Measurement function application for a 380kV OHL

Single line diagram for this application is given in figure 209:
380kV Busbar
800/5 A
380kV 120V
/
kV
3
3
P
Q
380kV OHL
ANSI09000039 V1 EN
Figure 209:
Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in
figure
209
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel PhaseAngleRef (see
settings for analog input modules in PCM600) using PCM600 for analog input
channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
general settings as shown in table 20.
level supervision of active power as shown in table 21.
calibration parameters as shown in table 22.
IED
ANSI09000039-1-en.vsd
Section 14
Monitoring
435