The following trip parameters can be set to regulate tripping.
Program
Set the required tripping scheme depending on value selected 3 phase or 1p/3p.
Operation
Sets the mode of operation. Disabled switches the tripping off. The normal selection is
Enabled.
TripLockout
Sets the scheme for lock-out. Disabled only activates lock-out output. Enabled activates
the lock-out output and latching output contacts. The normal selection is Disabled.
AutoLock
Sets the scheme for lock-out. Disabled only activates lock-out through the input
SETLKOUT. Enabled also allows activation from trip function itself and activates the
lockout output. The normal selection is Disabled.
tTripMin
Sets the required minimum duration of the trip pulse. It should be set to ensure that the
breaker is tripped and if a signal is used to initiate the Breaker failure protection phase
segregated activation and output CSPRBRF (50BF) function longer than the back-up trip
timer in CSPRBRF (50BF). Normal setting is 0.150s.

Trip matrix logic TMAGGIO

Identification
Function description
Trip matrix logic
Application
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route trip
signals and other logical output signals to the tripping logics SMPPTRC and SPTPTRC
or to different output contacts on the IED.