Event Counter Cntggio - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
14.5
14.5.1
14.5.2
14.5.3
Application manual
Table 22:
Settings for calibration parameters
Setting
Short Description
IMagComp5
Magnitude factor to calibrate
current at 5% of In
IMagComp30
Magnitude factor to calibrate
current at 30% of In
IMagComp100
Magnitude factor to calibrate
current at 100% of In
VAmpComp5
Magnitude factor to calibrate
voltage at 5% of Vn
VMagComp30
Magnitude factor to calibrate
voltage at 30% of Vn
VMagComp100
Magnitude factor to calibrate
voltage at 100% of Vn
IAngComp5
Angle calibration for current at 5%
of In
IAngComp30
Angle pre-calibration for current
at 30% of In
IAngComp100
Angle pre-calibration for current
at 100% of In

Event counter CNTGGIO

Identification
Function description
Event counter
Application
Event counter (CNTGGIO) has six counters which are used for storing the number of
times each counter has been activated. CNTGGIO can be used to count how many times
a specific function, for example the tripping logic, has issued a trip signal. All six counters
have a common blocking and resetting feature.
Setting guidelines
Operation: Sets the operation of Event counter (CNTGGIO) Enabled or Disabled.
Selected
Comments
value
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
IEC 61850
IEC 60617
identification
identification
CNTGGIO
S00946 V1 EN
Section 14
Monitoring
ANSI/IEEE C37.2
device number
-
437

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents