CHAPTER 3: IEC 61850 COMMUNICATION
SCL LOG MESSAGES
ERROR: iecGoosePubCreate failed for GSEControl <gcb name> in ldInst <logical device instance> in IED <ied
name>
This message is logged upon failure to create GSEControl for publisher GOOSE.
ERROR: GSSE not supported by this application
This message is logged when the type attribute of GSEControl is GSSE.
iecGoosePubCreateAll: OK
Informational. The publisher GOOSE configuration is complete without issues.
Backup CID data in FLASH is invalid, erasing it. Inspect the log and manually reboot the relay. Default to ICD.
To increase the reliability of the CID files stored in the relay, two copies are maintained in the non-volatile storage. One is
3
the working copy and the other is the backup copy. The working copy is the configuration that is currently active in the
device, and the backup copy is the last known good copy. This message is logged when both the working copy and the
backup copy are corrupted and unusable. In this scenario, the device configuration is defaulted. The urscl.log provides
more information, and a manual reboot is required to recover the device from this state.
Erasing CID data in flash, inspect log and manually reboot to ICD
To increase the reliability of the CID files stored in the relay, two copies are maintained in the non-volatile storage. One is
the working copy and the other is the backup copy. The working copy is the configuration that is currently active in the
device, and the backup copy is the last known good copy. This message is logged when the working copy is corrupted and
the configuration from the backup copy is ready to be applied. The urscl.log provides more information, and a manual
reboot is required to apply the backup CID file configuration.
scl2_vmd_create_all: FAILURE
This message is logged when the IED creation fails. This implies that configuration in the CID file is incorrect.
SCL Parsing Done
This message is logged when the incoming CID file parsing is complete.
IED <IED name>: multiple instances
This message is logged when multiple instances of IED are detected. The CID file requires correction.
Private section: Error GE_Authentication_Code
This message is logged when CRC check of Private section fails. Read the IID file either from the IED or EnerVista software,
and update the Private section of the CID file from the read IID file.
security_check_private_settings: <MODBUS address in hex>(<MODBUS address in decimal>-<format code>)
<MODBUS name> = <value>, No permission for <user role>
This message is logged when the role used to write the CID file does not have the write permission.
security_check_private_settings: invalid addr <MODBUS address in hex>
This message is logged when an invalid MODBUS address is detected.
Private section: Error order code or firmware version
This message is logged when a matching IP address is not detected in the ConnectedAPs for the target. Or, it is also logged
when the order code and firmware revision used to generate the CID file differ from that currently running in the relay. A
minor revision mismatch is tolerated.
UR SERIES – COMMUNICATIONS GUIDE
3-155