Calculating General Settings - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 3
REL650 setting examples
3.1.3.1
46

Calculating general settings

1.
Set GlobalBaseSel to 1
2.
Set LineAng to 81.9º
The positive sequence impedance line angle for the protected line is calculated as
=
LineAng
arctan
GUID-A8BDC47F-A097-42F4-9C1F-DA6AB2D6AC1A V1 EN
3.
Set CharPGZx and CharPPZx to Mho, Quadrilateral and Combined as per the
application for each zone.
4.
Set KN-factors
4.1. Set KNMag1 to 0.62
for Zone 1
4.2. Set KNAng1 to -0.6º
for Zone 1
4.3. Set KNMag2 to 0.62
For Zones 2, 3, 4, 5
4.4. Set KNAng2 to -0.6º
for Zones 2,3,4 and 5
the KN-factor is calculated for correct reach for phase-to-ground faults . The
definition of the KN-factor is:
-
Z
Z
=
, 0
line
, 1
line
KN
Z
, 1
line
GUID-201DAAE3-7D9E-48B9-9CCA-33B5C2E51103 V1 EN
For phase-to-ground fault loops the apparent impedance is defined as:
V
=
ph Ln
,
Z
-
ph ea
+
× ×
I
KN
3
ph Ln
,
GUID-509FDDAF-4B92-4DD5-A9A9-B2214B58E383-ANSI V1 EN
The magnitude and phase angle are set separately as KN is a complex value. The
KN-factor can be set separately for zone 1 and for the other zones. This is mainly for
application for double circuit lines where zone 1 should be set to assure underreach
and the other zones should be set to assure overreach. For a single circuit line it is
recommended to set the KN-factors to the same values.
Let Z
= 2.5 + j17.5 and Z
1,line
æ
ö
æ
ö
X
17
5 .
ç ç
÷ ÷
=
ç
÷
line
arctan
R
2
5 .
è
ø
è
ø
line
I
0
= 7.5 + j17.5, then KN is calculated as:
0,line
1MRK 506 334-UUS A
=
°
81
9 .
Application manual
(Equation 1)
(Equation 2)
(Equation 3)