Section 11
Control
11.1.3.3
296

Single circuit breaker with double busbar, internal voltage selection

Bus 1
Bus 2
Fuse
Fuse
VT
VT
189
289
BKR1
52
Line
ANSI10000196 V2 EN
Figure 134:
Connection of the SESRSYN (25) function block in a single breaker,
double busbar arrangement with internal voltage selection.
When internal voltage selection is needed, the voltage transformer circuit connections are
made according to figure 134. The voltage from busbar1 VT is connected to V3PB1 and
the voltage from busbar2 VT is connected to V3PB2. The voltage from the line VT is
connected to V3PL1. The positions of the disconnectors and VT fuses shall be connected
as shown in figure 134. The voltage selection parameter CBConfig is set to Double bus.
SMAI
VBus1
SMAI
VBus2
SMAI
VLine
Fuse
VT
1MRK 506 334-UUS A
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
GRP_OFF
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
FRDIFSYN
VB1FF
FRDERIVA
VB2OK
VOKSC
VB2FF
VDIFFSC
VL1OK
FRDIFFA
VL1FF
PHDIFFA
VL2OK
FRDIFFM
VL2FF
PHDIFFM
STARTSYN
INADVCLS
TSTSYNCH
VDIFFME
TSTSC
FRDIFFME
TSTENERG
PHDIFFME
AENMODE
Vbus
MENMODE
VLine
MODEAEN
MODEMEN
ANSI10000196-2-en.vsd
Application manual