1MRK 506 334-UUS A
8.3.3.4
Application manual
residual sum will have the same value as the remaining phase-to-ground voltage. See
Figure
124.
ANSI07000189 V1 EN
Figure 124:
Ground fault in Direct grounded system
Settings for Two step residual overvoltage protection
GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(VBase) and (SBase).
Operation: Disabled or Enabled
VBase is used as voltage reference for the voltage. The voltage can be fed to the IED in
different ways:
1.
The IED is fed from a normal voltage transformer group where the residual voltage
is created from the phase-to-ground voltages within the protection software.
2.
The IED is fed from a broken delta connection normal voltage transformer group. In
an open delta connection the protection is fed by the voltage 3V0 (single input). The
Voltage protection
ANSI07000189-1-en.vsd
Section 8
265