High Impedance Fault Detection (Hi-Z) Settings (Read/Write Setting); Field Current (Read/Write Grouped Setting) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
7C80
...Repeated for User Programmable
Pushbutton 7
"
7CB0
...Repeated for User Programmable
Pushbutton 8
"
7DE0
...Repeated for User Programmable
Pushbutton 9
"
7D10
...Repeated for User Programmable
Pushbutton 10
"
7D40
...Repeated for User Programmable
Pushbutton 11
"
7D70
...Repeated for User Programmable
Pushbutton 12
"
7DA0
...Repeated for User Programmable
Pushbutton 13
"
7DD0
...Repeated for User Programmable
Pushbutton 14
"
7E00
...Repeated for User Programmable
Pushbutton 15
"
7E30
...Repeated for User Programmable
Pushbutton 16

High Impedance Fault Detection (Hi-Z) Settings (Read/Write Setting)

F60
7E60
Hi-Z Function
"
7E61
Hi-Z Signal Source
"
7E62
Hi-Z Arcing Sensitivity
"
7E63
Hi-Z Phase Event Count
"
7E64
Hi-Z Ground Event Count
"
7E65
Hi-Z Event Count Time
"
7E66
Hi-Z OC Protection Coord Timeout
"
7E67
Hi-Z Phase OC Min Pickup
"
7E68
Hi-Z Neutral OC Min Pickup
"
7E69
Hi-Z Phase Rate of Change
"
7E6A
Hi-Z Neutral Rate of Change
"
7E6B
Hi-Z Loss of Load Threshold
"
7E6C
Hi-Z Three-Phase Event Threshold
"
7E6D
Hi-Z Voltage Supv Threshold
"
7E6E
Hi-Z Voltage Supv Delay
"
7E6F
Hi-Z Even Harmonic Restraint
"
7E70
Hi-Z Target
"
7E71
Hi-Z Events
"
7E72
Hi-Z Arcing Reset Time

Field Current (Read/Write Grouped Setting)

G60
7E74
Field Current Function
"
7E75
Field Current Origin
"
7E76
Field Current OC Pickup
"
7E77
Field Current OC Delay
"
7E78
Field Current UC Pickup
"
7E79
Field Current UC Delay
"
7E7A
Field Current Block
"
7E7C
Field Current Target
"
7E7D
Field Current Events
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
1 to 10
---
1
10 to250
---
1
10 to 500
---
1
5 to 180
min
1
10 to 200
seconds 1
0.01 to 10
pu
0.01
0.01 to 10
pu
0.01
1 to 999
A/2cycle 1
1 to 999
A/2cycle 1
5 to 100
%
1
1 to 1000
A
1
0 to 100
%
1
0 to 3000
cycles
2
0 to 100
%
1
0 to 2
---
1
0 to 1
---
1
0 to 6000
seconds 0.1
0 to 1
---
1
0 to 48
---
1
0.05 to 1
pu
0.01
0 to 600
seconds 0.01
0.05 to 1
pu
0.01
0 to 600
seconds 0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F167
0 (SRC 1)
F001
5
F001
30
F001
30
F001
15
F001
15
F001
150
F001
100
F001
150
F001
150
F001
15
F001
25
F001
5
F001
60
F001
20
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F151
0 (NONE)
F001
80
F001
100
F001
20
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
2-107
2