CHAPTER 3: IEC 61850 COMMUNICATION
Bkr0XCBR#
LNName:
data attribute
data obj.
Type
Pos
DPC
stVal
CODED ENUM
stSeld
BOOLEAN
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
BlkOpn
SPC
stVal
BOOLEAN
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
BlkCls
SPC
stVal
BOOLEAN
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
InRef1
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
InRef2
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
InRef3
ORG
setSrcRef
ObjectReference
setSrcCB
ObjectReference
UR SERIES – COMMUNICATIONS GUIDE
System
LDevice inst:
FC UR Name
ST
ST
CF
CF XCBR# Pos ctlModel
CF XCBR# Pos sboTimeout
CF
CF BREAKER # Toperate
ST
CF
CF XCBR# BlkOpn ctlModel
CF
CF
CF
ST
CF
CF XCBR# BlkCls ctlModel
CF
CF
CF
SP BREAKER # OPEN
SP
SP BREAKER # BLK OPEN
SP
SP BREAKER # CLOSE
SP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR element:
Description
Breaker position control and status
The controllable data status is "selected"
0 (pulse)
2 ms (actually one pass)
0
1
0 (operate-once)
Blocks breaker open commands from all
sources including protection
1 (persistent)
0
0
0
30000
0 (operate-once)
0
Blocks breaker close commands from all
sources
1 (persistent)
0
0
0
30000
0 (operate-once)
0
BREAKER # OPEN setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
BREAKER # BLK OPEN setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
BREAKER # CLOSE setting
Reference to the data attribute to input
Source GoCB of input if via GOOSE
Breaker Control element #
R/W/C
R/Ctrl
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R/C
R/Ctrl
R
R
R
R
R
R
R/W/C
R
R
R
R/Ctrl
R
R
R
R
R
R
R/W/C
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
3-91