CHAPTER 3: IEC 61850 COMMUNICATION
SCL LOG MESSAGES
Alternate access type <sel type> not supported
This message is logged when an unsupported alternate access type is detected.
dai_val_validate: Attribute <DAI flattened name> in <logical node> not found.
This message is logged when all possible functional constraint are searched and no match is found.
dai_val_validate: Attribute <flattened name> in <logical node> not a primitive type.
This message is logged when the attribute is not a basic (primitive) type.
\<logical node type> \<DAI flattened name>\ Val=<value> does not match any EnumVal. Trying numeric
conversion.
This message is logged when DAI does not have a matching enumeration.
3
\<logical node type>\<DAI flattened type> Val=<DAI value> Illegal character (0x%02x) in visible string.
This message is logged when DAI value has illegal characters.
String <DAI value> exceeds max len <maximum length>
This message is logged when the attribute value exceeds the maximum length.
String <DAI value> does not match fixed len <length>
This message is logged when DAI string is longer than the supported length.
dai_val_validate: Val <DAI value> conversion for <logical node>$<DAI fixed name> FAILED"
This message is logged when conversion of DAI value failed.
Attempt to change value of DAI <DAI flattened name> in node <lnClass> instance <ln inst> from value
<reference DAI value> to value <new DAI value>
This message is logged when an attempt is made to change the DAI value to an invalid value.
<logical node> Invalid DAI value: <DAI flattened name> = <DAI value>
This message is logged when an invalid value is detected for a DAI.
Invalid FC for DAI <DAI flattened name> in LN <logical node>
This message is logged when an invalid functional constraint is detected for a DAI.
Total invalid DAI->val <invalid DAI count>
This message is logged to show the total number of invalid DAIs.
check_iec61850_advanced_option: iedName or apName missing
This message is logged when the iedName or apName is missing.
check_iec61850_advanced_option: too many LD, should be <maximum number of supported logical devices>
This message is logged when the number of logical devices in an IED is detected to be more than six.
check_iec61850_advanced_option: too many RxGOOSE(<number of gcb>), should be <maximum number of
supported RxGOOSE>
This message is logged when the number of RxGOOSE are more than supported (16 for most products and 32 for C30).
UR SERIES – COMMUNICATIONS GUIDE