CHAPTER 3: IEC 61850 COMMUNICATION
LNName: LLN0
data obj. data attribute
Mod
stVal
ctlModel
sboTimeout
sboClass
operTimeout
MltLev
setVal
GoEna
Port1
setVal
GoEna
Port2
setVal
GoEna
Port3
setVal
Function#
#
setVal
UpdateT
ms
setVal
minVal
maxVal
stepSize
units
units.SIUnit
units.multiplier
UR SERIES – COMMUNICATIONS GUIDE
LDevice inst: Master
Type
FC UR Name
ENC
ENUMERATED
ST
TEST MODE FUNCTION
CtlModels
CF
LLN0.Mod.ctlModel
INT32U
CF
SboClasses
CF
INT32U
CF
SPG
BOOLEAN
SP
ENG
ENUMERATED
SP
PORT1 TxGOOSE ENABLE
ENG
ENUMERATED
SP
PORT2 TxGOOSE ENABLE
ENG
ENUMERATED
SP
PORT3 TxGOOSE ENABLE
ENG
ENUMERATED
SP
TxGOOSE# FUNCTION.
ING
INT32
SP
TxGOOSE UPDATE TIME
INT32
CF
INT32
CF
INT32
CF
Unit
CF
ENUMERATED
ENUMERATED
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Control to "on" changes
TEST MODE FUNCTION to Disabled.
Control to "on-blocked" results in
negative acknowledge.
Control to "test" changes
TEST MODE FUNCTION to Forcible.
Control to "test/blocked" changes
TEST MODE FUNCTION to Isolated
Control to "off" results in negative
acknowledge.
Test/blocked if TEST MODE FUNCTION
is Isolated, otherwise test if TEST MODE
FUNCTION is Forcible, otherwise on
Factory default is SBO control with
normal security
30000 ms
0 (operate-once)
0
True
PORT1 TxGOOSE ENABLE setting
PORT2 TxGOOSE ENABLE setting
PORT3 TxGOOSE ENABLE setting
TxGOOSE# FUNCTION setting,
duplicates GoEna in GoCB##
TxGOOSE UPDATE TIME setting
(heartbeat interval)
1
60
1
4, the code for time in seconds
0, the code for a multiplier of 1
R/W/C
R/Ctrl
R
3
R/C
R
R
R
R
R
R
R/C
R
R/C
R
R/C
R
R/W/C
R
R/C
R
R
R
R
R
R
3-27