Section 11
Control
11.4.3
342
QCBAY also provides blocking functions that can be distributed to different apparatuses
within the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
The function does not have a corresponding functionality defined in the IEC 61850
standard, which means that this function is included as a vendor specific logical node.
IEC13000016 V1 EN
Figure 149:
APC - Local remote function block

Interaction between modules

A typical bay with apparatus control function consists of a combination of logical nodes
or functions that are described here:
1MRK 506 334-UUS A
IEC13000016-1-en.vsd
Application manual