ABB REL650 Applications Manual page 35

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
Application manual
132 kV Bus
132kV/110V
189
289
289G
52
389G
1000/5
989
989G
132kV/110V
Line data
Line length : 50Km
Positive sequence line impedance:0. 195+j*0. 410Ohms Primary/Km
Zero sequence line impedance:0. 400+j*1. 310Ohms Primary/Km
Other configured functions
85
85
ZC PSCH
ZCWS PSCH
Cond
Cond
TCS SCBR
SPVN ZBAT
ANSI11000131 V2 EN
Figure 4:
A typical protection application for quadrilateral characteristic distance
zones in a single breaker arrangement, single pole tripping
BUS1
BUS2
132kV/110V
52PD
PD
CC RPLD
50BF 3I>BF
50
3I >>
CSP RBRF
SPT PIOC
68
Meter.
CV MMXN
ZM RPSB
Wh<->
ETP MMTR
59
U>
27
U<
OV2 PTOV
UV2 PTUV
85
85
Mont.
EC PSCH
ECRW PSCH
DRP RDRE
Section 2
Application
REL650A11A-5 DistanceZones,
1PH/3 PH Tripping Single Breaker
10AI(4I+1I+5U)
79
0->1
94
1->0
STB RREC
STP PTRC
Meter.
Meter.
C MMXU
C MSQI
SDD RFUF
I>
46
Iub
Cond
50STB
STB PTOC
BRC PTOC
S SCBR
q>
50N
IN>>
26
37
2I<
EF PIOC
LFPTTR
SDE PSDE
51/67
3I>
IN >
SOTF
51N/67N
OC4S PTOC
EF4 PTOC
ZCV PSOF
21
Z<->
Ph Sel
21
Z<
ZDN RDIR
FMPS PDIS
ZQM PDIS
Monit.
LMB RFLO
27
U<
Meter.
Meter.
LOV PTUV
V MMXU
V MSQI
VN MMXU
Function Enabled
Function Disabled
in Settings
in Settings
ANSI
IEC
ANSI
IEC
IEC61850
IEC61850
ANSI11000131-2-en.vsd
25 SYNC
SES RSYN
Meter.
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents