Setting Examples - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 14
Monitoring
14.4.4
434
Magnitude
% of In
compensation
+10
IMagComp5
IMagComp30
IMagComp100
5
-10
Angle
Degrees
compensation
+10
IAngComp30
IAngComp5
IAngComp100
5
-10
ANSI05000652 V3 EN
Figure 208:
Calibration curves

Setting examples

Three setting examples, in connection to Measurement function (CVMMXN), are
provided:
Measurement function (CVMMXN) application for a 380kV OHL
Measurement function (CVMMXN) application on the secondary side of a
transformer
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters values will
be provided.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
30
0-5%:
Constant
5-30-100%: Linear
>100%:
Constant
30
1MRK 506 334-UUS A
Measured
current
100
% of In
Measured
current
100
% of In
ANSI05000652_3_en.vsd
Application manual