DNP POINT LISTS
The deadbands for all Analog Input points are in the same units as the Analog Input quantity. For example, an Analog Input
quantity measured in volts has a corresponding deadband in units of volts. This is in conformance with DNP Technical
Bulletin 9809-001: Analog Input Reporting Deadband. Relay settings are available to set default deadband values
according to data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Request Function Codes supported: 1 (read), 2 (write, deadbands only), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time)
Change Event Scan Rate: defaults to 500 ms
Change Event Buffer Size: 256
Default Class for all Points: 2
4
4-12
CHAPTER 4: DNP COMMUNICATION
UR SERIES – COMMUNICATIONS GUIDE