MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: ACsrcMMXU#
data obj. data attribute
TotPF
instMag
instMag.i
mag
mag.i
units
units.SIUnit
units.multiplier
3
db
zeroDb
sVC
sVC.scaleFactor
sVC.offset
PFSign
setVal
Hz
instMag
instMag.i
mag
mag.i
units
units.SIUnit
units.multiplier
db
zeroDb
sVC
sVC.scaleFactor
sVC.offset
3-100
LDevice inst: Meter
UR element: AC Source #
Type
FC UR Name
MV
AnalogueValue
MX
INT32
SRC # Three Phase Power
Factor
AnalogueValue
MX
INT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF MMXU# TotPF DEADBAND
INT32U
CF
ScaledValue
CF
Config
FLOAT32
FLOAT32
ENG
ENUMERATED
SG
MV
AnalogueValue
MX
INT32
SRC # Frequency
AnalogueValue
MX
INT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF MMXU# Hz DEADBAND
INT32U
CF
ScaledValue
CF
Config
FLOAT32
FLOAT32
CHAPTER 3: IEC 61850 COMMUNICATION
Description
SRC # Three Phase Power Factor,
dimensionless
instMag.i deadbanded
65, the code for power factor
(dimensionless)
0, the code for a multiplier of 1
0
1/1000
0
Sign convention for power factor (PF) is
fixed at Lead/Lag (usually named IEEE)
2, the code for Lead/Lag (usually named
IEEE)
SRC # Frequency, in Hz
instMag.i deadbanded
33, the code for hertz (1/s)
0, the code for a multiplier of 1
0
1/1000
0
UR SERIES – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R

Hide quick links: