If, in this case, line voltage supervision is added, then rather than setting 989 to open state,
specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0

Interlocking for line bay ABC_LINE (3)

Application
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 184. The function
can also be used for a double busbar arrangement without transfer busbar or a single
busbar arrangement with/without transfer busbar.
289
189
189G
152
289G
989
ANSI04000478 V1 EN
Figure 184:
Switchyard layout ABC_LINE (3)
The interlocking functionality in 650 series can not handle the transfer bus
WA7(C).
WA1 (A)
WA2 (B)
WA7 (C)
789
989G
en04000478_ansi.vsd
Section 11
Control