ABB REL650 Applications Manual page 193

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
Application manual
IEC05000204 V1 EN
Figure 89:
Fault time with maintained selectivity
To assure selectivity between different protections, in the radial network, there have to be
a minimum time difference Dt between the time delays of two protections. The minimum
time difference can be determined for different cases. To determine the shortest possible
time difference, the operation time of protections, breaker opening time and protection
resetting time must be known. These time delays can vary significantly between different
protective equipment. The following time delays can be estimated:
Protection operation
15-60 ms
time:
Protection resetting time:
15-60 ms
Breaker opening time:
20-120 ms
Example for time coordination
Assume two substations A and B directly connected to each other via one line, as shown
in the figure 90. Consider a fault located at another line from the station B. The fault
current to the overcurrent protection of IED B1 has a magnitude so that the protection will
Section 7
Current protection
en05000204.wmf
187