Configuration Setting - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
11.5.11.3
384
Section 1
(WA1)A1
(WA2)B1
(WA7)C
AB_TRAFO
ABC_BC
ANSI04000487 V1 EN
Figure 189:
Busbars divided by bus-section disconnectors (circuit breakers)
The interlocking functionality in 650 series cannot handle the transfer bus
(WA7)C.
The project-specific logic for input signals concerning bus-coupler are the same as the
specific logic for the line bay (ABC_LINE):
Signal
BC_12_CL
A bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from bus-coupler bay (BC).
The logic is identical to the double busbar configuration "Signals from bus-coupler".

Configuration setting

If there are no second busbar B and therefore no 289 disconnector, then the interlocking
for 289 is not used. The state for 289, 2189G, BC_12 are set to open by setting the
appropriate module inputs as follows. In the functional block diagram, 0 and 1 are
designated 0=FALSE and 1=TRUE:
289_OP = 1
289QB2_CL = 0
2189G_OP = 1
2189G_CL = 0
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
en04000487_ansi.vsd
1MRK 506 334-UUS A
A2
B2
C
ABC_BC
Application manual