code for status-only
Disconnect switch open commands
blocked from all sources including
protection
0, the code for status-only
Disconnect switch close commands
blocked from all sources
0, the code for status-only
R/W/C
R
R/C
R
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R