Examples On How To Connect A Three Phase-To-Ground Connected Vt To The Ied - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
4.2.4.3
Application manual
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
100 V
110 V
115 V
120 V
230 V
The IED fully supports all of these values and most of them will be shown in the following
examples.
Examples on how to connect a three phase-to-ground connected VT to the
IED
Figure
43
gives an example on how to connect the three phase-to-ground connected VT
to the IED. It as well gives overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
For correct terminal designations, see the connection diagrams valid for
the delivered IED.