Neutral Time Overcurrent (Read/Write Grouped Setting) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

MEMORY MAP
Products
Address Register name
"
5A13
B30, C60, C70,
5A26
D30, D60, F35,
F60, L30, L60,
L90, M60, N60,
T60
2
"
5A39
B30, C60, C70,
5A4C
D60, F35, F60,
L90, M60, N60,
T60
"
5A5F
C60, C70, D60,
5A72
F35, F60, L90,
M60, N60, T60
"
5A85
C70, F35, N60,
5A98
T60
"
5AAB
"
5ABE
"
5AD1
Neutral Time Overcurrent (Read/Write Grouped Setting) (1, 2, 4, or 6 Modules)
B30, C60, C70,
5B00
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
T60
"
5B01
"
5B02
"
5B03
"
5B04
"
5B05
"
5B06
"
5B07
"
5B09
"
5B0A
"
5B0B
B30, C60, C70,
5B11
D30, D60, F35,
F60, L30, L60,
L90, T60
B30, C60, C70,
5B22
D60, F35, F60,
L60, L90, T60
"
5B33
B30, C60, C70,
5B44
F35, L90, T60
2-64
...Repeated for Phase Instantaneous
Overcurrent 2
...Repeated for Phase Instantaneous
Overcurrent 3
...Repeated for Phase Instantaneous
Overcurrent 4
...Repeated for Phase Instantaneous
Overcurrent 5
...Repeated for Phase Instantaneous
Overcurrent 6
...Repeated for Phase Instantaneous
Overcurrent 7
...Repeated for Phase Instantaneous
Overcurrent 8
...Repeated for Phase Instantaneous
Overcurrent 9
...Repeated for Phase Instantaneous
Overcurrent 10
...Repeated for Phase Instantaneous
Overcurrent 11
...Repeated for Phase Instantaneous
Overcurrent 12
Neutral Time Overcurrent 1 Function
Neutral Time Overcurrent 1 Signal Source
Neutral Time Overcurrent 1 Input
Neutral Time Overcurrent 1 Pickup
Neutral Time Overcurrent 1 Curve
Neutral Time Overcurrent 1 Multiplier
Neutral Time Overcurrent 1 Reset
Neutral Time Overcurrent 1 Block
Neutral Time Overcurrent 1 Target
Neutral Time Overcurrent 1 Events
Reserved (6 items)
...Repeated for Neutral Time Overcurrent 2
...Repeated for Neutral Time Overcurrent 3
...Repeated for Neutral Time Overcurrent 4
...Repeated for Neutral Time Overcurrent 5
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0 to 30
pu
0.001 F001
0 to 16
---
1
0 to 600
---
0.01
0 to 1
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
UR SERIES – COMMUNICATIONS GUIDE
Format
Default
F102
0 (Disabled)
F167
0 (SRC 1)
F122
0 (Phasor)
1000
F103
0 (IEEE Mod
Inv)
F001
100
F104
0
(Instantaneo
us)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents