MEMORY MAP
F173

ENUMERATION: DCmA INPUT/OUTPUT RANGE

Bitmask
DCmA input/output range
0
0 to –1 mA
1
0 to 1 mA
2
–1 to 1 mA
2
3
0 to 5 mA
4
0 to 10 mA
5
0 to 20 mA
6
4 to 20 mA
F174
ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F176

ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT

Bitmask
Synchrocheck dead source
0
None
1
LV1 and DV2
2
DV1 and LV2
3
DV1 or DV2
4
DV1 Xor DV2
5
DV1 and DV2
F177
ENUMERATION: COMMUNICATION PORT
0 = None, 1 = COM1-RS485 (not applicable to UR firmware 7.00),
2 = COM2-RS485, 3 = Front Panel-RS232, 4 = Network - TCP,
5 = Network - UDP
F179
ENUMERATION: NEGATIVE SEQUENCE DIRECTIONAL
OVERCURRENT TYPE
0 = Neg Sequence, 1 = Zero Sequence
F183

ENUMERATION: AC INPUT WAVEFORMS

Bitmask
Definition
0
Off
1
8 samples/cycle
2
16 samples/cycle
3
32 samples/cycle
4
64 samples/cycle
2-180
CHAPTER 2: MODBUS COMMUNICATION
F186
ENUMERATION: MEASUREMENT MODE
0 = Phase to Ground, 1 = Phase to Phase
F187
ENUMERATION: HI-Z STATES
Bitmask
Hi-Z state
0
Normal
1
Coordination Timeout
2
Armed
5
Arcing
9
Downed Conductor
F188

ENUMERATION: HI-Z CAPTURE TRIGGER TYPES

Bitmask
Trigger type
0
None
1
Loss Of Load
2
Arc Suspected
3
Arcing
4
Overcurrent
5
Down Conductor
6
External
F189
ENUMERATION: INRUSH INHIBIT MODE
0 = Per Phase, 1 = 2-out-of-3, 2 = Average