Section 11
Control
11.2.2.13
310
SMBRREC (79)
BJ-TRIP
OR
ZCVPSOF-TRIP
CCRBRF (50BF)
TRBU
ANSI11000168 V1 EN
Figure 137:
Lock-out arranged with an external Lock-out relay
SMBRREC (79)
BU-TRIP
OR
INHIBIT
ZCVPSOF-TRIP
UNSUCCL
CCRBRF (50BF)
SOFTWARE
OR IO RESET
TRBU
MAN CLOSE
SMBRREC (79) CLOSE
SESRSYN (25)
AUTOSTOP
MANENOK
ANSI11000167 V1 EN
Figure 138:
Lock-out arranged with internal logic with manual closing going through
in IED

Automatic continuation of the reclosing sequence

SMBRREC (79) function can be programmed to proceed to the following reclosing shots
(if multiple shots are selected) even if start signals are not received from the protection
functions, but the breaker is still not closed. This is done by setting parameter AutoCont =
Enabled and tAutoContWait to the required delay for the function to proceed without a
new start.
INHIBIT
UNSUCCL
OR
SMPPTRC (94)
OR
SETLKOUT
RESET LOCK-OUT
RSTLKOUT
OR
OR
1MRK 506 334-UUS A
Lock-out
RXMD1
11
21
12
CLOSE COMMAND
MAIN ZAK CLOSE
ANSI11000168
CLLKOUT
AND
CLOSE COMMAND
ANSI11000167_1_en.vsd
Application manual
_2_en.vsd