Configuration Setting - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
11.5.9.2
376
189
189G
DB_BUS_A
152
6189
989
989G
ANSI04000518 V1 EN
Figure 183:
Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined.
DB_BUS_A (3) handles the circuit breaker QA1 that is connected to busbar WA1 and the
disconnectors and earthing switches of this section. DB_BUS_B (3) handles the circuit
breaker QA2 that is connected to busbar WA2 and the disconnectors and earthing
switches of this section.
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE and DB_BUS_B
must be used.

Configuration setting

For application without 989 and 989G, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE
and 1=TRUE:
989_OP = 1
989_CL = 0
989G_OP = 1
989G_CL = 0
289
252
289G
6289
1MRK 506 334-UUS A
WA1 (A)
WA2 (B)
489G
DB_BUS_B
589G
389G
DB_LINE
en04000518_ansi.vsd
Application manual