Calculating Settings For Step 2 - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
3.1.10.3
Application manual
where k is the transient overreach (due to fault current DC-component) of the
overcurrent function. For the four step residual overcurrent function, k = 1.05.
2.
Set t1 to 0 s

Calculating settings for step 2

1.
Set Pickup2 to 140 % of IBase
To assure that step 2 detects all short circuits on the line a phase-phase-ground and
phase-ground short circuit is applied at point 1 (the adjacent busbar), see figure 24.
The source impedance at line end A should be maximized (minimum short circuit
power) at this calculation. The residual current works out as
3I
= 2.39 kA
0AB,min
If possible the delay of 3I
(normally 0.4 s). To assure selectivity with this time delay the function should not
overreach adjacent lines out from the remote busbar and out from the local busbar.
To assure selectivity to ground-fault current protections of the other lines going out
from the remote busbar the following calculations shall be made.
A
REL 650
Y
ANSI11000116 V1 EN
Figure 24:
Fault case for step 2 calculation
The calculated fault current fed to the protection is 3I
current fed to the fault point is 3I
overcurrent protection at line B – C is 3I
ground-fault protection at an ground-fault at step 1 reach can be calculated:
=
3
I
3
I
, 0
sel
0
BC
,
step
1
GUID-C1EC0C94-A9F7-4C8D-A0F2-1A63076EFC04 V1 EN
>> should be set equal to the distance protection zone 2
0
Step 2- reach
Step 1- reach
Z 1 = R 1 + jX 1
Z 0 = R 0 + jX0
Communication
. The step 1 setting of the four step residual
0,BC
0BC,step1
3
I
×
, 0
AB
3
I
, 0
BC
REL650 setting examples
B
REL 650
Step 1- reach
Y
Step 2- reach
. The calculated total fault
0,AB
. The current measured by the
Section 3
C
ANSI11000116_1_en.vsd
(Equation 24)
73