Section 12
Scheme communication
12.1.3.2
12.1.3.3
12.1.3.4
398
tSendMin
Set
= 0 s
Unblock
Disabled
Set
=
(Set to
used.
Set to
Set
tSecurity
= 0.035 s

Delta blocking scheme

Set
Operation
=
Enabled
SchemeType
DeltaBlocking
Set
=
tCoord
Set
= 0 s
tSendMin
Set
= 0 s
Set
Unblock
=
Disabled
(Set to
used.
Set to
tSecurity
Set
= 0.035 s
Set
DeltaI
= 10 %IB
DeltaV
Set
= 5 %VB
Delta3I0
Set
= 10 %IB
Delta3V0
Set
= 5 %VB
Permissive underreaching scheme
Operation
Enabled
Set
=
Set
SchemeType
=
Permissive UR
tCoord
Set
= 0 ms
tSendMin
Set
= 0.1 s
Unblock
Disabled
Set
=
Set
tSecurity
= 0.035 s
Permissive overreaching scheme
Set
Operation
=
Enabled
Scheme type
Permissive OR
Set
=
tCoord
Set
= 0 ms
tSendMin
Set
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Disabled
tSecurity
Set
= 0.035 s
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
Restart if Unblocking scheme with alarm for loss of guard is to be used)
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
Restart if Unblocking scheme with alarm for loss of guard is to be used)
1MRK 506 334-UUS A
Application manual