Setting Guidelines - ABB REL650 Applications Manual

Line distance protection relion 650 series
Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 334-UUS A
11.7.3
11.8
11.8.1
Application manual
(controlled by the PSTO input), giving switching commands through the CMDPOS12 and
CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integer
number 0 – 3.
An example where VSGGIO is configured to switch Autorecloser enabled–disabled from
a button symbol on the local HMI is shown in
the local HMI are normally used for enable–disable operations of the circuit breaker.
PSTO
INTONE
IPOS1
IPOS2
NAM_POS1
Disabled
NAM_POS2
Enabled
ANSI07000112 V2 EN
Figure 190:
Control of Autorecloser from local HMI through Selector mini switch

Setting guidelines

Selector mini switch (VSGGIO) function can generate pulsed or steady commands (by
setting the Mode parameter). When pulsed commands are generated, the length of the
pulse can be set using the tPulse parameter. Also, being accessible on the single line
diagram (SLD), this function block has two control modes (settable through CtlModel):
Dir Norm and SBO Enh.
IEC61850 generic communication I/O functions
DPGGIO
Identification
Function description
IEC 61850 generic communication I/O
functions
figure
VSGGIO
CMDPOS12
CMDPOS21
IEC 61850
identification
DPGGIO
Section 11
190. The Close and Open buttons on
INV
OUT
INPUT
SMBRREC_79
ON
SETON
OFF
IEC07000112-2-en_ansi.vsd
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Control