ABB REL650 Applications Manual page 356

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
350
be used. For B1B2_BS, corresponding signals from busbar B are used. The same type of
module (A1A2_BS) is used for different busbars, that is, for both bus-section circuit
breakers A1A2_BS and B1B2_BS.
Signal
189OPTR
189 is open.
289OPTR
289 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
EXDU_BS
No transmission error from the bay BS (bus-section coupler bay) that contains the
above information.
For a busbar grounding switch, these conditions from the A1 busbar section are valid:
189OPTR (bay 1/sect.A1)
. . .
. . .
. . .
189OPTR (bay n/sect.A1)
DCOPTR (A1/A2)
VP189TR (bay 1/sect.A1)
. . .
. . .
. . .
VP189TR (bay n/sect.A1)
VPDCTR (A1/A2)
EXDU_BB (bay 1/sect.A1)
. . .
. . .
. . .
EXDU_BB (bay n/sect.A1)
EXDU_DC (A1/A2)
ANSI04000506 V1 EN
Figure 153:
Signals from any bays in section A1 to a busbar grounding switch in the
same section
For a busbar grounding switch, these conditions from the A2 busbar section are valid:
BB_DC_OP
AND
VP_BB_DC
AND
EXDU_BB
AND
en04000506_ansi.vsd
1MRK 506 334-UUS A
Application manual