Single Circuit Breaker With Double Busbar, External Voltage Selection - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
11.1.3.2
Application manual

Single circuit breaker with double busbar, external voltage selection

Bus 1
Bus 2
Fuse
Fuse
VT
VT
BKR1
ANSI11000165 V2 EN
Figure 133:
Connection of SESRSYN (25) function block in a single breaker, double
busbar arrangement with external voltage selection
In this type of arrangement no internal voltage selection is required. The voltage selection
is made by external relays typically connected according to figure 133. Suitable voltage
and VT fuse failure supervision from the two busbars are selected based on the position of
the busbar disconnectors. This means that the connections to the function block will be the
same as for the single busbar arrangement. The voltage selection parameter CBConfig is
set to No voltage sel.
189
SMAI
VBus
289
52
SMAI
VLine
Fuse
VT
Line
Section 11
Control
SESRSYN (25)
V3PB1*
SYNOK
GRP_OFF
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
FRDIFSYN
VB1FF
FRDERIVA
VB2OK
VOKSC
VB2FF
VDIFFSC
VL1OK
FRDIFFA
VL1FF
PHDIFFA
VL2OK
FRDIFFM
VL2FF
PHDIFFM
STARTSYN
INADVCLS
TSTSYNCH
VDIFFME
TSTSC
FRDIFFME
TSTENERG
PHDIFFME
AENMODE
Vbus
MENMODE
VLine
MODEAEN
MODEMEN
ANSI11000165-2-en.vsd
295

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents