ABB REL650 Applications Manual page 368

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
362
Signal
189OPTR
189 is open.
289OPTR
289 is open.
VP189TR
The switch status of 189 is valid.
VP289TR
The switch status of 289 is valid.
EXDU_BS
No transmission error from the bay BS (bus-section coupler bay) that contains the
above information.
For a bus-section disconnector, these conditions from the A1 busbar section are valid:
189OPTR (bay 1/sect.A1)
. . .
. . .
. . .
189OPTR (bay n/sect.A1)
VP189TR (bay 1/sect.A1)
. . .
. . .
. . .
VP189TR (bay n/sect.A1)
EXDU_BB (bay 1/sect.A1)
. . .
. . .
. . .
EXDU_BB (bay n/sect.A1)
ANSI04000494 V1 EN
Figure 166:
Signals from any bays in section A1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the A2 busbar section are valid:
189OPTR (bay 1/sect.A2)
. . .
. . .
. . .
189OPTR (bay n/sect.A2)
DCOPTR (A2/A3)
VP189TR (bay 1/sect.A2)
. . .
. . .
. . .
VP189TR (bay n/sect.A2)
VPDCTR (A2/A3)
EXDU_BB (bay 1/sect.A2)
. . .
. . .
. . .
EXDU_BB (bay n/sect.A2)
EXDU_DC (A2/A3)
ANSI04000495 V1 EN
Figure 167:
Signals from any bays in section A2 to a bus-section disconnector
S1DC_OP
AND
VPS1_DC
AND
EXDU_BB
AND
en04000494_ansi.vsd
S2DC_OP
AND
VPS2_DC
AND
EXDU_BB
AND
en04000495_ansi.vsd