GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(VBase) and (SBase).
SummationType: Summation type (Group 1 + Group 2, Group 1 - Group 2, Group 2 -
Group 1 or –(Group 1 + Group 2)).
DFTReference: The reference DFT block (InternalDFT Ref,DFTRefGrp1 or External
DFT ref) .
FreqMeasMinVal: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of VBase (for each instance x).

Global base values GBASVAL

Identification
Function description
Global base values
Application
Global base values function (GBASVAL) is used to provide global values, common for
all applicable functions within the IED. One set of global values consists of values for
current, voltage and apparent power and it is possible to have six different sets.
This is an advantage since all applicable functions in the IED use a single source of base
values. This facilitates consistency throughout the IED and also facilitates a single point
for updating values when necessary.
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one out of
the six sets of GBASVAL functions.
Setting guidelines
VBase: Phase-to-phase voltage value to be used as a base value for applicable functions
throughout the IED.
IBase: Phase current value to be used as a base value for applicable functions throughout
the IED.
IEC 61850
IEC 60617
identification
identification
GBASVAL
-
Section 17
Basic IED functions
ANSI/IEEE C37.2
device number
-
483