Function description
Instantaneous phase overcurrent
protection, phase segregated output
Application
Long transmission lines often transfer great quantities of electric power from production
to consumption areas. The unbalance of the produced and consumed electric power at
each end of the transmission line is very large. This means that a fault on the line can easily
endanger the stability of a complete system. The transient stability of a power system
depends mostly on three parameters (at constant amount of transmitted electric power):
The type of the fault. Three-phase faults are the most dangerous, because no power
can be transmitted through the fault point during fault conditions.
The magnitude of the fault current. A high fault current indicates that the decrease of
transmitted power is high.
The total fault clearing time. The phase angles between the Electro motive forces
(EMFs) of the generators on both sides of the transmission line increase over the
permitted stability limits if the total fault clearing time, which consists of the
protection operating time and the breaker opening time, is too long.
The fault current on long transmission lines depends mostly on the fault position and
decreases with the distance from the generation point. For this reason the protection must
operate very quickly for faults very close to the generation (and relay) point, for which
very high fault currents are characteristic.
The instantaneous phase overcurrent protection phase segregated output SPTPIOC (50)
can operate in 10 ms for faults characterized by very high currents.
Setting guidelines
The parameters for Instantaneous phase overcurrent protection phase segregated output
SPTPIOC (50) are set via the local HMI or Protection and Control Manager (PCM600).
IEC 61850
IEC 60617
identification
identification
SPTPIOC
3I>>
SYMBOL-Z V1 EN
1MRK 506 334-UUS A
ANSI/IEEE C37.2
device number
50
Application manual