Application

SP16GGIO function block is used to send up to 16 logical signals to other systems or
equipment in the substation. Inputs should be connected in ACT tool.
Setting guidelines
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
IEC61850 generic communication I/O functions
MVGGIO
Identification
Function description
IEC61850 generic communication I/O
functions
Application
IEC61850 generic communication I/O functions (MVGGIO) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation.
It can also be used inside the same IED, to attach a RANGE aspect to an analog value and
to permit measurement supervision on that value.
Setting guidelines
The settings available for IEC61850 generic communication I/O functions (MVGGIO)
function allows the user to choose a deadband and a zero deadband for the monitored
signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and
low-low ranges of the measured value. The actual range of the measured value is shown
on the range output of MVGGIO function block. When a Measured value expander block
(MVEXP) is connected to the range output, the logical outputs of the MVEXP are changed
accordingly.
IEC 61850
IEC 60617
identification
identification
MVGGIO
-
1MRK 506 334-UUS A
ANSI/IEEE C37.2
device number
-
Application manual