Section 11
Control
336
Figure
144
gives an overview from what places the apparatus control function receive
commands. Commands to an apparatus can be initiated from the Control Centre (CC), the
station HMI or the local HMI on the IED front.
Station HMI
Local
HMI
IED
Apparatus
Apparatus
Control
CLOSE/OPEN
CLOSE/OPEN
breakers disconnectors grounding switches
ANSI08000227 V1 EN
Figure 144:
Overview of the apparatus control functions
Features in the apparatus control function:
Operation of primary apparatuses
Select-Execute principle to give high security
Selection function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchronism check
Operation counter
Suppression of Mid position
The apparatus control function is realized by means of a number of function blocks
designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI