Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
Application manual
FDPSPDIS (21)
I3P*
TRIP
V3P*
PICKUP
BLOCK
FWD_A
DIRCND
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
NDIR_A
NDIR_B
NDIR_C
NDIR_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
STCNDZI
DLECND
ANSI10000194 V1 EN
Figure 73:
The connection of Phase preference logic function (PPLPHIZ) between
Five zone distance protection, quadrilateral and mho characteristic
(ZQMPDIS, 21) and Phase selection with load encroachment,
quadrilateral characteristic function (FDPSPDIS, 21)
As the fault is a double ground-faults at different locations of the network, the fault current
in the faulty phase on each of the lines will be seen as a phase current and at the same time
as a neutral current as the remaining phases on each feeder virtually carries no (load)
current. A current through the grounding impedance does not exist. It is limited by the
impedance to below the typical, say 25 to 40 A. Occurring neutral current is thus a sign of
a cross-country fault (a double ground- fault)
ANSI06000553 V1 EN
Figure 74:
The currents in the phases at a double ground fault
PPLPHIZ
I3P*
PICKUP
V3P
ZREL
BLOCK
RELAG
RELBG
RELCG
PHSEL
IC=IG
IA=IG
en06000553_ansi.vsd
Section 6
Impedance protection
ZQDPDIS (21)
I3P*
TRIP
V3P*
TRZ1
BLOCK
TRZ2
BLKZ
TRZ3
BLKTR
TRZ4
PHSEL
TRZ5
DIRCND
PICKUP
BLKPG
PU_Z1
BLKPP
PU_Z2
Z3_PU
Z4_PU
Z5_PU
STND1
STND2
STND3
STND4
STND5
ANSI10000194_1_en.vsd
155