Section 16
Station communication
462
Stationbus
IED1
IED2
IED3
IED1
DO1/DA1
IED1
IED1
DO1/DA2
IED1
IED1
DO2/DA1
IED1
IED1
DO2/DA2
IED1
IED1
DO3/DA1
IED1
IED1
DO3/DA2
IED1
FBa
FBb
FBc
PLC Program
IEC08000145 V1 EN
Figure 217:
SMT: GOOSE principle and signal routing with SMT
Special function blocks take the data set and present it via the function block as output
signals for application functions in the application configuration. Different GOOSE
receive function blocks are available for the specific tasks.
SMT links the different data object attributes (for example stVal or magnitude) to the
output signal to make it available for functions in the application configuration. When a
matrix cell array is marked red the IEC 61850–8–1 data attribute type does not fit together,
even if the GOOSE receive function block is the partner. SMT checks this on the content
of the received data set. See
DO1
DO1/DA1
DO1/DA2
DO3
DO2/DA1
SMT
DO2/DA2
DO3/DA1
DO2
DO3/DA2
Receive-FB
IEC08000145.vsd
Figure 218
1MRK 506 334-UUS A
DA1
DA2
DA1
DA1
DA2
DA2
DA1
DA2
Application manual