Section 3
REL650 setting examples
50
Each individual tower foot has a resistance to ground up to 100 Ω, as the soil has very
high resistivity. The towers are however connected to each other via the shield wire
at the top of the towers, grounded to every tower. The effective tower footing
resistance is thus maximum 10 Ω.
R ≈ R
+ R
arc
towerfoot
This is the minimum value for the fault resistance reach RFPG1 setting. It can be
valuable to have much higher RFPG1 setting. it is proposed to set RFPG1 to 2 · Z1
(should never be larger than 4.5 · X1, where X1 is the reactive part of Z1):
In case of load transfer at the line there is a risk of phase shift of the fault resistance
that moves the apparent impedance into the zone 1 characteristic even if the fault is
external.
X
20
Line impedance
15
10
5
5
IEC09000411 V1 EN
Figure 8:
Load current compensation for zone 1 (quadrilateral characteristic)
The built in load current compensation of the zone 1 characteristic prevents
unwanted trip. This load compensation feature is present in zone 1 phase to ground
measuring element for quadrilateral characteristic.
7.
Set OpModetPGZ1 to Enabled.
Zone 1 phase to ground loop gives trip.
8.
Set OpModetPPZ1 to Enabled.
= 1.1 + 10 Ω
Load current compensation
10
15
1MRK 506 334-UUS A
A
Resistive fault at load export
20
25
30
IEC09000411-1-en.vsd
Application manual
Rf
R