ABB REL650 Applications Manual page 130

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 6
Impedance protection
124
Parallel line out of service and not grounded
A
OPEN
CLOSED
21
ANSI05000223 V1 EN
Figure 58:
Parallel line is out of service and not grounded
When the parallel line is out of service and not grounded, the zero sequence on that line
can only flow through the line admittance to the ground. The line admittance is high which
limits the zero-sequence current on the parallel line to very low values. In practice, the
equivalent zero-sequence impedance circuit for faults at the remote bus bar can be
simplified to the circuit shown in figure
The line zero sequence mutual impedance does not influence the measurement of the
distance protection in a faulty circuit. This means that the reach of the underreaching
distance protection zone is reduced if, due to operating conditions, the equivalent zero
sequence impedance is set according to the conditions when the parallel system is out of
operation and grounded at both ends.
-
Z
Z
0
0m
I
0
A
-
Z
Z
0
0m
B
IEC09000255 V1 EN
Figure 59:
Equivalent zero-sequence impedance circuit for a double-circuit line with
one circuit disconnected and not grounded
The reduction of the reach is equal to equation 45.
(
1
×
×
+
2
Z
Z
1
0
E
3
=
K
U
(
)
1
×
×
+
2
Z
Z
1
0
3
EQUATION1284 V1 EN
B
OPEN
Z0m
CLOSED
21
en05000223_ansi.vsd
58
Z
0m
I
0
C
IEC09000255_1_en.vsd
)
+
R
Z
f
= -
1
(
×
×
Z
2
Z
+
R
1
0
f
1MRK 506 334-UUS A
2
m
0
)
+
+
Z
3
R
0
f
Application manual
(Equation 45)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents