Section 11
Control
11.8.2
11.8.3
11.9
11.9.1
11.9.2
11.9.3
388

Application

The IEC61850 generic communication I/O functions (DPGGIO) function block is used to
send three logical outputs to other systems or equipment in the substation. The three inputs
are named OPEN, CLOSE and VALID, since this function block is intended to be used as
a position indicator block in interlocking and reservation station-wide logics.
Setting guidelines
The function does not have any parameters available in the local HMI or PCM600.
Single point generic control 8 signals SPC8GGIO
Identification
Function description
Single point generic control 8 signals
Application
The Single point generic control 8 signals (SPC8GGIO) function block is a collection of
8 single point commands, designed to bring in commands from REMOTE (SCADA) to
those parts of the logic configuration that do not need complicated function blocks that
have the capability to receive commands (for example SCSWI). In this way, simple
commands can be sent directly to the IED outputs, without confirmation. Confirmation
(status) of the result of the commands is supposed to be achieved by other means, such as
binary inputs and SPGGIO function blocks.
PSTO is the universal operator place selector for all control functions.
Even if PSTO can be configured to allow LOCAL or ALL operator
positions, the only functional position usable with the SPC8GGIO
function block is REMOTE.
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GGIO) function are set
via the local HMI or PCM600.
IEC 61850
IEC 60617
identification
identification
SPC8GGIO
-
1MRK 506 334-UUS A
ANSI/IEEE C37.2
device number
-
Application manual