Figure 147:
Application principles for reservation with external wiring
The solution in figure
147
application example in figure 148.
IED
IED
. . .
IEC09000260 V2 EN
Figure 148:
Application principle for an alternative reservation solution
Bay control (QCBAY)
The Bay control (QCBAY) is used to handle the selection of the operator place for the bay.
The function gives permission to operate from two types of locations either from Remote
(for example, control centre or station HMI) or from Local (local HMI on the IED) or from
all (Local and Remote). The Local/Remote switch position can also be set to Off, which
means no operator place selected that is, operation is not possible neither from local nor
from remote.
IED
SCSWI
RES_EXT
SELECTED
Other SCSWI in the bay
BI
can also be realized over the station bus according to the
SCSWI
RES_EXT
SELECTED
GOOSEINTLKRCV
Other SCSWI in the bay to SELGGIO
RESGRANT
Section 11
Control
OR
BO
ANSI09000259-1-en.vsd
SELGGIO