CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
ProcBusFail
SPS
Process bus system status
ProcBusTrbl
SPS
Process Bus Trouble
PtpFail
SPS
Bad PTP Signal
RecMod
ENG
AR Mode setting: 1 = 1 and 3 Pole, 2 = 1 Pole, 3 = 3 Pole-A, 4 = 3 Pole-B
RefWinding
INS
Reference winding
RelDpo
SPS
This data object indicates that not all criteria are fulfilled, and the switching/operation
action is not released to proceed. Complement of Rel.
RrtdComFail
SPS
RRTD communication failure
Rs
SPS
Autoreclose has been reset either manually or by the rest timer
RsLO1
ENG
Reset lockout on condition setting: 0 = Off, 1 = On, in this case on Breaker Closed
condition
RsLOTmcs
ING
This setting establishes how long the breaker stays closed after a manual close
command, in order for the autorecloser to reset from lockout
RsTms
INS
The UTC time of the last clear in seconds elapsed since 00:00:00 January 1, 1970
RtdTrbl
SPS
RTD Trouble
RvOp
SPS
Fault direction is reverse
RxGooseOff
SPS
One or more RxGOOSE is not responding
Sat1
SPS
Indicates CT saturation is detected.
For SttDifPDIF, indicates phase saturation of differential is detected per phase.
Sat
1
SPS
Indicates CT saturation is detected per phase (where the last digit of instance number
1, 2, or 3 refers to phase A, B, and C respectively)
SecEthFail
SPS
Second Ethernet failure
SeqDlTmcs
ING
Time interval allowed for a single reclose shot. Timing is started whenever reclose shot
is initiated and is active until a breaker closed signal is sent.
SeqTO
SPS
The incomplete sequence timer timed out
ShotCnt1
SPS
Autoreclosec # shot count is equal to the number indicated by the data instance
number
ShotCnt1
SPS
Autoreclosec shot count is equal to the number indicated by the data instance number Rec13pRREC
SntpFail
SPS
SNTP server is not responding
StrBia
ACD
B90 Start Biased indicates the detection of a fault or an unacceptable condition by
Biased Differential element
StrOutgoing
SPS
This Data Object indicates an unstable Power swing detection for outgoing Locus
StrPhs
SPS
Indicates the detection of a fault or an unacceptable condition on a particular phase-
to-phase loop
StrRec3p
SPS
Initiate a three-pole reclose
StrZ2GndDl
SPS
Start zone 2 ground timer
StrZ2PhDl
SPS
Start zone 2 phase timer
StTyp
ENG
Switch input status type: 0 = 3-Pole (i.e. not independent pole status), 1 = 1-Pole (i.e.
three independent pole status)
StubBusOp
SPS
The stub bus function is operated
SwFail
SPS
Autoreclose mode switching failed
SysExcp
SPS
System exception
TdrTrbl
SPS
TDR Trouble
TempMnt
SPS
The ambient temperature is greater than the maximum operating temperature
TgtEna1
ENG
Enable generation of targets (front panel display messages) setting: 0 = Self-reset, 1 =
Latched, and 2 = Disabled
ThrdEthFail
SPS
Third Ethernet failure
UR SERIES – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical
nodes...
LPHD
LPHD
LPHD
Rec13pRREC
PctDifPDIF1
SynChkRSYN
LPHD
Rec13pRREC
Rec3pRREC
3
Rec3pRREC
OscRDRE
LPHD
NegDocRDIR,
NeuDocRDIR
LPHD
B_DifPDIF, SttDifPDIF
BusDifPDIF
LPHD
Rec3pRREC,
Rec13pRREC
Rec13pRREC
Rec3pRREC
LPHD
B_DifPDIF
PwrSwgRPSB1
PhsDisPDIS
TrOutPTRC
TrOutPTRC
TrOutPTRC
Bkr?XCBR,
LinDfPDIF
Rec13pRREC
LPHD
LPHD
LPHD
AuxOvPTOV,
AuxUvPTUV,
B_IocPIOC,
B_TocPTOC,
BkrFaRBRF
LPHD
3-133